Organization 5.2 5.0 ADMINISTRATIVE CONTROLS 5.2 Organization 5.2.1 Onsite and Offsite Organizations Onsite and offsite organizations shall be established for unit operation and corporate management, respectively.

The onsite and offsite organizations shall include the positions for activities affecting safety of the nuclear power plant.

a.

Lines of authority, responsibility, and communication shall be defined and established throughout highest management levels, intermediate levels, and all operating organization positions.

These relationships shall be documented and updated, as appropriate, in organization charts, functional descriptions of departmental responsibilities and relationships, and job descriptions for key personnel positions, or in equivalent forms of documentation.

These requirements shall be documented in the FSAR.

b.

The Plant General Manager shall be responsible for overall safe operation of the plant and shall have control over those onsite activities necessary for safe operation and maintenance of the plant.

c.

The Chief Executive Officer shall have corporate responsibility for overall plant nuclear safety and shall take any measures needed to ensure acceptable performance of the staff in operating, maintaining, and providing technical support to the plant to ensure nuclear safety.

d.

The individuals who train the operating staff, carry out health physics, or perform quality assurance functions may report to the appropriate onsite manager; however, these individuals shall have sufficient organizational freedom to ensure their independence from operating pressures.

5.2.2 Unit Staff The unit staff organization shall include the following:

a.

At least two Equipment Operators shall be assigned when the unit is in MODE 1, 2. or 3; and at least one Equipment Operator shall be assigned when the unit is in MODE 4 or 5.

(continued)

Columbia Generating Station Amendment No. 44 1691 5.2-1

Organization 5.2 5.2 Organization 5.2.2 Unit Staffq (continued)

b.

Shift crew composition may be less than the minimum requirement of 10 CFR 50.54(m)(2)(i) and 5.2.2.a and 5.2.2.f for a period of time not to exceed 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> in order to accommodate unexpected absence of on-duty shift crew members provided immediate action is taken to restore the shift crew composition to within the minimum requirements.

c.

An individual qualified to implement radiation protection procedures shall be on site when fuel is in the reactor.

The position may be vacant for not more than 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, in order to provide for unexpected absence, provided immediate action is taken to fill the required position.

d.

Administrative procedures shall be developed and implemented to limit the working hours of personnel who perform safety related functions (e.g., licensed SROs, licensed ROs, health physicists, equipment operators, and key maintenance personnel).

The controls shall include guidelines on working hours that

-ensure adequate shift coverage shall be maintained without routine heavy use of overtime.

Any deviation from the above guidelines shall be authorized in advance by the Plant General Manager or his designee.

in accordance with approved administrative procedures, with documentation of the basis for granting the deviation.

Controls shall bd included in the procedures to require a periodic independent review be conducted to ensure that excessive hours have not been assigned.

Routine deviation from the working hour guidelines shall not be authorized.

e.

The Operations Manager or Assistant Operations Manager shall hold an SRO license.

f.

An individual shall provide advisory technical support to the unit operations shift crew in the areas of thermal hydraulics, reactor engineering, and plant analysis with regard to the safe operation of the unit.

This individual shall meet the qualifications specified by the Commission Policy Statement on Engineering Expertise on Shift.

Columbia Generating Station 5.2-2 Amendment No.

14,169*.,182

Unit Staff Qualifications 5.3 5.0 ADMINISTRATIVE COOTROLS 5.3 Unit Staff Qualifications 5.3.1 Each member of the unit staff shall meet or exceed the minimum qualifications of ANSI/ANS N18.1-1971, for comparable positions described in the FSAR, except for:

a.

The Operations Manager, who shall meet the requirements of ANSI/ANS N18.1-1971 with the exception that in lieu of meeting the stated ANSI/ANS requirement to hold a Senior Reactor Operator (SRO) license at the time of appointment to the position, the Operations Manager shall:

1.

Hold an SRO license at the time of appointment;

2.

Have held an SRO license; or

3.

Have been certified for equivalent SRO knowledge; and

b.

The Radiation Protection Manager, who shall meet or exceed the qualifications of Regulatory Guide 1.8, Revision 1-R, May 1977.

5.3.2 For the purpose of 10 CFR 55.4, a licensed Senior Reactor Operator (SRO) and a licensed Reactor Operator (RO) are those individuals who, in addition to meeting the requirements of TS 5.3.1, perform the functions described in 10 CFR 50.54(m).

Columbia Generating Station Amendment No.

44,16,* 182 5.3-1

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.3 Post Accident Sampling (continued)

c.

Provisions for maintenance of sampling and analysis equipment.

5.5.4 Radioactive Effluent Controls Program This program. conforming to 10 CFR 50.36a, provides for the control of radioactive effluents and for maintaining the doses to members of the public from radioactive effluents as low as reasonably achievable.

The program shall be contained in the

ODCM, shall be implemented by procedures.

and shall include remedial actions to be taken whenever the program limits are exceeded.

The program shall include the following elements:

a.

Limitations on the functional capability of radioactive liquid and gaseous monitoring instrumentation including surveillance tests and setpoint determination in accordance with the methodology in the ODCM;

b.

Limitations on the concentrations of radioactive material released in liquid effluents to unrestricted areas, conforming to 10 times the concentration values in Appendix B. Table 2. Column 2 to 10 CFR 20.1001

- 20.2402;

c.

Monitoring, sampling, and analysis of radioactive liquid and gaseous effluents pursuant to 10 CFR 20.1302 and with the methodology and parameters in the ODCM;

d.

Limitations on the annual and quarterly doses or dose commitment to a member of the public from radioactive materials in liquid effluents released from each unit to unrestricted areas, conforming to 10 CFR 50, Appendix I;

e.

Determination of cumulative and projected dose contributions from radioactive effluents for the current calendar quarter and current calendar year in accordance with the methodology and parameters in the ODCM at least every 31 days:

(continued)

Amendment No.

149..69,182 Columbia Generating Station 5.5-3

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.4 Radioactive Effluent Controls Program (continued)

f.

Limitations on the functional capability and use of the liquid and gaseous effluent treatment systems to ensure that appropriate portions of these systems are used to reduce releases of radioactivity when the projected doses in a period of 31 days would exceed 2% of the guidelines for the annual dose or dose commitment, conforming to 10 CFR 50, Appendix I;

g.

Limitations on the dose rate resulting from radioactive material released in gaseous effluents from the site to areas at or beyond the site boundary shall be limited to the following:

1.

For noble gases:

less than or equal to a dose rate of 500 mrems/yr to the whole body and less than or equal to a dose rate of 3000 mrems/yr to the skin, and

2.

For iodine-131, iodine-133, tritium, and for all radionuclides in particulate form with half lives

> 8 days:

less than or equal to a dose rate of 1500 mrems/yr to any organ:

h.

Limitations on the annual and quarterly air doses resulting from noble gases released in gaseous effluents from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I;

i.

Limitations on the annual and quarterly doses to a member of the public from iodine-131, iodine-133, tritium, and all radionuclides in particulate form with half lives > 8 days in gaseous effluents released from each unit to areas beyond the site boundary, conforming to 10 CFR 50, Appendix I:

j.

Limitations on the annual dose or dose commitment to any member of the public, beyond the site boundary, due to releases of radioactivity and to radiation from uranium fuel cycle sources, conforming to 40 CFR 190; and

k.

Limitations on venting and purging of the primary containment through the Standby Gas Treatment System to maintain releases as low as reasonably achievable.

(continued)

Columbia Generating Station Programs and Manuals Amendment No.

149,169,182 5.5-4

Programs and Manuals 5.5 5.5 Programs and Manuals' (continued) 5.5.4 ASME Boiler and Pressure Vessel Code and applicable Addenda terminology for inservice testing artivities Required Frequencies for performing inservice testing activities Weekly Monthly Quarterly or every 3 months Semiannually or every 6 months Every 9 months Yearly or annually Biennially or every 2 years At least once per At least once per 7 days 31 days At least once per 92 days At At At least least least once once once per 184 days per 276 days per 366 days At least once per 731 days (continued)

  • The Inservice Testing Program requirement for full stroke exercise testing at each refueling outage for TIP-V-6 shall not be required for the refueling outage conducted in the Spring, 1997.

This exception shall expire upon reaching MODE 4 for a plant shutdown of sufficient duration to allow TIP-V-6 testing, or May 15, 1998, whichever occurs first.

Amendment No.

44 9,169, 18 2 Columbia Generating Station Radioactive Effluent Controls Program (continued)

1.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Radioactive Effluent Controls Program surveillance frequency.

Component CYclic or Transient Limit This program provides controls to track the FSAR, Table 3.9-1.

Note 1, cyclic and transient occurrences to ensure that components are maintained within the design limits.

Inservice Testing Program This program provides controls for inservice testing of ASME Code Class 1. 2, and 3 pumps and valves.*

a.

Testing Frequencies specified in Section XI of the ASME Boiler and Pressure Vessel Code and applicable Addenda as follows:

5.5.5 5.5.6 activities S....

i I

5.5-5

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.6 Inservice Testing Program (continued)

b.

The provisions of SR 3.0.2 are applicable to the above required Frequencies for performing inservice testing activities;

c.

The provisions of SR 3.0.3 are applicable to inservice testing activities; and

d.

Nothing in the ASME Boiler and Pressure Vessel Code shall be construed to supersede the requirements of any TS.

5.5.7 Ventilation Filter Testing Program (VFTP)

The VFTP shall establish the required testing of Engineered Safety Feature (ESF) filter ventilation systems.

Tests described in Specification 5.5.7.a and 5.5.7.b shall be performed once per 24 months; after each complete or partial replacement of the HEPA filter train or charcoal adsorber filter; after any structural maintenance on the system housing; and, following significant painting, fire, or chemical release in any ventilation zone communicating with the system while it is in operation.

Tests described in Specification 5.5.7.c shall be performed once per 24 months; after 720 hours0.00833 days <br />0.2 hours <br />0.00119 weeks <br />2.7396e-4 months <br /> of system operation; after any structural maintenance on the system housing; and, following significant painting, fire, or chemical release in any ventilation zone communicating with the system while it is in operation.

Tests described in Specification 5.5.7.d and 5.5.7.e shall be performed once per 24 months.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the VFTP test Frequencies.

a.

Demonstrate for each of the ESF systems that an inplace test of the high efficiency particulate air (HEPA) filters shows a penetration and system bypass < 0.05% when tested in accordance with Regulatory Guide 1.52, Revision 2, and ASME N510o-1989 at the system flowrate specified below:

(continued)

Columbia Generating Station Amendment No.

1-49 i--6 182 5.5-6

Programs and Manuals 5.5 5.5 Programs and Manuals' 5.5.7 Ventilation Filter Testing Program (VFTP)

(continued)

ESF Ventilation System SGT System CREF System Flowrate (cfm) 4012 to 4902 900 to 1100

b.

Demonstrate for each of the ESF systems that an inplace test of the charcoal adsorber shows a penetration and system bypass < 0.05% when tested in accordance with Regulatory Guide 1.52, Revision 2, and ASME N510-1989 at the system flowrate specified below:

ESF Ventilation System SGT System CREF System Flowrate (cfm) 4012 to 4902 900 to 1100

c.

Demonstrate for each of the ESF systems that a laboratory test of a sample of the charcoal adsorber, when obtained as described in Regulatory Guide 1.52, Revision 2, shows the methyl iodide penetration less than the value specified below when tested in accordance with ASTM D3803-1989 at a temperature of 30 0C (86 0F) and the relative humidity specified below.

Testing of the SGT System will also be conducted at a face velocity of 75 feet per minute.

ESF Ventilation System SGT System CREF System Penetration (%)

0.5 2.5 Allowed tolerances in the above testing parameters of temperature, relative humidity, and face velocity are as specified in ASTM D3803-1989.

d.

Demonstrate for each of the ESF systems that the pressure drop across the combined HEPA filters and the charcoal adsorbers is less than the value specified below when tested at the system flowrate specified below:

ESF Ventilation System Delta P (inches wg)

SGT System CREF System

<8

<6 4012 to 4902 900 to 1100 (continued)

Columbia Generating Station RH (%)

70 70 Flowrate (cfm)

Amendment No.

149 169,182*

5.5-7

Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.7 Ventilation Filter Testing Program (VFTP)

(continued)

e.

Demonstrate that the heaters for each of the ESF systems dissipate the nominal value specified below when tested in accordance with ASME N510-1989:

ESF Ventilation System Wattage (kW)

SGT System 18.6 to 22.8 CREF System 4.5 to 5.5 5.5.8 Explosive Gas and Storage Tank Radioactivity Monitoring Program This program provides controls for potentially explosive gas mixtures contained in the Main Condenser Offgas Treatment System and the quantity of radioactivity contained in unprotected outdoor liquid storage tanks.

The program shall include:

a.

The limits for concentrations of hydrogen in the Main Condenser Offgas Treatment System and a surveillance program to ensure the limits are maintained.

Such limits shall be appropriate to the system's design criteria (i.e., whether or not the system is designed to withstand a hydrogen explosion); and

b.

A surveillance program to ensure that the quantity of radioactivity contained in all outside temporary liquid radwaste tanks that are not surrounded by liners, dikes, or walls, capable of holding the tanks' contents and that do not have tank overflows and surrounding area drains connected to the Liquid Radwaste Treatment System is less than the amount that would result in concentrations greater than the limits of Appendix B. Table 2, Column 2 to 10 CFR 20.1001

- 20.2402, at the nearest potable water supply and the nearest surface water supply in an unrestricted area, in the event of an uncontrolled release of the tanks' contents.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program Surveillance Frequencies.

(continued)

Columbia Generating Station Amendment No.

4-4 1691 5.5-8

Reporting Requirements 5.6 5.0 ADMINISTRATIVE CONTROLS 5.6 Reporting Requirements The following reports shall be submitted in accordance with 10 CFR 50.4.

5.6.1 Occupational Radiation Exposure Report A tabulation on an annual basis of the number of station, utility, and other personnel (including contractors) for whom monitoring was performed, receiving an annual deep dose equivalent of

> 100 mrems and the associated collective deep dose equivalent (reported in man-rem) according to work and job functions (e.g.,

reactor operations and surveillance, inservice inspection, routine maintenance, special maintenance (describe maintenance),

waste processing, and refueling).

This tabulation supplements the requirements of 10 CFR 20.2206.

The dose assignments to various duty functions may be estimated based on electronic or pocket dosimeter, thermoluminescent dosimeter (TLD),

or film badge measurements.

Small exposures totalling < 20% of the individual total dose need not be accounted for.

In the aggregate, at least 80% of the total whole body dose received from external sources should be assigned to specific major work functions.

The report shall be submitted by April 30 of each year.

5.6.2 Annual Radiological Environmental Operating Report The Annual Radiological Environmental Operating Report covering the operation of the unit during the previous calendar year shall be submitted by May 15 of each year.

The report shall include summaries, interpretations, and analyses of trends of the results of the Radiological Environmental Monitoring Program for the reporting period.

The material provided shall be consistent with the objectives outlined in the Offsite Dose Calculation Manual (ODCM),

and in 10 CFR 50, Appendix I. Sections IV.B.2, IV.B.3, and IV.C.

The Annual Radiological Environmental Operating Report shall include the results of analyses of all radiological environmental samples and of all environmental radiation measurements taken during the period pursuant to the locations specified in the table and figures in the ODCM, as well as summarized and tabulated results of these analyses and measurements in the format of the table in the Radiological Assessment Branch Technical Position, Revision 1, November 1979.

In the event that some individual results are not available for inclusion with the report, the (continued)

Columbia Generating Station Amendment No.

4-- 1691 5.6-1

Reporting Requirements 5.6 5.6 Reporting Requirements 5.6.2 Annual Radiological Environmental Operatinq Report (continued) report shall be submitted noting and explaining the reasons for the missing results.

The missing data shall be submitted in a supplementary report as soon as possible.

.5.6.3 Radioactive Effluent Release Report The Radioactive Effluent Release Report covering the operation of the unit shall be submitted in accordance with 10 CFR 50.36a.

The report shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the unit.

The material provided shall be consistent with the objectives outlined in the ODCM and the Process Control Program and in conformance with 10 CFR 50.36a and 10 CFR 50.

Appendix I,Section IV.B.1.

5.6.4 Monthly Operating Reports Routine reports of operating statistics and shutdown experience shall be.submitted on~a monthly basis no later than the 15th of each month following the calendar month covered by the report.

5.6.5 CORE OPERATING LIMITS REPORT (COLR)

a.

Core operating limits shall be established prior to each reload cycle, or prior to any remaining portion of a reload cycle, and shall be documented in the COLR for the following:

1.

The APLHGR for Specification 3.2.1:

2.

The MCPR for Specification 3.2.2:

3.

The LHGR for Specification 3.2.3; and

4.

LCO 3.3.1.3, "Oscillation Power Range Monitor (OPRM)

Instrumentation."

(continued)

Amendment No.

19,169.*,,-.,7+/-,182 5.6-2 Columbia Generating Station

High Radiation Area 5.7 5.0 ADMINISTRATIVE CONTROLS 5.7 High Radiation Area,.

As provided in paragraph 20.1601(c) of 10 CFR Part 20. the following controls shall be applied to high radiation areas in place of the controls required by paragraph 20.1601(a) and (b) of 10 CFR Part 20.

5.7.1 High Radiation Areas with Dose Rates not Exceeding 1.0 rem/hour (at 30 centimeters from the radiation sources or from any surface penetrated by the radiation)

a.

Each entryway to such an area shall be barricaded and conspicuously posted as a high radiation area.

Such barricades may be opened as necessary to permit entry or exit of personnel or equipment.

b.

Access to, and activities in, each such area shall be controlled by means of a Radiation Work Permit (RWP) or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.

c.

Individuals qualified in radiation protection procedures and personnel continuously escorted by such individuals may be exempted from the requirement for an RWP or equivalent while performing their assigned duties provided that they are otherwise following plant radiation protection procedures for entry to, exit from, and work in such areas.

d.

Each individual or group entering such an area shall possess:

1.

A radiation monitoring device that continuously displays radiation dose rates in the area; or

2.

A radiation monitoring device that continuously integrates the radiation dose rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint; or (continued)

Columbia Generating Station 5.7-1 Amendment No..-49,-169,182

High Radiation Area 5.7 5.7 High Radiation Area 5.7.1 High Radiation Areas with Dose Rates not Exceeding 1.0 rem/hour (at 30 centimeters from the radiation sources or from any surface penetrated by the radiation)

(continued)

3.

A radiation monitoring device that continuously transmits dose rate and cumulative dose to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area; or

4.

A self-reading dosimeter (e.g.. pocket ionization chamber or electronic dosimeter) and, (i)

Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel radiation exposure within the area, or (ii)

Be under the surveillance, as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with individuals in the area who are covered by such surveillance.

e.

Except for individuals qualified in radiation protection procedures, or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them.

These continuously escorted personnel will receive a pre-job briefing prior to entry into such areas.

This dose rate determination, knowledge, and pre-job briefing dose not require documentation prior to initial entry.

(continued)

Columbia Generating Station 5.7-2 Amendment No.

14-9,169, 18 2 v

High Radiation Area 5.7 5.7 High Radiation Area 5.7.2 High Radiation Areas with Dose Rates Greater than 1.0 rem/hour (at 30 centimeters from the radiation source or from any surface penetrated by the radiation), but less than 500 rads/hour (at I meter from the radiation source or from any surface penetrated by the radiation)

a.

Each entryway to such an area shall be conspicuously posted as a high radiation area and shall be provided with a locked or continuously guarded door or gate that prevents unauthorized entry, and in addition:

1.

All such door and gate keys shall be maintained under the administrative control of the Shift Supervisor, Radiation Protection Manager, or his or her designee.

2.

Doors and gates shall remain locked except during periods of personnel or equipment entry or exit.

b.

Access to, and activities in, each such area shall be controlled by means of an RWP or equivalent that includes specification of radiation dose rates in the immediate work area(s) and other appropriate radiation protection equipment and measures.

c.

Individuals qualified in radiation protection procedures may be exempted from the requirement for an RWP or equivalent while performing radiation surveys in such areas provided that they are otherwise following plant radiation protection procedures for entry to. exit from, and work in such areas.

d.

Each individual or group entering such an area shall possess:

1.

A radiation monitoring device that continuously integrates the radiation rates in the area and alarms when the device's dose alarm setpoint is reached, with an appropriate alarm setpoint, or

2.

A radiation monitoring device that continuously transmits dose rate and cumulative dose to a remote receiver monitored by radiation protection personnel responsible for controlling personnel radiation exposure within the area with the means to communicate with and control every individual in the area, or (continued)

Columbia Generating Station Amendment No.

1-49)*.1-9,182 5.7-3

High Radiation Area 5.7 5.7 High Radiation Area 5.7.2 Hiqh Radiation Areas with Dose Rates Greater than 1.0 rem/hour (at 30 centimeters from the radiation source or from any surface penetrated by the radiation), but less than 500 rads/hour (at 1 meter from the radiation source or from any surface penetrated by the radiation)

(continued)

3.

A self-reading dosimeter (e.g.,

pocket ionization chamber or electronic dosimeter) and, Mi) Be under the surveillance, as specified in the RWP or equivalent, while in the area, of an individual qualified in radiation protection procedures, equipped with a radiation monitoring device that continuously displays radiation dose rates in the area; who is responsible for controlling personnel exposure within the area, or (ii)

Be under the surveillance, as specified in the RWP or equivalent, while in the area, by means of closed circuit television, of personnel qualified in radiation protection procedures, responsible for controlling personnel radiation exposure in the area, and with the means to communicate with and control every individual in the area.

4.

In those cases where options 2.

and 3.,

above are impractical or determined to be inconsistent with the "As Low As is Reasonably Achievable" principle, a radiation monitoring device that continuously displays radiation dose rates in the area.

e.

Except for individuals qualified in radiation protection procedures, or personnel continuously escorted by such individuals, entry into such areas shall be made only after dose rates in the area have been determined and entry personnel are knowledgeable of them.

These continuously escorted personnel will receive a pre-job briefing prior to entry into such areas.

This dose rate determination, knowledge, and pre-job briefing dose not require documentation prior to initial entry.

(rnntinilpd)

Columbia Generating Station 5.7-4 Amendment No.' 14,19182