Tennessee Valley Authonty, Post Office Box 2000, Soddy-Daisy, Tennessee 37384-2000 December 23, 2002 Chattanooga Environmental Assistance Center Division of Water Pollution Control State Office Building, Suite 550 540 McCallie Avenue Chattanooga, Tennessee 37402-2013 Attention: Mike Kelley
Dear Mr. Kelley:
TENNESSEE VALLEY AUTHORITY - SEQUOYAH NUCLEAR PLANT - TENNESSEE STORM WATER MULTI-SECTOR GENERAL PERMIT FOR INDUSTRIAL ACTIVITIES PERMIT NO. TNR050000 SECTOR 0 EXCEEDANCE OF THE MONITORING CUT OFF CONCENTRATION Please find enclosed the thirty day notification and the lab analysis for the exceedance of the monitoring cut-off concentration for total recoverable iron for Storm Water Outfall No. 2.
Please contact me at (423) 843-6700 if you have any questions or comments.
Sincerely, Michael G. Beavers Acting Environmental Supervisor Signatory Authority for Richard T. Purcell Site Vice President Sequoyah Nuclear Plant Enclosures cc (Enclosures):
- U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Pr.ted wn racyed papa
Tennessee Valley Authority - Sequoyah Nuclear Plant - Tennessee Storm Water Multi-Sector General Permit for Industrial Activities Permit No. TNRO50000 Sector 0 Exceedance of the Monitoring Cut-Off Concentration Description of Event:
Tennessee Storm Water Multi-Sector General Permit for Industrial Activities Sector 0 requires annual monitoring of total recoverable iron. Sequoyah Nuclear Plant sampled for total recoverable iron on November 15, 2002. The storm water analytical monitoring results were received on December 5, 2002. As stated in Table 0-1, Monitoring Requirements for Steam Electric Power Generating Facilities, the cut-off concentration for total recoverable iron is 5.0 mg/L. The analytical monitoring results for Storm Water Outfall No. 2 showed a total recoverable iron concentration of 6.2 mg/L.
Likely Causes of the Exceedance:
Likely causes of the exceedance of the cut-off concentration for total recoverable iron are:
(1) Background iron concentrations in the soil in the area of Storm Water Outfall No. 2 and/or (2) Increased industrial activity in the area surrounding Storm Water Outfall No. 2 due to the Steam Generator Replacement Project scheduled to be completed June 2003.
Certification Statement:
I certify under penalty of law that this document and all attachments were prepared under my direction or supervision in accordance with a system designed to assure that qualified personnel properly gathered and evaluated the information submitted. Based on my inquiry of the person or persons who manage the system, or those persons directly responsible for gathering the information, the information submitted is, to the best of my knowledge and belief, true, accurate, and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment for knowing violation.
S ig n a tu re
,f. / J,,I.-- -
Michael G. Beavers Title m,
- 4 Acting Environmental Supervisor
Data Report Number: 21205-155715 Report of Results:
NPDES TENNESSEE VALLEY AUTHORITY CENTRAL LABORATORIES SERVICES 1101 Market Street, PSC 1B-C Chattanooga, Tennessee 37402-2801 Phone: (423) 876-4318
- Fax: (423) 876-4137 NPDES Final Data Report Shipping Address Chickamauga Power Service Center North Side Chickamauga Reservation Chattanooga, Tennessee 37415 Customer Address: Pgm Admin Environmental SB 2A-SQN Phone 423-843-6700 Fax: 423-843-7080 E-Mail SQN Environmental Location Code: SQN Field ID: SW#2 Sample
Description:
IRON Permit Number:
Discharge Number:
Method of Transport:
Cont. Flow (MGD):
Sample ID:
LRF ID:
AC19134 02110203 Matrix: Water Date Collected:
11/15/2002 Time Collected:
16:28 EST Date Received:
11/20/2002 Time Received:
10.12 Project Manager: Lisabeth R Pearson Plant: SQN Project Account Code: 000WQYN Regulation: NPDES
- pH (Field):
Analysis Analysi Method Analyte CAS Number Resul Units MDL2 Date s
Analyst Reference Metals Digestion for ICP Complete 11/25/2002 13 48 MAA Iron, Total 7439-89-6 6.2 mg/L 001 12/05/2002 10 13 LMJ EPA 200.7 Sample Comments: None Page 4 of 13 12/05/2002 1 Chemical Abstracts Service Registry Number 2 Method Detection Limit