LOP Instrumentation 3.3.8.1 Table 3.3,8.1-1 (page 1 of 1)

Loss of Power Instrumentation REQUIRED CHANNELS PER SURVEILLANCE ALLOWABLE FUNCTION DIVISION REQUIREMENTS VALUE

2. Divisions 1, 2 and Opposite Unit Division 2 - 4.16 kV Emergency Bus Undervoltage
a.

Loss of Voltage - 4.16 kV 2

SR 3.3.8.1.3

b.

Loss of voltage - Time Delay 2

SR 3.3.8.1.3 2 3.1 seconds and _ 10.9 seconds SR 3.3.B.1.4 SR 3.3.8.1.5

c.

Degraded Voltage - 4.16 kV 2

SR 3.3.8.1.1 k 3814 V and s 3900 V Basis SR 3.3.8.1.2 SR 3.3.8.1.5

d.

Degraded Voltage -

Time 2

SR 3.3.8.1.1

Ž 270.1 seconds and Delay.

No LOCA SR 3.3.8.1.2 s 329.9 seconds SR 3.3.8.1.5

e.

Degraded Voltage -

Time 21-)Ib)

SR 3.3.8.1.1 2 9.4 seconds and 5 10.9 seconds

Delay, LOCA SR 3.3.B.1.2 SR 3.3.8.1.5
2.

Division 3-4.16 kV Emergency Bus Undervoltage

a.

Loss of Voltage - 4.16 kV 2

SR 3.3.8.1.3

Ž 2596 V and < 3137 V Basis SR 3.3.8.1.4 SR 3.3.8.1.5

b.

Loss of Voltage - Time Delay 2

SR 3.3.8.1.3

_ 10.9 seconds SR 3.3.8.1.4 SR 3.3.8.1.5

c.

Degraded Voltage - 4.16 kV 2

SR 3.3.8.1.1

? 3814 V and s 3900 V Basis SR 3.3.8.1.2 SR 3.3.8.1.5

d.

Degraded Voltage -

Time 2

SR 3.3.8.1.1 z 270.1 seconds and

Delay, No LOCA SR 3.3.8.1.2 s 329.9 seconds SR 3.3.8.1.5
e.

Degraded Voltage - Time 2(,l}b)

SR 3.3.8.1.1 z 9.4 seconds and _5 10.9 seconds Delay.

LOCA SR 3.3.8.1.2 SR 3.3.B.I.5 (a) In MODES 4 and 5, when associated ECCS subsystem(s) are required to be OPERABLE per LCO 3.5.2, "ECCS Shutdown. '

(b) With no fuel in the reactor vessel, not required to be OPERABLE.

Amendment No.

155/141 LaSalle I and 2 3.3.8.1-3