RTS Instrumentation 3.3.1 Table 3 3 1-1 (page 1 of 8)

Reactor Trip System instrumentation APPLICABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS CHANNELS CONDITIONS REQUIREMENTS VALUE(a)

1.

Manual Reactor 1,2 2

B SR 3 3.1.14 NA Trip 3 (b), 4(b), 5(b) 2 C

SR 3 3.1 14 NA

2.

Power Range Neutron Flux a

High 1,2 4

D SR 3 3 1.1

_< 112.3% RTP SR 3.3 1 2 SR 3.3 1.7 SR 3 3.1 11 SR 3 3 1.16 b

Low 1(c),2 4

E SR 3.3.1.1

< 28 3% RTP SR 3.3 1.8 SR331 11 SR 3 3 1.16 3

Power Range 1,2 4

E SR 3 3 1 7 6.3 % RTP Neutron Flux SR33 111 with time Rate - High SR 3.3 1.16 constant Positive Rate

> 2sec

4.

Intermediate 1 (c), 2 (d) 2 F, G SR 3 3.1.1

_< 35 3% RTP Range Neutron SR 3 3 1.8 Flux SR 3 3 1.11 (continued)

The Allowable Value defines the limiting safety system setting See the Bases for the Trip Setpoints With Rod Control System capable of rod withdrawal or one or more rods not fully inserted.

Below the PL10 (Power Range Neutron Flux) interlock.

Above the P-6 (Intermediate Range Neutron Flux) interlock Amendment No. 151 (a)

(b)

(c)

(d)

I CALLAWAY PLANT 3.3-17