ML022770239
| ML022770239 | |
| Person / Time | |
|---|---|
| Site: | North Anna |
| Issue date: | 09/26/2002 |
| From: | Sarver S Virginia Electric & Power Co (VEPCO) |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| 02-606 | |
| Download: ML022770239 (104) | |
Text
VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 September 26, 2002 U.S. Nuclear Regulatory Commission Serial No.:
02-606 Attention: Document Control Desk NLOS/mm Washington, D.C. 20555 Docket Nos.:
50-338/339 License Nos.:
NPF-4/7 Gentlemen:
VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
NORTH ANNA POWER STATION UNITS I AND 2 EMERGENCY RESPONSE DATA SYSTEM (ERDS)
DATABASE UPDATES As a result of implementation of the Emergency Response Facility Computer System (ERFCS) software into the plant computer system at North Anna Power Station, modifications to ERDS related points were necessary. The changes are detailed in the Data Point Library (DPL) reference file forms provided in Attachments 1 and 2.
Attachments 3 and 4 provide the revision summaries (change reports) for the affected points for Units 1 and 2, respectively.
No new commitments are intended by this letter. If you have any questions concerning these results, please contact us.
Very truly yours, f
en P. Sarver Director - Nuclear Licensing and Operations Support Attachments
- 1. North Anna Unit 1 Updated Data Point Library Sheets
- 2. North Anna Unit 2 Updated Data Point Library Sheets
- 3. North Anna Unit 1 Revision Summary
- 4. North Anna Unit 2 Revision Summary Commitments made in this letter: None
cc:
U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth Street, SW Suite 23T85 Atlanta, Georgia 30303-8931 Mr. M. J. Morgan NRC Senior Resident Inspector North Anna Power Station Ms. K. Lynne Saul, Program Manager (diskette enclosed)
Engineering, Scientific, & Management Services Scientech, Inc.
440 West Broadway Idaho Falls, ID 83402
ATTACHMENT 1 NORTH ANNA UNIT 1 UPDATED DATA POINT LIBRARY SHEETS
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A AX FD FL 1/A FlFW001A AFW FLOW TO SG A (BL)
STM GEN A AUX FEEDWATER FLOW A
GPM 0-600' H20 0.0 500.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEN IA VARIABLE N/A N/A N/A N/A Senses auxiliary feed pump discharge to steam generator A.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A AX FD FL 2/B FlFW002A AFW FLOW TO SG B (YW)
STM GEN B AUX FEEDWATER FLOW A
GPM 0-600" H20 0.0 500.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEN IB VARIABLE N/A N/A N/A N/A Senses auxiliary feed pump discharge to steam generator B.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A AX FD FL 3/C FIFW003A AFW FLOW TO SG C (WT)
STM GEN C AUX FEEDWATER FLOW A
GPM 0-600" H20 0.0 500.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEN IC VARIABLE N/A N/A N/A N/A Senses auxiliary feed pump discharge to steam generator C.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A SG LEVEL I/A LIFW004A SG A WR LEVEL (NL)
STEAM GENERATOR A WATER LEVEL A
PCT 0-575" H20 0.0 100.0 TNKBOT N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT STEAM GENERATOR 1-RC-E-1A VARIABLE N/A N/A N/A WET Senses the water level in steam generator 1-RC-E-1A.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A SG LEVEL 2/B LIFW008A SG B WR LEVEL (NL)
STEAM GENERATOR B WATER LEVEL A
PCT 0-575" H20 0.0 100.0 TNKBOT N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT STEAM GENERATOR 1-RC-E-1B VARIABLE N/A N/A N/A WET Senses the water level in steam generator I-RC-E-1B.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A SG LEVEL 3/C LlFW012A SG C WR LEVEL (NL)
STEAM GENERATOR C WATER LEVEL A
PCT 0-575' H20 0.0 100.0 TNKBOT N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT STEAM GENERATOR 1-RC-E-IC VARIABLE N/A N/A N/A WET Senses the water level in steam generator I-RC-E-1C.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
03/21/1991 NAl N/A REAC VES LEV LlRC003C RVLIS DYNAMIC HEAD LEVEL REACTOR VESSEL WATER LEVEL A
PCT N/A 0.0 120.0 TNKBOT N/A P
AVERAGE HEAD VENT VARIABLE SEE SYSTEM DESCRIPTION (TOP)
& BOTTOM OF VESSEL N/A N/A N/A WET The 2 DYNAMIC HEAD level signals are used in conjunction with the reactor coolant pump (RCP) breaker statuses to calculate this value.
The dynamic head readings are invalid if no RCP's are running; therefore, this point will be set invalid if no RCP breakers are closed.
If any of the RCP breakers are closed, the average of the valid dynamic head level signals is used to calculate this point.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A CNTMNTRAD RlRM207C CNTMT HR RAD MON COL4(166)
RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 0.316 1.OE+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT ON THE INSIDE CRANE WALL VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level within the reactor containment.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A CQTMNT RAD RlRM208C CNTMT HR RAD MON COL 12 RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 0.316 1.OE+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT ON THE INSIDE CRANE WALL VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level within the reactor containment.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A CNTMNT RAD RlRM209C CNTMT PERS HATCH RAD MON RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 3.16E-5 10.0 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT OUTSIDE CONTAINMENT PERSONNEL HATCH VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level in the Personnel Hatch area.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A CNTMNT RAD RIRM215C CNTMT AREA RAD MON RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 3.16E-5 10.0 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT REACTOR CONTAINMENT VARIABLE N/A N/A N/A N/A Detects gaunma radiation in the reactor containment.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A CTMNT SMP WR LlRS002C CONTAINMENT WR SUMP LEVEL CONTAINMENT SUMP WR LEVEL A
FT N/A 0.0 12.00 TNKBOT N/A P
2 AVERAGE -
SEE SYSTEM DESCRIPTION RECIRC SPRAY SUMP-SEE SYSTEM DESCRIPTION VARIABLE N/A N/A N/A N/A Two transmitters (LT-RS-151A-2
& B-2) monitor recirc spray sump level in the sump itself (0-6'81) and two additional transmitters (LT-RS-151A-l
& B-I) monitor the level above the sump itself (6181-11'41).
The valid wide range signals are averaged (2 signals if all are valid).
If neither signal is valid, this point is marked invalid.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A EFF GAS RAD RlRM204C AUX STM LINE RAD MON (176)
RADIOACTIVITY OF RELEASED GASES A
MR/HR N/A 0.0398 0.1259E+8 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURBINE-DRIVEN AUX FEED PUMP EXHAUST VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level in the turbine-driven auxiliary feed pump exhaust ("Terry" turbine).
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A EFF GAS RAD R3RM225C PV NORMAL RAD MONITOR RADIOACTIVITY OF RELEASED GASES A
UCI/CC N/A 1.OE-7 1.OE-2 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT SWGR BLDG ELEV 307 VARIABLE N/A N/A N/A N/A Continually senses radiation level in a sample stream from the process vent.
This is the normal range instrument for this data.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA1 N/A EFF GAS RAD R3RM229C VS A NORMAL RADN RATE MON RADIOACTIVITY OF RELEASED GASES A
UCI/S N/A 1.0E-1 1.OE+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A" and provides a signal to RG-VG179-1A's microcomputer for determination of radiation release rate.
This is the normal range instrument for this data.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A EFF LIQ RAD R3RM214C SW DISCH TO RSVR RAD MON RADIOACTIVITY OF RELEASED LIQ A
CPM N/A 3.162 1.0E+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT OFF-LINE IN A CMN HDR OF 2 36"DSCH LINES VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level of the service water discharge to the service water reservoir.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A H2 CONC AlGWO01C CNTMT H2 CONCENTRATION CONTAINMENT HYDROGEN CONC A
PCT N/A 0.0 10.0 N/A N/A P
2 AVERAGE -
SEE SYSTEM DESCRIPTION AUX BLDG ELEV 259 VARIABLE N/A N/A N/A N/A Takes a sample of containment atmosphere and measures the hydrogen concentration in the sample.
The valid signals are averaged (2 signals if all are valid).
If none of the signals is valid, this point is marked invalid.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A HP SI FLOW FlSIO03A TOTAL HOT LEG SI FLOW (WT)
HIGH PRESSURE SI FLOW A
GPM N/A 0.0 1000.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT CHRGING PMP DISCH UPSTRM OF HOT LEG VARIABLE N/A N/A N/A N/A Provides flow indication on the SI headers from the HHSI pumps to the hot leg of each loop.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A LP SI FLOW FiSIO01A L HD INJ HEADER FLOW A (NL)
GPM 0 -
499.3" H20 0.0 4600.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT LPSI PUMP A DISCHARGE VARIABLE N/A N/A N/A N/A Provides flow indication from LHSI pump A.
PRINTED 09110/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A LP SI FLOW FlSIO02A L HD INJ HEADER FLOW B (NL)
GPM 0
499.3" H20 0.0 4600.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT LPSI PUMP B DISCHARGE VARIABLE N/A N/A N/A N/A Provides flow indication from LHSI pump B.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A MAIN SL 1/A RIRM201C MS LINE A RAD MON (170)
STM GEN A STEAM LINE RAD LEVEL A
MR/HR N/A 0.0398 0.1259E+8 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT MN STM SAFETY VLV RISER -
M.S.
VLV HOUSE VARIABLE N/A N/A N/A N/A Continuously monitors the 32 inch A main steam safety line indicates radiation level.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAI N/A MAIN SL 2/B RlRM202C MS LINE B RAD MON (171)
STM GEN B STEAM LINE RAD LEVEL A
MR/HR N/A 0.0398 0.1259E+8 N/A N/A P
I EXPONENTIATED VALUE OF LOGARITHMIC INPUT MN STM SAFETY VLV RISER -
M.S.
VLV HOUSE VARIABLE N/A N/A N/A N/A Continuously monitors the 32 inch B main steam safety line and indicates radiation level.
PRINTED 09/10/2002
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A MAIN SL 3/C RlRM203C MS LINE C RAD MON (172)
STM GEN C STEAM LINE RAD LEVEL A
MR/HR N/A 0.0398 0.1259E+8 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT MN STM SAFETY VLV RISER -
M.S.
VLV HOUSE VARIABLE N/A N/A N/A N/A Continuously monitors the 32 inch C main steam safety line and indicates radiation level.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A NI INTER RNG MINMO03C INTERMEDIATE RANGE POWER NUCLEAR INSTRUMENTS, INT RANGE A
AMPS 3e 120% Power 1.OE-II 1.OE-3 N/A N/A P
2 MAXIMUM -
SEE SYSTEM DESCRIPTION ADJACENT TO OUTSIDE OF REACTOR VESSEL VARIABLE N/A N/A N/A N/A The highest valid intermediate range signal is used for this point.
2 intermediate range signals are available for use.
If neither of the intermediate range signals is valid, this point is marked invalid.
The intermediate range inputs are logrithnic in nature.
Therefore, the highest valid intermediate range signal is exponentiated to yield the value for this point.
PRINTED 09/10/2002
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NAl N/A RCS LTDN RAD RlRM214C RCS LETDOWN HIGH RAD MON RAD LEVEL OF RCS LETDOWN LINE A
MR/HR N/A 1.0 1.OE+4 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT RCS LETDOWN LINE VARIABLE N/A N/A N/A N/A Continuously monitors radiation level in the reactor coolant by means of a strap-on monitor on the letdown line.
PRINTED 09/10/2002
ATTACHMENT 2 NORTH ANNA UNIT 2 UPDATED DATA POINT LIBRARY SHEETS
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A AX FD FL 1/A F2FW001A AFW FLOW TO SG A (BL)
STM GEN A AUX FEEDWATER FLOW A
GPM 0-600" H20 0.0 500.00 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEN IA VARIABLE N/A N/A N/A N/A Senses auxiliary feed pump discharge to steam generator A.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A AX FD FL 2/B F2FW002A AFW FLOW TO SG B (YW)
STM GEN B AUX FEEDWATER FLOW A
GPM 0-600" H20 0.0 500.00 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEN 1B VARIABLE N/A N/A N/A N/A Senses auxiliary feed pump discharge to steam generator B.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A AX FD FL 2/B F2FW003A AFW FLOW TO SG C (WT)
STM GEN B AUX FEEDWATER FLOW A
GPM 0-600" H20 0.0 500.00 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT AUX FEED PMP DISCH UPSTRM OF STM GEM IC VARIABLE N/A N/A N/A N/A Senses auxiliary feed pump discharge to steam generator C.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A CNTMNT RAD R2RM207C CNTMT HR RAD MON COLUMN 4 RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 0.316 1.OE+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT ON THE INSIDE CRANE WALL VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level within the reactor Containment.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A CNTMNT RAD R2RM208C CNTMT HR RAD MON COL 12 RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 0.316 1.OE+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT ON THE INSIDE CRANE WALL VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level within the reactor containment.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A CNTMNT RAD R2RM209C CNTMT PERS HATCH RAD MON RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 3.16E-5 10.0 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT OUTSIDE CONTAINMENT PERSONNEL HATCH VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level in the Personnel Hatch area.
PRINTED 09/10/2002
STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/17/2002 NA2 N/A RCS LTDN RAD R2RM214C RCS LETDOWN HIGH RAD MON RAD LEVEL OF RCS LETDOWN LINE A
MR/HR N/A 1.0 1.0E4 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT RCS LETDOWN LINE VARIABLE N/A N/A N/A N/A Continuously monitors radiation level in the reactor coolant by means of a sample from the letdown line.
PRINTED 09/17/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
MOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A CNTMNT RAD R2RM215C CNTMT AREA RAD MON RADIATION LEVEL IN CONTAINMENT A
R/HR N/A 3.16E-5 10.0 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT REACTOR CONTAINMENT VARIABLE N/A N/A N/A N/A Detects ganmma radiation in the reactor containment.
PRINTED 09/10/2002
STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A CTMNT SMP WR L2RS002C CONTAINMENT WR SUMP LEVEL CONTAINMENT SUMP WR LEVEL A
FT N/A 0.0 12.0 TNKBOT N/A P
2 AVERAGE -
SEE SYSTEM DESCRIPTION RECIRC SPRAY SUMP-SEE SYSTEM DESCRIPTION VARIABLE N/A N/A N/A N/A Two transmitters (LT-RS-251A-2 & B-2) monitor recirc spray sump level in the sump itself (0-6'8") and two additional transmitters (LT-RS-251A-I & B-l) monitor the level above the sump itself (6181-1141). The valid wide range sibnals are averaged (2 signals if all are valid).
If neither signal is valid, this point is marked invalid.
PRINTED 09/10/2002
STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A EFF GAS RAD R3RM225C PV NORMAL RAD MONITOR RADIOACTIVITY OF RELEASED GASES A
UCI/CC N/A 1.OE-7 1.OE-2 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT SWGR BLDG ELEV 307 VARIABLE N/A N/A N/A N/A Continually senses radiation level in a sample stream from the process vent.
This is the normal range instrument for this data.
PRINTED 09/10/2002
STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A EFF GAS RAD R3RM229C VS A NORMAL RADN RATE MON RADIOACTIVITY OF RELEASED GASES A
UCI/S N/A 1.OE-1 1.OE+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack 'A" and provides a signal to RG-VG179-1A's microcomputer for determination of radiation release rate.
This is the normal range instrument for this data.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A EFF GAS RAD R2RM204C AS LINE RADIATION MONITOR RADIOACTIVITY OF RELEASED GASES A
MR/HR N/A 3.98E-2 1.259E7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURBINE-DRIVEN AUX FEED PUMP EXHAUST VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level in the turbine-driven auxiliary feed pump exhaust (*Terry" turbine).
PRINTED 09/10/2002
STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A EFF LIQ RAD R3RM214C SW DISCH TO RSVR RAD MON RADIOACTIVITY OF RELEASED LIQ A
CPM N/A 3.162 1.0E+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT OFF-LINE IN A CMN HDR OF 2 36"DSCH LINES VARIABLE N/A N/A N/A N/A Continuously monitors the radiation level of the service water discharge to the service water reservoir.
PRINTED 09/10/2002
STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A H2 CONC A2GWO01C CNTMT H2 CONCENTRATION CONTAINMENT HYDROGEN CONC A
PCT N/A 0.0 10.0 N/A N/A P
2 AVERAGE -
SEE SYSTEM DESCRIPTION AUX BLDG ELEV 259 VARIABLE N/A N/A N/A N/A Takes a sample of containment atmosphere and measures the hydrogen concentration in the sample.
The valid signals are averaged (2 signals if all are valid).
If none of the signals is valid, this point is marked invalid.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A HP SI FLOW F2SIO03A TOTAL HOT LEG SI FLOW (WT)
HIGH PRESSURE SI FLOW A
GPM N/A 0.0 1000.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT CHRGING PMP DISCH UPSTRM OF HOT LEG VARIABLE N/A N/A N/A N/A Provides flow indication on the SI headers from the HHSI pumps to the hot leg of each loop.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A LP SI FLOW F2SIO01A L HD INJ HEADER FLOW A (NL)
GPM 0 -
499.3" H20 0.0 4600.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT LPSI PUMP A DISCHARGE VARIABLE N/A N/A N/A N/A Provides flow indication from LHSI pump A.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A LP SI FLOW F2SI002A L HD INJ HEADER FLOW B (NL)
GPM 0 -
499.3' H20 0.0 4600.0 N/A N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT LPSI PUMP B DISCHARGE VARIABLE N/A N/A N/A N/A Provides flow indication from LHSI pump B.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A MAIN SL I/A R2RM201C MS LINE A RAD MON (270)
STM GEN A STEAM LINE RAD LEVEL A
MR/HR N/A 3.98E-2
- 1. 259E7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT MN STM SAFETY VLV RISER -
M.S.
VLV HOUSE VARIABLE N/A N/A N/A N/A Continuously monitors the 32 inch A main steam safety line and indicates radiation level.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A MAIN SL 2/B R2RM202C MS LINE B RAD MON (271)
STM GEN B STEAM LINE RAD LEVEL A
MR/HR N/A 3.98E-2 1.259E7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT MN STM SAFETY VLV RISER -
M.S.
VLV HOUSE VARIABLE N/A N/A N/A N/A Continuously monitors the 32 inch B main steam safety line and indicates radiation level.
PRINTED 09/10/2002
STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A MAIN SL 3/C R2RM203C MS LINE C RAD MON (272)
STM GEN C STEAM LINE RAD LEVEL A
MR/HR N/A 3.98E-2 1.259E7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT MN STM SAFETY VLV RISER -
M.S.
VLV HOUSE VARIABLE N/A N/A N/A N/A Continuously monitors the 32 inch C main steam safety line and indicates radiation level.
PRINTED 09/10/2002
STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A NI INTER RNG M2NM003C INTERMEDIATE RANGE POWER NUCLEAR INSTRUMENTS, INT RANGE A
AMPS 3e 120% Power 1.OE-1l 1.OE-3 N/A N/A P
2 MAXIMUM -
SEE SYSTEM DESCRIPTION ADJACENT TO OUTSIDE OF REACTOR VESSEL VARIABLE N/A N/A N/A N/A The highest valid intermediate range signal is used for this point.
2 intermediate range signals are available for use.
If neither of the intermediate range signals is valid, this point is marked invalid.
The intermediate range inputs are logrithmic in nature.
Therefore, the highest valid intermediate range signal is exponentiated to yield the value for this point.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A SG LEVEL 1/A L2FW004A SG A WR LEVEL (NL)
STEAM GENERATOR A WATER LEVEL A
PCT 0-575" H20 0.0 100.0 TNKBOT N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT STEAM GENERATOR 2-RC-E-1A VARIABLE N/A N/A N/A WET Senses the water level in steam generator 2-RC-E-1A.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A SG LEVEL 2/B L2FW008A SG B WR LEVEL (NL)
STEAM GENERATOR B WATER LEVEL A
PCT 0-575' H20 0.0 100.0 TNKBOT N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT STEAM GENERATOR 2-RC-E-1B VARIABLE N/A N/A N/A WET Senses the water level in steam generator 2-RC-E-1B.
PRINTED 09/10/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
09/10/2002 NA2 N/A SG LEVEL 3/C L2FW012A SG C WR LEVEL (NL)
STEAM GENERATOR C WATER LEVEL A
PCT 0-575" H20 0.0 100.0 TNKBOT N/A S
N/A N/A -
THIS IS A DIRECT SENSOR INPUT STEAM GENERATOR 2-RC-E-IC VARIABLE N/A N/A N/A WET Senses the water level in steam generator 2-RC-E-1C.
PRINTED 09/10/2002
Page No.
1 STATION: North Anna PRINTED UNIT:
1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT FIFW001A AT 13:00 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 07/01/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: -0.2 IS: 0.0
Page No.
2 STATION: North Anna PRINTED UNIT:
1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F1FW002A AT 13:01 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 07/01/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: -0.2 IS: 0.0
Page No.
3 STATION: North Anna PRINTED UNIT:
1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT FlFW003A AT 13:01 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 07/01/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS:
-0.2 IS: 0.0
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 09/10/2002 CHANGED POINT LIFW004A AT 14:34 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 PLANT SPEC POINT DESC:
WAS:
Page No.
4
PRINTED 09/10/2002 STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT LIFW008A AT 14:34 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 PLANT SPEC POINT DESC:
WAS:
Page No.
5
STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 09/10/2002 CHANGED POINT LIFW012A AT 14:34 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 PLANT SPEC POINT DESC:
WAS:
Page No.
Page No.
7 STATION: North Anna PRINTED UNIT:
1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT A1GWOO1C AT 13:03 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS:
-1.5 IS: 0.0
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 09/10/2002 CHANGED POINT MlNMO03C AT 13:04 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 05/17/1991 IS: 09/10/2002 MAXIMUM INSTR RANGE:
WAS: 1.2589E-3 IS: 1.OE-3 Page No.
Page No.
9 PRINTED 09/10/2002 STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT LlRC003C AT 14:47 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 10/20/1993 IS: 09/10/2002 MAXIMUM INSTR RANGE:
WAS: 122.0 IS: 120.0
Page No.
10 STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 09/10/2002 CHANGED POINT RlRM201C AT 13:09 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 09/30/1998 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 0.03981 IS: 0.0398
Page No.
11 STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 09/10/2002 CHANGED POINT RlRM202C AT 13:09 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 09/30/1998 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 0.03981 IS: 0.0398
Page No.
12 STATION: North Anna PRINTED UNIT: 1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT RIRM203C AT 13:10 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 09/30/1998 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 0.03981 IS: 0.0398
Page No.
13 STATION: North Anna PRINTED UNIT: 1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT RlRM204C AT 13:10 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 09/30/1998 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 0.03981 IS: 0.0398
Page No.
14 PRINTED 09/10/2002 STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT RIRM207C AT 13:13 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 0.3162 IS: 0.316
Page No.
15 STATION: North Anna PRINTED UNIT:
1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R1RM208C AT 13:14 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 0.3162 IS: 0.316
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 09/10/2002 CHANGED POINT RlRM209C AT 13:15 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 3.162E-5 IS: 3.16E-5 Page No.
16
Page No.
17 STATION: North Anna PRINTED UNIT: 1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R1RM214C AT 13:16 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/07/1996 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS:
0.0 IS: 1.0
Page No.
18 PRINTED 09/10/2002 STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT RlRM215C AT 13:17 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 3.162E-5 IS: 3.16E-5
STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 09/10/2002 CHANGED POINT L1RS002C AT 13:17 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 04/29/1994 IS: 09/10/2002 MAXIMUM INSTR RANGE:
WAS: 11.33 IS: 12.00 Page No.
19
Page No.
20 PRINTED 09/10/2002 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT FISIO01A AT 13:18 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
MAXIMUM INSTR RANGE:
WAS: 05/17/1991 IS: 09/10/2002 WAS: 4000.0 IS: 4600.0
STATION:
North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT PRINTED 09/10/2002 CHANGED POINT F1SIO02A AT 13:19 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 05/17/1991 IS: 09/10/2002 MAXIMUM INSTR RANGE:
WAS: 4000.0 IS: 4600.0 Page No.
21
Page No.
22 STATION: North Anna PRINTED UNIT: 1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT FISIO03A AT 13:20 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 05/17/1991 IS: 09/10/2002 PLANT SPEC POINT DESC:
WAS: TOTAL HOT LEG SI FLOW (WT)
IS: TOTAL HOT LEG SI FLOW (WT)
Page No.
23 STATION: North Anna PRINTED UNIT:
1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM214C AT 13:21 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MAXIMUM INSTR RANGE:
WAS: 1.OE+6 IS: 1.OE+7
Page No.
24 STATION: North Anna PRINTED UNIT: 1 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM225C AT 13:21 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 01/24/2002 IS: 09/10/2002 PLANT SPEC POINT DESC:
WAS:
PV NORMAL RAD MON IS: PV NORMAL RAD MONITOR
Page No.
25 PRINTED 09/10/2002 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM229C AT 13:22 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/11/2002 IS: 09/10/2002 PLANT SPEC POINT DESC:
WAS: VS A NORM RADN RATE MON IS: VS A NORMAL RADN RATE MON
Page No.
1 STATION: North Anna PRINTED UNIT:
2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM214C AT 13:21 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MAXIMUM INSTR RANGE:
WAS: 1.OE+6 IS: 1.OE+7
Page No.
2 PRINTED 09/10/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM225C AT 13:21 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
PLANT SPEC POINT DESC:
WAS: 01/24/2002 IS: 09/10/2002 WAS:
PV NORMAL RAD MON IS: PV NORMAL RAD MONITOR
Page No.
3 PRINTED 09/10/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM229C AT 13:22 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
PLANT SPEC POINT DESC:
WAS: 03/11/2002 IS: 09/10/2002 WAS: VS A NORM RADN RATE MON IS: VS A NORMAL RADN RATE MON
Page No.
4 STATION: North Anna PRINTED UNIT:
2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2FW001A AT 15:42 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 07/01/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS:
-0.2 IS: 0.0
Page No.
5 STATION: North Anna PRINTED UNIT:
2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2FW002A AT 15:42 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 07/01/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS:
-0.2 IS: 0.0
Page No.
6 STATION: North Anna PRINTED UNIT:
2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2FW003A AT 15:43 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 07/01/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS:
-0.2 IS: 0.0
Page No.
7 PRINTED 09/10/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT L2FW004A AT 15:44 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
PLANT SPEC POINT DESC:
WAS: 03/21/1991 IS: 09/10/2002 WAS:
Page No.
8 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT L2FW008A AT 15:44 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
PLANT SPEC POINT DESC:
WAS: 03/21/1991 IS: 09/10/2002 WAS: SG B WR LEVEL (NL)
PRINTED 09/10/2002
Page No.
9 PRINTED 09/10/2002 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT L2FW012A AT 15:44 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
PLANT SPEC POINT DESC:
WAS: 03/21/1991 IS: 09/10/2002 WAS:
Page No.
10 STATION: North Anna PRINTED UNIT: 2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT A2GWO01C AT 15:45 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS:
-1.5 IS: 0.0
Page No.
11 PRINTED 09/10/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT M2NMO03C AT 15:47 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
MAXIMUM INSTR RANGE:
WAS: 05/17/1991 IS: 09/10/2002 WAS: 1.2589E-3 IS: 1.OE-3
Page No.
12 CHANGED POINT R2RM201C DATE:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
PRINTED 09/10/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT AT 15:48 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
WAS: 09/30/1998 IS: 09/10/2002 WAS: 0.03981 IS: 3.98E-2 WAS: 0.1259E+8 IS: 1.259E7
Page No.
13 CHANGED POINT R2RM202C DATE:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
PRINTED 09/10/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT AT 15:49 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
WAS: 09/30/1998 IS: 09/10/2002 WAS: 0.03981 IS: 3.98E-2 WAS: 0.1259E+8 IS: 1.259E7
Page No.
14 CHANGED POINT R2RM203C DATE:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
PRINTED 09/10/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT AT 15:59 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
WAS: 09/30/1998 IS: 09/10/2002 WAS: 0.03981 IS: 3.98E-2 WAS: 0.1259E+8 IS: 1.259E7
Page No.
15 CHANGED POINT R2RM204C AT DATE MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
PRINTED 09/10/2002 STATION: North Anna UNIT: 2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT 16:00 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
WAS: 09/30/1998 IS: 09/10/2002 WAS: 0.03981 IS: 3.98E-2 WAS: 0.1259E+8 IS: 1.259E7
Page No.
16 STATION: North Anna PRINTED UNIT:
2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R2RM207C AT 16:00 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 0.3162 IS: 0.316
Page No.
17 STATION: North Anna PRINTED UNIT: 2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R2RM208C AT 16:02 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 0.3162 IS: 0.316
Page No.
18 STATION: North Anna PRINTED UNIT:
2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R2RM209C AT 16:03 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 3.162E-5 IS: 3.16E-5
Page No.
19 STATION: North Anna PRINTED UNIT:
2 09/17/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R2RM214C AT 11:24 ON 09/17/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 05/16/1995 IS: 09/17/2002 MINIMUM INSTR RANGE:
WAS:
0.0 IS: 1.0
Page No.
20 STATION: North Anna PRINTED UNIT: 2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R2RM215C AT 16:03 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 09/10/2002 MINIMUM INSTR RANGE:
WAS: 3.162E-5 IS: 3.16E-5
Page No.
21 STATION: North Anna PRINTED UNIT:
2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT L2RS002C AT 16:04 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 04/29/1994 IS: 09/10/2002 MAXIMUM INSTRERANGE:
WAS: 11.33 IS: 12.0
Page No.
22 STATION: North Anna PRINTED UNIT:
2 09/10/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANCE REPORT CHANGED POINT F2S1001A AT 16:04 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 05/17/1991 IS: 09/10/2002 MAXIMUM INSTR RANGE:
WAS: 4000.0 IS: 4600.0
Page No.
23 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2SI002A AT 16:05 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
MAXIMUM INSTR RANGE:
WAS: 05/17/1991 IS: 09/10/2002 WAS: 4000.0 IS: 4600.0 PRINTED 09/10/2002
Page No.
24 PRINTED 09/10/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT F2SI0O3A AT 16:06 ON 09/10/2002.
CHANGES WERE AS FOLLOWS:
DATE:
PLANT SPEC POINT DESC:
WAS: 05/17/1991 IS: 09/10/2002 WAS: TOTAL HOT LEG SI FLOW (WT)
IS: TOTAL HOT LEG SI FLOW (WT)
<>