Text
Committed to Nuclear Excellence December 13, 2002 Mano K. Nazar Site Vice President Prairie Island Nuclear Generating Plant Nuclear Management Company, LLC 1717 Wakonade Dr. East
- Welch MN 55089 Technical Specification 5.6.7 U S Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket No. 50-282 License No.
DPR-42 2002 Unit 1 Steam Generator Inspection Results - 15 Day Report In accordance with Technical Specification 5.6.7.1, the number of tubes plugged or sleeved in each steam generator is provided in Table 1.
EOC 21 2002 Re pairs BOC22 Type of Repair 11SG 12SG 11SG 12SG 11SG 12SG Tubes Plugged 171 377 22 178 193 555 Tubes Sleeved 0
1076 0
-2*
0 1074 Table 1 Two sleeved tubes were removed from service In accordance with Technical Specification 5.6.7.4, the identification of F* and EF*
tubes and the location and extent of degradation are included in Attachment 1 to this letter. There are 387 tubes classified as F* tubes and 16 tubes classified as EF* tubes.
In this letter we have made no new Nuclear Regulatory Commission commitments.
Please contact Jeff Kivi (651-388-1121) if you have any questions related to this letter.
AL It -Ai Mano K. Naza Site Vice Pre dent Prairie Islan fuclear Generating Plant Prairie Island Unit I RF022 PluQs and Sleeves
USNRC NUCLEAR MANAGEMENT COMPANY, LLC December 13, 2002 Page 2 c: Regional Administrator-Region III, NRC Senior Resident Inspector, NRC NRR Project Manager, NRC
Attachment:
11 and 12 Steam Generator EF* and F* Tube Report
ATTACHMENT 1 11 and 12 Steam Generator EF* and F* Tube Report
NUCLEAR MANAGEMENT COMPANY, LLC USNRC December 13, 2002 Page 2 CODES Location (Landmark)
TRH = Top of OEM Hard Roll Hot Leg IBH = Bottom of Additional Hard Roll 1 2BH = Bottom of Additional Hard Roll 2 EBH = Bottom of Additional Elevated Hard Roll Types of F and EF Stars EF* = EF* Tube with Elevated Additional Roll Expansion F*O = F* Tube without Additional Roll Expansion F*I = F* Tube with One Additional Roll Expansion F*2 = F* Tube with Second Higher Additional Roll Expansion Indication Code MAD = Multiple Axial Indication - No Longer Detectable MAI = Multiple Axial Indication MAN = Multiple Axial Indication - No Change SAD = Single Axial Indication - No Longer Detectable SAI = Single Axial Indication SAN = Single Axial Indication - No Change SCN = Single Circumferential Indication - No Change SVN = Single Volumetric Indication - No Change 11 STEAM GENERATOR F*0 TUBES, BOC22, 2002 NO. SIG Leg Row Col Indication Location Elev from Elev to Status 1
11 H
1 9
SAN TRH
-2.54
-2.43 F*0 2
11 H
8 9
SCN TRH
-2.56
-2.51 F*0 3
11 H
3 11 SAI TRH
-2.67
-2.54 F*0 4
11 H
1 12 SAN TRH
-2.54
-2.43 F*0 5
11 H
2 12 SAN TRH
-2.25
-2.21 F*0 6
11 H
5 12 SAN TRH
-2.38
-2.24 F*0 7
11 H
6 12 MAN TRH
-2.38
-2.22 F*0 8
11 H
2 13 MAI TRH
-2.59
-2.51 F*0 9
11 H
1 14 SAN TRH
-2.53
-2.46 F*0 10 11 H
2 14 MAI TRH
-2.75
-2.61 F*0 11 11 H
3 14 SAN TRH
-2.34
-2.24 F*0 12 11 H
1 15 MAN TRH
-2.60
-2.55 F*0 13 11 H
5 15 SAI TRH
-2.77
-2.63 F*0 14 11 H
1 16 SAN TRH
-2.42
-2.34 F*0 15 11 H
2 16 SAI TRH
-2.53
-2.46 F*0 16 11 H
5 16 SAI TRH
-2.87
-2.73 F*0
NUCLEAR MANAGEMENT COMPANY, LLC USNRC December 13, 2002 Page 3 11 STEAM GENERATOR F*0 TUBES, BOC22, 2002 NO. S/G Leg Row Col Indication Location Elev from Elev to Status 17 11 H
1 17 MAN TRH
-2.92
-2.82 F*0 18 11 H
2 17 MAN TRH
-2.31
-2.19 F*0 19 11 H
1 18 SAN TRH
-2.43
-2.34 F*0 20 11 H
2 18 SAN TRH
-2.55
-2.49 F*0 21 11 H
7 18 SAI TRH
-2.78
-2.60 F*0 22 11 H
1 19 SAN TRH
-2.62
-2.50 F*0 23 11 H
1 20 MAN TRH
-2.65
-2.59 F*0 24 11 H
10 20 SAN TRH
-2.67
-2.51 F*0 25 11 H
1 21 SAN TRH
-2.64
-2.49 F*0 26 11 H
3 21 MAN TRH
-2.52
-2.20 F*O 27 11 H
10 21 MAN TRH
-2.64
-2.55 F*0 28 11 H
1 22 MAN TRH
-2.65
-2.55 F*0 29 11 H
2 22 SAI TRH
-2.57
-2.49 F*0 30 11 H
3 22 SAN TRH
-2.53
-2.47 F*0 31 11 H
1 23 SAN TRH
-2.48
-2.41 F*0 32 11 H
6 23 MAN TRH
-2.55
-2.43 F*0 33 11 H
8 23 SAN TRH
-2.50
-2.43 F*0 34 11 H
1 24 SAN TRH
-2.59
-2.45 F*0 35 11 H
2 24 MAN TRH
-2.56
-2.48 F*0 36 11 H
1 25 MAN TRH
-2.53
-2.25 F*0 37 11 H
2 25 SAN TRH
-2.52
-2.45 F*0 38 11 H
3 25 MAN TRH
-2.61
-2.50 F*0 39 11 H
4 25 MAN TRH
-2.51
-2.33 F*0 40 11 H
5 25 MAN TRH
-2.53
-2.40 F*0 41 11 H
10 25 SAN TRH
-2.51
-2.37 F*0 42 11 H
12 25 MAN TRH
-2.59
-2.51 F*0 43 11 H
20 25 MAN TRH
-2.68
-2.43 F*0 44 11 H
21 25 MAN TRH
-2.77
-2.67 F*0 45 11 H
1 26 MAN TRH
-2.53
-2.41 F*0 46 11 H
6 26 SAN TRH
-2.50
-2.39 F*0 47 11 H
7 26 SAN TRH
-2.48
-2.36 F*0 48 11 H
8 26 SAN TRH
-2.59
-2.52 F*0 49 11 H
12 26 SAN TRH
-2.45
-2.36 F*0 50 11 H
13 26 MAI TRH
-2.65
-2.59 F*0 51 11 H
15 26 SAN TRH
-2.44
-2.37 F*0 52 11 H
17 26 MAN TRH
-2.41
-2.33 F*0 53 11 H
18 26 SAN TRH
-2.55
-2.49 F*0 54 11 H
19 26 MAN TRH
-2.53
-2.42 F*0 55 11 H
20 26 MAN TRH
-2.64
-2.51 F*0 56 11 H
21 26 MAN TRH
-2.53
-2.46 F*0 57 11 H
1 27 MAN TRH
-2.76
-2.35 F*0 58 11 H
2 27 MAN TRH
-2.35
-2.25 F*O 59 11 H
4 27 MAN TRH
-2.43
-2.31 F*0 60 11 H
5 27 MAN TRH
-2.56
-2.42 F*0
NUCLEAR MANAGEMENT COMPANY, LLC USNRC Attachment I December 13, 2002 Page 4 11 STEAM GENERATOR F*0 TUBES. BOC22. 2002 NO. S/G Leg Row Col Indication Location Elev from Elev to Status 61 11 H
6 27 SAN TRH
-2.48
-2.21 F*0 62 11 H
7 27 MAN TRH
-2.50
-2.38 F*0 63 11 H
13 27 MAN TRH
-2.42
-2.30 F*0 64 11 H
19 27 MAN TRH
-2.46
-2.37 F*0 65 11 H
20 27 MAN TRH
-2.44
-2.31 F*0 66 11 H
1 28 MAN TRH
-2.65
-2.53 F*0 67 11 H
4 28 SAN TRH
-2.49
-2.33 F*0 68 11 H
5 28 MAN TRH
-2.57
-2.45 F*0 69 11 H
6 28 SAN TRH
-2.33
-2.26 F*0 70 11 H
7 28 SAN TRH
-2.54
-2.47 F*0 71 11 H
8 28 SAI TRH
-2.72
-2.64 F*0 72 11 H
9 28 SAN TRH
-2.57
-2.49 F*0 73 11 H
10 28 SAN TRH
-2.40
-2.33 F*0 74 11 H
12 28 SAN TRH
-2.44
-2.37 F*0 75 11 H
16 28 SAN TRH
-2.42
-2.35 F*0 76 11 H
18 28 SAN TRH
-2.33
-2.26 F*0 77 11 H
19 28 MAN TRH'
-2.44
-2.36 F*0 78 11 H
20 28 MAN TRH
-2.40
-2.30 F*0 79 11 H
1 29 MAN TRH
-2.50
-2.31 F*0 80 11 H
2 29 SAN TRH
-2.55
-2.45 F*0 81 11 H
5 29 SAN TRH
-2.45
-2.23 F*0 82 11 H
7 29 MAN TRH
-2.37
-2.29 F*0 83 11 H
8 29 SAN TRH
-2.62
-2.51 F*0 84 11 H
11 29 SAN TRH
-2.32
-2.26 F*0 85 11 H
12 29 MAN TRH
-2.54
-2.41 F*0 86 11 H
15 29 SAN TRH
-2.19
-2.11 F*0 87 11 H
17 29 SAI TRH
-2.80
-2.70 F*0 88 11 H
18 29 SAN TRH
-2.47
-2.33 F*0 89 11 H
19 29 MAN TRH
-2.42
-2.21 F*0 90 11 H
20 29 MAN TRH
-2.54
-2.36 F*0 91 11 H
21 29 SAN TRH
-2.43
-2.39 F*0 92 11 H
1 30 SAN TRH
-2.83
-2.62 F*0 93 11 H
5 30 SAN TRH
-2.45
-2.38 F*0 94 11 H
7 30 MAN TRH
-2.60
-2.45 F*0 95 11 H
8 30 SAI TRH
-2.75
-2.61 F*0 96 11 H
9 30 SAN TRH
-2.66
-2.48 F*0 97 11 H
11 30 SAI TRH
-2.60
-2.52 F*0 98 11 H
13 30 SAN TRH
-2.57
-2.39 F*0 99 11 H
14 30 MAN TRH
-2.55
-2.45 F*0 100 11 H
15 30 SAN TRH
-2.42
-2.35 F*0 101 11 H
19 30 MAN TRH
-2.34
-2.23 F*0 102 11 H
20 30 MAN TRH
-2.54
-2.44 F*0 103 11 H
21 30 SAN TRH
-2.41
-2.26 F*0 104 11 H
1 31 MAN TRH
-2.72
-2.55 F*0
USNRC December 13, 2002 Page 5 NUCLEAR MANAGEMENT COMPANY, LLC 11 STEAM GENERATOR F*0 TUBES, BOC22, 2002 NO. S/G Leg Row Col Indication Location Elev from Elev to Status 105 11 H
5 31 SAN TRH
-2.48
-2.33 F*0 106 11 H
9 31 MAN TRH
-2.61
-2.55 F*0 107 11 H
10 31 MAN TRH
-2.74
-2.64 F*0 108 11 H
13 31 SAN TRH
-2.56
-2.47 F*0 109 11 H
15 31 MAN TRH
-2.54
-2.39 F*0 110 11 H
18 31 SAN TRH
-2.48
-2.33 F*0 111 11 H
19 31 MAN TRH
-2.42
-2.32 F*0 112 11 H
21 31 SAN TRH
-2.50
-2.36 F*0 113 11 H
1 32 MAN TRH
-2.70
-2.50 F*0 114 11 H
4 32 SAN TRH
-2.46
-2.29 F*0 115 11 H
6 32 SAN TRH
-2.66
-2.50 F*0 116 11 H
7 32 MAI TRH
-2.60
-2.55 F*0 117 11 H
8 32 SAN TRH
-2.52
-2.32 F*0 118 11 H
12 32 SAI TRH
-2.64
-2.57 F*0 119 11 H
13 32 MAN TRH
-2.64
-2.56 F*0 120 11 H
15 32 SA!
TRH
-2.65
-2.61 F*0 121 11 H
16 32 MAI TRH
-2.68
-2.61 F*0 122 11 H
19 32 MAN TRH
-2.41
-2.32 F*0 123 11 H
20 32 SAN TRH
-2.44
-2.33 F*0 124 11 H
21 32 MAN TRH
-2.43
-2.26 F*0 125 11 H
1 33 SAN TRH
-2.80
-2.62 F*0 126 11 H
2 33 SAN TRH
-2.60
-2.52 F*0 127 11 H
4 33 SAI TRH
-2.62
-2.58 F*0 128 11 H
7 33 SAN TRH
-2.64
-2.56 F*0 129 11 H
8 33 SAI TRH
-2.63
-2.57 F*0 130 11 H
9 33 SAI TRH
-2.66
-2.58 F*0 131 11 H
11 33 SAN TRH
-2.66
-2.56 F*0 132 11 H
12 33 SAN TRH
-2.55
-2.38 F*0 133 11 H
13 33 SAN TRH
-2.66
-2.55 F*0 134 11 H
14 33 MAN TRH
-2.66
-2.57 F*0 135 11 H
15 33 SAI TRH
-2.62
-2.56 F*0 136 11 H
16 33 MAN TRH
-2.38
-2.31 F*0 137 11 H
17 33 SAN TRH
-2.38
-2.30 F*0 138 11 H
18 33 SAN TRH
-2.47
-2.32 F*0 139 11 H
19 33 SAN TRH
-2.36
-2.24 F*0 140 11 H
20 33 SAN TRH
-2.41
-2.32 F*0 141 11 H
1 34 SAN TRH
-2.81
-2.58 F*0 142 11 H
3 34 SAI TRH
-2.61
-2.50 F*0 143 11 H
5 34 SAI TRH
-2.69
-2.61 F*0 144 11 H
6 34 SAN TRH
-2.53
-2.45 F*0 145 11 H
7 34 SAN TRH
-2.66
-2.55 F*0 146 11 H
8 34 SAN TRH
-2.62
-2.54 F*0 147 11 H
9 34 SAN TRH
-2.74
-2.61 F*0 148 11 H
10 34 MAN TRH
-2.59
-2.51 F*0
1:
USNRC Attachment I December 13, 2002 Page 6 NUCLEAR MANAGEMENT COMPANY, LLC S11 STEAM GENERATOR F*0 TUBES, BOC22, 2002 NO. S/G Leg Row Col Indication Location Elev from Elev to Status 149 11 H
11 34 MAN TRH
-2.67
-2.55 F*0 150 11 H
12 34 MAN TRH
'-2.60
-2.52 F*0 151 11 H
13 34 SAN TRH
-2.60
-2.50 F*0 152 11 H
15 34 SAI TRH
-2.75
-2.64 F*0 153 11 H
16 34 SAI TRH
-2.62
-2.54 F*0 154 11 H
17 34 SAN TRH
-2.16
-2.09 F*0 155 11 H
18 34 SAN TRH
-2.38
-2.30 F*0 156 11 H
19 34 MAN TRH
-2.27
-2.20 F*0 157 11 H
1 35 SAN TRH
-2.88
-2.72 F*0 158 11 H
2 35 SAN TRH
-2.66
-2.51 F*0 159 11 H
4 35 SAN TRH
-2.62
-2.54 F*0 160 11 H
5 35 SAI TRH
-2.58
-2.52 F*0 161 11 H
6 35 SAN TRH
-2.62
-2.54 F*0 162 11 H
7 35 SAI TRH
-2.56
-2.47 F*0 163 11 H
8 35 MAI TRH
-2.63
-2.55 F*0 164 11 H
9 35 SAI TRH
-2.58
-2.53 F*0 165 11 H
10 35 SAI TRH
-2.60
-2.56 F*0 166 11 H
12 35 SAN TRH
-2.61
-2.57 F*0 167 11 H
13 35 SAN TRH
-2.56
-2.47 F*0 168 11 H
14 35 MAI TRH
-2.63
-2.55 F*0 169 11 H
15 35 SAN TRH
-2.55
-2.44 F*0 170 11 H
16 35 SAN TRH
-2.65
-2.57 F*0 171 11 H
20 35 SAI TRH
-2.49
-2.41 F*0 172 11 H
1 36 MAN TRH
-2.70
-2.51 F*0 173 11 H
2 36 MAN TRH
-2.43
-2.29 F*0 174 11 H
4 36 MAI TRH
-2.46
-2.39 F*0 175 11 H
5 36 SAN TRH
-2.50
-2.41 F*0 176 11 H
6 36 SAI TRH
-2.56
-2.52 F*0 177 11 H
7 36 SAI TRH
-2.55
-2.48 F*0 178 11 H
8 36 MAI TRH
-2.53
-2.45 F*0 179 11 H
9 36 SAN TRH
-2.55
-2.47 F*0 180 11 H
10 36 SAI TRH
-2.46
-2.42 F*0 181 11 H
12 36 SAI TRH
-2.47
-2.43 F*0 182 11 H
13 36 MAN TRH
-2.54
-2.39 F*0 183 11 H
14 36 MAN TRH
-2.60
-2.47 F*0 184 11 H
15 36 SAN TRH
-2.57
-2.50 F*0 185 11 H
16 36 MAN TRH
-2.63
-2.52 F*0 186 11 H
17 36 SAI TRH
-2.49
-2.39 F*0 187 11 H
20 36 SAN TRH
-2.49
-2.35 F*0 188 11 H
21 36 SAN TRH
-2.47
-2.36 F*0 189 11 H
1 37 MAN TRH
-2.57
-2.41 F*0 190 11 H
2 37 MAN TRH
-2.47
-2.36 F*0 191 11 H
3 37 SAI TRH
-2.57
-2.50 F*0 192 11 H
6 37 MAN TRH
-2.60
-2.51 F*0
II USNRC Attachment I December 13, 2002 Page 7 NUCLEAR MANAGEMENT COMPANY, LLC 11 STEAM GENERATOR F*0 TUBES, BOC22, 2002 NO. S/G Leg Row Col Indication Location Elev from Elev to Status 193 11 H
8 37 SAI TRH
-2.54
-2.46 F*0 194 11 H
9 37 SAN TRH
-2.58
-2.47 F*0 195 11 H
10 37 SAI TRH
-2.53
-2.49 F*0 196 11 H
12 37 MAI TRH
-2.60
-2.50 F*0 197 11 H
13 37 SAI TRH
-2.50
-2.44 F*0 198 11 H
15 37 SAI TRH
-2.47
-2.36 F*0 199 11 H
16 37 MAN TRH
-2.52
-2.36 F*0 200 11 H
19 37 MAN TRH
-2.67
-2.48 F*0 201 11 H
20 37 SAN TRH
-2.51
-2.43 F*0 202 11 H
1 38 SAN TRH
-2.82
-2.71 F*0 203 11 H
5 38 SAI TRH
-2.58
-2.51 F*0 204 11 H
8 38 MAN TRH
-2.71
-2.57 F*0 205 11 H
9 38 MAN TRH
-2.52
-2.26 F*0 206 11 H
11 38 SAI TRH
-2.41
-2.33 F*0 207 11 H
12 38 SAN TRH
-2.57
-2.39 F*0 208 11 H
13 38 MAN TRH
-2.38
-2.33 F*0 209 11 H
14 38 MAN TRH
-2.53
-2.42 F*0 210 11 H
15 38 MAN TRH
-2.46
-2.33 F*0 211 11 H
16 38 SAN TRH
-2.55
-2.48 F*0 212 11 H
18 38 SAI TRH
-2.51
-2.44 F*0 213 11 H
21 38 SAN TRH
-2.58
-2.40 F*0 214 11 H
22 38 MAN TRH
-2.64
-2.46 F*0 215 11 H
1 39 MAN TRH
-2.46
-2.27 F*0 216 11 H
2 39 MAN TRH
-2.49
-2.38 F*0 217 11 H
-4 39 SAN TRH
-2.57
-2.49 F*0 218 11 H
6 39 SAI TRH
-2.51
-2.47 F*0 219 11 H
7 39 SAN TRH
-2.42
-2.32 F*0 220 11 H
10 39 SAI TRH
-2.45
-2.41 F*O 221 11 H
12 39 MAI TRH
-2.59
-2.51 F*0 222 11 H
14 39 MAI TRH
-2.60
-2.51 F*0 223 11 H
15 39 MAN TRH
-2.43
-2.33 F*0 224 11 H
16 39 SAI TRH
-2.43
-2.39 F*0 225 11 H
19 39 SAI TRH
-2.48
-2.41 F*0 226 11 H
20 39 MAN TRH
-2.61
-2.21 F*0 227 11 H
21 39 SAN TRH
-2.56
-2.42 F*0 228 11 H
22 39 SAN TRH
-2.57
-2.37 F*0 229 11 H
25 39 SAI TRH
-2.53
-2.49 F*0 230 11 H
35 39 SAN TRH
-2.46
-2.33 F*0 231 11 H
1 40 MAN TRH
-2.58
-2.47 F*0 232 11 H
5 40 SAN TRH
-2.35
-2.23 F*0 233 11 H
6 40 SAI TRH
-2.46
-2.42 F*O 234 11 H
9 40 MAN TRH
-2.44
-2.31 F*0 235 11 H
12 40 MAN TRH
-2.41
-2.36 F*0 236 11 H
13 40 MAN TRH
-2.36
-2.28 F*0
USNRC December 13, 2002 Page 8 NUCLEAR MANAGEMENT COMPANY, LLC 11 STEAM GENERATOR F*O TUBES, BOC22, 2002 NO. S/G Leg Row Col Indication Location Elev from Elev to Status 237 11 H
14 40 SAN TRH
-2.51
-2.42 F*0 238 11 H
15 40 SAN TRH
-2.19
-2.12 F*0 239 11 H
19 40 MAN TRH
-2.50
-2.39 F*0 240 11 H
20 40 MAN TRH
-2.59
-2.39 F*0 241 11 H
22 40 MAN TRH
-2.58
-2.34 F*0 242 11 H
1 41 MAN TRH
-2.59
-2.49 F*0 243 11 H
7 41 MAN TRH
-2.47
-2.41 F*0 244 11 H
12 41 SAN TRH
-2.75
-2.63 F*0 245 11 H
15 41 MAN TRH
-2.48
-2.34 F*0 246 11 H
16 41 SAN TRH
-2.69
-2.62 F*0 247 11 H
17 41 SAN TRH
-2.48
-2.38 F*0 248 11 H
18 41 SAN TRH
-2.49
-2.33 F*0 249 11 H
19 41 SAN TRH
-2.46
-2.34 F*0 250 11 H
20 41 SAN TRH
-2.50
-2.34 F*0 251 11 H
4 42 MAN TRH
-2.58
-2.47 F*0 252 11 H
6 42 MAI TRH
-2.50
-2.43 F*0 253 11 H
8 42 SAN TRH
-2.55
-2.37 F*0 254 11 H
11 42 SAI TRH
-2.51
-2.43 F*0 255 11 H
12 42 MAN TRH
-2.56
-2.46 F*0 256 11 H
14 42 SAN TRH
-2.54
-2.49 F*0 257 11 H
15 42 MAI TRH
-2.44
-2.34 F*0 258 11 H
16 42 SAN TRH
-2.56
-2.48 F*0 259 11 H
19 42 SAN TRH
-2.48
-2.38 F*0 260 11 H
20 42 SAN TRH
-2.54
-2.30 F*0 261 11 H
21 42 MAN TRH
-2.47
-2.34 F*0 262 11 H
1 43 SAN TRH
-2.71
-2.56 F*0 263 11 H
2 43 SAN TRH
-2.68
-2.57 F*0 264 11 H
6 43 MAN TRH
-2.69
-2.56 F*0 265 11 H
8 43 SAN TRH
-2.68
-2.62 F*0 266 11 H
12 43 SAN TRH
-2.66
-2.61 F*0 267 11 H
14 43 SAN TRH
-2.42
-2.32 F*0 268 11 H
15 43 MAN TRH
-2.50
-2.41 F*0 269 11 H
17 43 MAN TRH
-2.52
-2.41 F*0 270 11 H
19 43 SAN TRH
-2.38
-2.27 F*0 271 11 H
21 43 SAN TRH
-2.48
-2.34 F*0 272 11 H
22 43 SAN TRH
-2.55
-2.36 F*0 273 11 H
1 44 SAN TRH
-2.67
-2.59 F*0 274 11 H
5 44 SAN TRH
-2.55
-2.48 F*0 275 11 H
6 44 SAN TRH
-2.56
-2.45 F*0 276 11 H
7 44 SAN TRH
-2.45
-2.41 F*0 277 11 H
10 44 MAN TRH
-2.50
-2.39 F*0 278 11 H
12 44 SAN TRH
-2.51
-2.41 F*0 279 11 H
13 44 SAI TRH
-2.47
-2.40 F*0 280 11 H
14 44 MAN TRH
-2.55
-2.46 F*0
NUCLEAR MANAGEMENT COMPANY, LLC USNRC Attachment I December 13, 2002 Page 9 11 STEAM GENERATOR F*0 TUBES, BOC22, 2002 NO. S/G Leg Row Col Indication Location Elev from Elev to Status 281 11 H
16 44 MAN TRH
-2.60
-2.48 F*0 282 11 H
17 44 MAN TRH
-2.53
-2.42 F*0 283 11 H
20 44 MAN TRH
-2.59
-2.36 F*0 284, 11 H
21 44 SAN TRH
-2.56
-2.38 F*0 285 11 H
22 44 SAN TRH
-2.47
-2.19 F*0 286 11 H
1 45 SAN TRH
-2.54
-2.36 F*0 287 11 H
6 45 SAN TRH
-2.51
-2.35 F*0 288 11 H
7 45 SAI TRH
-2.62
-2.55 F*0 289 11 H
8 45 SAN TRH
-2.68
-2.51 F*O 290 11 H
9 45 SAN TRH
-2.47
-2.41 F*0 291 11 H
10 45 SAN TRH
-2.72
-2.58 F*0 292 11 H
12 45 MAN TRH
-2.60
-2.53 F*0 293 11 H
14 45 MAN TRH
-2.93
-2.81 F*0 294 11 H
15 45 MAN TRH
-2.48
-2.42 F*0 295 11 H
19 45 MAN TRH
-2.47
-2.36 F*0 296 11 H
20 45 SAI TRH
-2.58
-2.51 F*0 297 11 H
21 45 MAN TRH
-2.46
-2.38 F*0 298 11 H
22 45 SAI TRH
-2.59
-2.51 F*0 299 11 H
3 46 MAN TRH
-2.62
-2.56 F*0 300 11 H
4 46 MAN TRH
-2.60
-2.48 F*0 301 11 H
6 46 MAN TRH
-2.53
-2.45 F*0 302 11 H
7 46 MAN TRH
-2.49
-2.40 F*0 303 11 H
9 46 SAN TRH
-2.53
-2.49 F*0 304 11 H
11 46 SAN TRH
-2.48
-2.41 F*0 305 11 H
15 46 MAI TRH
-2.36
-2.32 F*0 306 11 H
17 46 MAN TRH
-2.54
-2.46 F*0 307 11 H
19 46 SAI TRH
-2.50
-2.46 F*0 308 11 H
20 46 MAN TRH
-2.22
-2.11 F*0 309 11 H
21 46 MAN TRH
-2.54
-2.43 F*0 310 11 H
1 47 SAN TRH
-2.57
-2.51 F*0 311 11 H
5 47 SAN TRH
-2.47
-2.41 F*0 312 11 H
6 47 SAN TRH
-2.50
-2.41 F*0 313 11 H
8 47 SAN TRH
-2.58
-2.49 F*0 314 11 H
19 47 SAN TRH
-2.48
-2.41 F*0 315 11 H
22 47 SAN TRH
-2.71
-2.53 F*0 316 11 H
26 47 SAI TRH
-2.48
-2.41 F*0 317 11 H
1 48 MAN TRH
-2.51
-2.27 F*0 318 11 H
1 49 SAN TRH
-2.43
-2.33 F*0 319 11 H
2 49 MAN TRH
-2.59
-2.37 F*0 320 11 H
1 50 MAN TRH
-2.73
-2.59 F*0 321 11 H
1 51 SAN TRH
-2.42
-2.20 F*0 322 11 H
20 51 SAl TRH
-2.32
-2.26 F*0 323 11 H
1 52 MAN TRH
-2.43
-2.24 F*0 324 11 H
5 52 SAI TRH
-2.57
-2.53 F*0
t.
NUCLEAR MANAGEMENT COMPANY, LLC USNRC December 13, 2002 Page 10 11 STEAM GENERATOR F*0 TUBES. 20C22. 2002 NO. S/G Leg Row Col Indication Location Elev from Elev to Status 325 11 H
4 53 SAI TRH
-2.66
-2.52 F*0 326 11 H
1 54 MAN TRH
-2.70
-2.59 F*0 327 11 H
34 54 SAI TRH
-2.76
-2.52 F*0 328 11 H
1 55 SAN TRH
-2.79
-240 F*O 329 11 H
2 55 SAN TRH
-2.57
-2.44 F*0 330 11 H
5 55 MAN TRH
-2.77
-2.63 F*O 331 11 H
19 55 SAI TRH
-2.21
-2.17 F*0 332 11 H
1 56 SAN TRH
-2.84
-2.54 F*0 333 11 H
1 57 SAN TRH
-2.71
-2.53 F*0 334 11 H
2 57 SAN TRH
-2.39
-2.32 F*0 335 11 H
1 58 SAN TRH
-2.73
-2.59 F*0 336 11 H
19 58 SAN TRH
-2.45
-2.40 F*0 337 11 H
1 59 SAN TRH
-2.81
-2.69 F*0 338 11 H
20 59 SAI TRH
-2.46
-2.40 F*0 339 11 H
1 60 SAN TRH
-2.74
-2.59 F*0 340 11 H
4 60 SAN TRH
-2.46
-2.39 F*0 341 11 H
19 60 MAN TRH
-2.45
-2.29 F*0 342 11 H
20 60 MAI TRH
-2.48
-2.39 F*0 343 11 H
2 62 SAN TRH
-2.49
-2.33 F*0 344 11 H
11 64 SAN TRH
-2.59
-2.52 F*0 345 11 H
4 65 SAI TRH
-2.64
-2.54 F*0 346 11 H
1 67 MAN TRH
-2.67
-2.52 F*0 347 11 H
6 67 MAI TRH
-2.81
-2.64 F*0 348 11 H
1 68 SAN TRH
-2.74
-2.59 F*0 349 11 H
20 68 SAI TRH
-2.69
-2.59 F*0 350 11 H
1 70 MAN TRH
-2.65
-2.51 F*0 351 11 H
1 71 SAN TRH
-2.51
-2.40 F*0 352 11 H
1 72 SAN TRH
-2.63
-2.52 F*0 353 11 H
1 73 SAN TRH
-2.56
-2.44 F*0 354 11 H
1 74 SAN TRH
-2.71
-2.60 F*0 355 11 H
1 75 SAN TRH
-2.55
-2.44 F*0 356 11 H
1 76 SAN TRH
-2.66
-2.42 F*0 357 11 H
1 78 SAN TRH
-2.81
-2.35 F*0 358 11 H
1 87 SAN TRH
-2.67
-2.47 F*0
NUCLEAR MANAGEMENT COMPANY, LLC USNRC Attachment I December 13, 2002 Page 11 No. S/G Leg Row Col Percent Location Elev from Elev to Status 1
11 H
18 7
SVN 1BH
-2.81
-2.49 F*1 2
11 H
19 17 SAD 1BH
-1.22 F*1 3
11 H
23 17 SAN 1BH
-2.25
-2.06 F*1 4
11 H
8 27 SAD IBH
-1.12 F*1 5
11 H
34 28 SAD 1BH
-1.12 F*1 6
11 H
26 35 SAD 1BH
-1.26 F*1 7
11 H
30 46 SAD 1BH
-1.02 F*l 8
11 H
12 51 SAD IBH
-1.14 F*1 9
11 H
5 56 SAN IBH
-1.34
-1.26 F*1 10 11 H
5 57 SAD 1BH
-1.07 F*1 11 11 H
11 58 SAD IBH
-1.10
-0.99 F*1 12 11 H
12 63 SAD IBH
-1.23 F*1 13 11 H
11 65 MAD IBH
-1.28 F*1 14 11 H
6 72 MAN IBH
-1.40
-1.18 F*1 15 11 H
8 78 MAN 1BH
-3.04
-2.43 F*1 11 STEAM GENERATOR F*2 TUBES, BOC22, 2002 No. S/G Leg Row Col Percent Location Elev from Elev to Status 1
11 H
22 35 SAN 2BH
-1.39
-1.32 F*2 2
11 H
2 51 MAN 2BH 1
-2.63
-0.10 F*2 3
11 H
9 67 MAN 2BH
-2.57
-1.37 F*2 11 STEAM GENERATOR EF* TUBES, BOC22, 2002 No. S/G Leg Row Col Percent Location Elev from Elev to Status 1
11 H
9 26 SAN EBH
-13.46
-13.36 EF*
2 11 H
7 31 SAN EBH
-13.72
-13.65 EF*
3 11 H
10 33 MAN EBH
-13.29
-13.10 EF*
4 11 H
14 34 MAI EBH
-13.37
-13.30 EF*
5 11 H
4 40 SAN EBH
-13.30
-13.23 EF*
6 11 H
10 40 SCN EBH
-14.65
-14.40 EF*
7 11 H
17 45 SAN EBH
-12.29
-10.13 EF*
8 11 H
9 47 MAN EBH
-12.45
-9.96 EF*
9 11 H
16 48 MAN EBH
-12.96
-9.43 EF*
10 11 H
16 50 SAN EBH
-10.68
-9.62 EF*
11 11 H
12 53 SAN EBH
-9.20
-8.97 EF*
12 11 H
20 53 SVN EBH
-12.89
-12.79 EF*
13 11 H
12 60 SAN EBH
-13.31
-13.20 EF*
14 11 H
14 64 SAN EBH
-9.02
-8.84 EF*
15 11 H
13 71 SAN EBH
-10.49
-1009 EF*
16 11 H
7 87 SAN EBH
-13.45
-13.32 EF*
11 STEAM GENERATOR F*1 TUBES, BOC22, 2002
-- p1 NUCLEAR MANAGEMENT COMPANY, LLC USNRC December 13, 2002 Page 12 No. S/G Leg Row Col Percent Location Elev from Elev to Status 1
12 H
27 10 SAN TRH
-2.53
-2.47 F*0 2
12 H
22 19 SAI TRH
-2.55
-2.44 F*0 3
12 H
36 58 MAI TRH
-2.66
-2.57 F*0 4
12 H
25 68 SAN TRH
-2.62
-2.53 F*O 5
12 H
40 71 SAI TRH
-2.67
-2.57 F*0 6
12 H
10 88 SCN TRH
-2.25
-2.16 F*0 12 STEAM GENERATOR F*1 TUBES, BOC22, 2002 No. S/G Leg Row Col Percent Location Elev from Elev to Status 1
12 H
34 31 MAN 1BH
-1.18
-1.08 F*1 2
12 H
31 46 SAN 1BH
-1.16
-1.01 F*I 3
12 H
31 47 MAD 1BH
-1.00 F*1 4
12 H
32 47 MAD IBH
-0.81 F*1 5
12 H
4 71 MAN IBH
-1.96
-1.76 F*I 12 STFAM GENERATOR F*0 TUBES. BOC22. 2002