ML021610487

From kanterella
Jump to navigation Jump to search
EN-02-021, Nuclear Management Company, LLC (Point Beach)
ML021610487
Person / Time
Site: Point Beach 
Issue date: 06/10/2002
From: Jennifer Dixon-Herrity, Luehman J
NRC/OE
To:
Nuclear Management Co
Dixon-Herrity J
References
EA-02-021 EN-02-021
Download: ML021610487 (1)


Text

PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION June 10, 2002 EN-02-021 OFFICE OF ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION Licensee:

Nuclear Management Company, LLC (EA-02-090)

(Point Beach)

Docket No. 50-301

Subject:

ISSUANCE OF FINAL SIGNIFICANCE DETERMINATION AND NOTICE OF VIOLATION This is to inform the Commission that a WHITE Significance Determination Process (SDP) finding and associated Notice of Violation will be issued on or around June 13, 2002, to Nuclear Management Company, LLC as a result of inspections at the Point Beach Nuclear Plant. This WHITE finding, an issue with low to moderate increased importance to safety, which may require additional NRC inspections, concerned the self-revealing failure of safety injection system pump 2P-15B due to nitrogen gas binding. The failure of the licensee to promptly identify and correct a significant condition adverse to quality regarding leakage from the 2T-34A safety injection accumulator was identified as a violation of 10CFR50, Appendix B, Criterion XVI, Corrective Action. Leakage of nitrogen-saturated borated water from the accumulator caused the gas binding.

It should be noted that the licensee has not been specifically informed of this action. The schedule of issuance and notification are:

Mailing of Notice of Violation June 13, 2002 Telephone Notification of licensee June 13, 2002 The State of Wisconsin will be notified.

Contacts:

J. Dixon-Herrity, OE, 415-1980 J. Luehman, OE, 415-2741 Distribution:

OWFN Chairman Meserve Comm. Dicus Comm. Diaz Comm. McGaffigan Comm. Merrifield SECY OCA PA OWFN EDO DEDR DEDE OE OGC NRR OI SP TWFN OCFO OP CENTER NMSS OIG OCIO RES ACRS IP Regional Offices RI RII RIII RIV MAIL ADAMS ADAMS ACCESSION NO. ML021610487 G:\\OECASES\\en02-021.PtBeach.wpd OE:ES OE:DD JDixon-Herrity JLuehman 06/10/2001 06/10/2001