ML021550497
| ML021550497 | |
| Person / Time | |
|---|---|
| Site: | Susquehanna |
| Issue date: | 05/24/2002 |
| From: | Susquehanna |
| To: | Document Control Desk, Office of Nuclear Security and Incident Response |
| References | |
| EP-PS-130 | |
| Download: ML021550497 (14) | |
Text
May.
24, 2002 Page 1
of 1
MANUAL HARD COPY DISTRIBUTION DOCUMENT TRANSMITTAL 2002-2644 USER INFORMATION:
FTI EMPL#:23244 CA#:
0386 Phone#: 254-3658 TRANSMITTAL INFORMATION:
-t':
05/24/2002 LOCATION:
DOCUMENT CONTROL DESK FROM:
NUCLEAR RECORDS DOCUMENT CONTROL CENTER
- NUCSA-2)
"----THE FOLLOWING CHANGES HAVE OCCURRED TO THE HARDCOPY OR ELECTRONIC MANUAL ASSIGNED TO YOU:
130 130 HP II DOSE CALCULATOR:
EMERGENCY PLAN POSITION SPECIFIC PROCEDURE REMOVE MANUAL TABLE OF CONTENTS DATE: 02/27/2002 ADD MANUAL TABLE OF CONTENTS DATE: 05/23/2002 CATEGORY:
PROCEDURES TYPE:
EP ID:
EP-PS-130 REMOVE:
REV:13 ADD:
REV:
14 UPDATES FOR HARD COPY MANUALS WILL BE DISTRIBUTED WITHIN 5
DAYS IN ACCORDANCE WITH DEPARTMENT PROCEDURES.
PLEASE MAKE ALL CHANGES AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX UPON RECEIPT OF HARD COPY.
FOR ELECTRONIC MANUAL USERS, ELECTRONICALLY REVIEW THE APPROPRIATE DOCUMENTS AND ACKNOWLEDGE COMPLETE IN YOUR NIMS INBOX.
EP-PS-130, REV 14 (HPII DOSE CALCULATOR)
REMOVE:
ADD:
REMOVE:
ADD:
REMOVE:
ADD:
REMOVE:
ADD:
REMOVE:
ADD:
REMOVE:
ADD:
REMOVE:
ADD:
TABLE OF CONTENTS, PAGES 1, 2, & 3, REV 13 TABLE OF CONTENTS, PAGES 1, 2, & 3, REV 14 TAB A, REV 2 TAB A, REV 3 TAB D, REV 5 TAB D, REV 6 TAB F, REV 5 TAB F, REV 6 TAB 15, EP-AD-098, REV 3 TAB 15, EP-AD-098, REV 4 TAB 3, (EP-AD-000-1 90, Rev 2)
TAB 3, INTENTIONALLY BLANK TAB 14, (EP-AD-000-500, Rev 0)
TAB 14, INTENTIONALLY BLANK
PROCEDURE COVER SHEET PPL SUSQUEHANNA, LLC NUCLEAR DEPARTMENT PROCEDURE HP II DOSE CALCULATOR:
Emergency Plan Position Specific Instruction EP-PS-1 30 Revision 14 Page 1 of 3 QUALITY CLASSIFICATION:
APPROVAL CLASSIFICATION:
[] QA Program
[
Non-QA Program F] Plant E] Non-Plant Z
Instruction EFFECTIVE DATE:
PERIODIC REVIEW FREQUENCY:
Two Years PERIODIC REVIEW DUE DATE:
,.* 2, "OO9t RECOMMENDED REVIEWS:
All Procedure Owner:
Nuclear Emergency Planning Responsible Supervisor:
Primary Radiation Protection Coordinator Responsible FUM:
Supvervisor-Nuclear Emergency Planning Responsible Approver:
General Manager-Plant Support FORM NDAP-QA-0002-1, Rev. 3, Page 1 of 1
EP-PS-130 Revision 14 Page 2 of 3 HP II DOSE CALCULATOR:
Emergency Plan-Position Specific Instruction WHEN:
At request of Shift Supervisor HOW NOTIFIED:
Working hours - telephone call or plant page REPORT TO:
Shift Supervisor until TSC is activated, then TSC Dose Calculator WHERE TO REPORT:
OSC initially, then TSC OVERALL DUTY:
Perform, validate, and report dose calculations.
MAJOR TASKS:
TAB:
REVISION:
Report to the Operations Support Center.
Obtain briefing from OSC Coordinator or Shift Supervisor.
Obtain meteorological data.
Withdraw vent monitor data from SPING console.
Perform dose calculations, then report results to those who request them.
Initiate radio communications with and direct OSCAR until relieved by the Health Physics Radioman.
Validate dose calculations with field reading from OSCAR and report.
Once TSC is activated, maintain dose calculations and direct clerk.
I TAB A TAB B TAB C TAB D TAB E TAB F 3
1 4
6 6
6 TAB G TAB H 5
3 I
I
EP-PS-130 Revision 14 Page 3 of 3 SUPPORTING INFORMATION:
TAB:
Emergency Telephone'Instructions TAB 1 Emergency Organization TAB 2 Intentionally Blank TAB 3 Onsite Emergency Monitoring Locations TAB 4 Emerggncy Facility Form Flow TAB 5 Emergency Classification TAB 6 Public Protective Action Recommendation Guide TAB 7 PPL Emergency Personnel Dose Assessment and TAB 8 Protective Action Recommendation (PAR) Guide Meteorological Data Acquisition TAB 9 Vent Monitor Data Acquisition TAB 10 MIDAS Dose Projection Computer Model Instructions TAB 11 PAVSS Instructions TAB 12 1-131 Frisker Measurement: Conversion Factors TAB 13 Intentionally Blank TAB 14 Remote Monitoring System Base Station Instructions TAB 15
REFERENCES:
SSES Emergency Plan NUREG-0654, Planning Standards and Evaluation Criteria NUREG-0731, Guidelines for Utility Management Structure and Technical Resources, September 1980
TAB A EP-PS-130-A Revision 3 Page 1 of 1 MAJOR TASK:
Report to the Operations Support Center.
SPECIFIC TASKS:
HOW:
- 1.
Obtain RO-2/2A and master keys for locked doors/gates.
la.
Go to the Health Physics office.
Obtain the following:
(1) High Radiation Area master keys.
(2) Passage function key and magnetic placard holder for Door 159.
(3) Source checked RO-2/2A.
- 2.
Proceed to OSC.
TAB D EP-PS-130-D Revision 6 Page 1 of 1 MAJOR TASK:
Obtain vent monitor data.
SPECIFIC TASKS:
HOW:
- 1.
Obtain vent monitor data from PICSY.
- 2.
Request Chemistry assistance to withdraw vent monitor data, if data not available from PICSY.
- 3.
If SPING is not available, consider other options.
HELP Meteorological Data Acquisition See TAB 9 HELP Vent Monitor Data Acquisition See TAB 10 3a.
Consider the use of PAVSS.
HELP PAVSS Instructions See TAB 12 3b.
Consider utilizing RMS data (e.g. Highest fixed monitor reading)
HELP Remote Monitoring System Base Station Instructions See TAB 15
TAB F EP-PS-130-F Revision 6 Page 1 of 1 MAJOR TASK:
Initiate radio communications with and direct OSCAR until relieved by the Health Physics Radioman.
SPECIFIC TASKS:
HOW:
- 1.
Initiate HP Radioman functions.
HELP HP Radioman Instruction EP-PS-134 la.
Initiate a separate Radioman's Log for the HP Radioman Position.
- 2.
Turnover control HP Radioman upon of OSCAR to his arrival.
2a.
Provide the information Radioman:
following to the HP
- 1) Name of OSCAR and YTD TEDE.
Technician
- 2)
Whether OSCAR has been dispatched.
- 3)
Whether radio contact with OSCAR has been establ-i1shed.
- 4)
OSCAR's current instructions.
- 5)
Any RMS abnormalities.
TAB 3 EP-PS-130-3 INTENTIONALLY BLANK
TAB 14 EP-PS-130-14 INTENTIONALLY BLANK
TAB 15 EP-PS-130-15 REMOTE MONITORING SYSTEM BASE STATION INSTRUCTIONS 1.0 Perform RMS Setup/Operational Check prior to initiating OSCAR field monitoring.
NOTE: For RMS keyboard command reference, see RMS Keyboard Commands included within this tab.
1.1 On the RMS terminal, open the panel located above the keyboard and rotate the power switch (first knob, right side) to the ON position.
1.2 Select the Area Monitor Coverage Screen using [<-] and [ENTER].
1.3 Input BASE for the requested user name, then [ENTER].
1.4 Input STATION for the requested password, then [ENTER].
1.5 Select [1] to bring up the Mobile Survey Plot (MSP).
1.6 Select [S] to display the System Summary Screen.
1.7 Verify RMS operability.
1.7.1 If each available Fixed and Remote Monitor reading displayed on the System Summary Screen is being updated approximately every 10 seconds, RMS is considered to be fully functional. Proceed to Tab B (depress the [1] key to restore MSP screen).
1.7.2 If all of the Fixed and Remote Monitors shown on the System Summary Screen are NOT being updated (i.e., there is no incoming radiological telemetry), then go to Tab A, Step 5a (depress the [1] key to restore the MSP screen).
2.0 Implement RMS Monitoring Strategy in accordance with the flowchart on the following page.
2.1 Use the [ESC] key to go back to the Mobile Survey Plot screen (selection #1 on the Group #5 screen).
EP-AD-000-098, Revision 4, Page 1 of 4
'Clear = Off-line
'Gray - On-line
- Yellow = Release in progress
,Red = Shelter Magenta = Evacuate Note; See RMS Field Measurement Guidelines for RMS Alarm Setpoints. -T Check Mobile Survey Plot Screen (MSPS) for status Are any of Fixed Monitor$
Fixed Monitors alarming?
yes n
yno Contact TSC Dose Calculator to:
Re-evaluate monitoring strategy.
i RMS MONI IORING STRATEGY Note 1: Alarms may occur at multiple locations. To determine status of alarms, access Event Log [E]. Use [1] to return to MSPS
[Alt] [C]
- 1) Hit the [space bar] to silence alarm and [ALT] [C] to clear OSCAR's source check alarm.
- 2) Use estimated centerline to identify/
locate the highest reading Fixed Monitor.
- 3) From MSPS, use [page up] or [page down] keys to display affected Fixed Monitor.
- 4) Use arrow keys [-- ] or [<--] to select alarming Fixed Monitor.
- 5) Hit [F4] to produce primary data report, then [Alt] [P] to print both primary and secondary data reports.
- 6) Hit [Esci to return to MSPS.
- 7) Give printed report to TSC Dose Calculator.
See Note I for multiple alarms.
no yes t,-d 15 EP-PS-130-15 When Plume Is Located:
- Continue directing OSCAR to traverse the plume as necessary.
- After plume is characterized, consult TSC Dose Calculator to determine necessity of additional traverses.
- Use [Alt] [C] after each traverse of the plume.
EP-AD-000-098, Revision 4, Page 2 of 4 Use the arrow keys to select and monitor OSCAR's progress on MSPS.
Note: OSCAR's ID in the selection box is OSCAR[.
or Have OSCAR return to their dispatch/standby location.
- 1) Notify TSC Dose Calculator.
- 2) At completion of traverse, hit [F4],
then [Alt] [P] to print report.
- 3) Give printed report to the TSC Dose Calculator.
- 4) Hit [esc] to return display to MSPS.
See Note I for multiple alarms.
Continue Monitoring Strategy:
-Track OSCAR's dose.
- Consider dose extensions.
- Utilize ALARA to minimize dose.
-Track CDE Iodine and TEDE when directed by TSC Dose Calculator via form in TAB 2 of EP-PS-134 (HP Radioman).
- Consider respiratory protection for OSCAR.
K Contact TSC Dose Calculator to:
Re-evaluate monitoring Strategy and necessity of additional OSCAR traverses.
or Discontinue monitoring with OSCAR and have OSCAR return to their dispatch location.
-0.1 I
"-i.*Direct OSCAR to monitor the 1
affected sectors.
TAB 15 EP-PS-1 30-15 RMS GAMMA DOSE R RMS FIELD MEASUREMENT GUIDELINES RELEASE SHELTERe CUATE mrem/hr T:0.1 116.0
~
160 CHILD THYROID CDE DOSE RATE:
FRISKER AIR SAMPLE (CARTRIDGE):
68.<
82.8-1 Net CPM 120 Notify TSC Dose Calculator I
ASAP ASAP IMMEDIATE MAGENTA DATA:
Indicates the need for immediate consideration of field (last column) team protective actions EP-AD-000-098, Revision 4, Page 3 of 4 8281 1200
TAB 15 EP-PS-130-15 RMS Keyboard Commands
[S]: System Summary Screen
[E]: View Event Log
[1]: Display MSP from Main Menu Return to MSP from Event Log
[*-], [4'], [4-], [---] : Move Cursor (left, up, down, right) to select displayed radiological telemetry
[ENTERJ: Inputs command / selection
[PAGE UP]: Pages Up Through System Formats
[PAGE DOWN]: Pages Down Through System Formats
[ALT] [Z]: Zoom MSP Maps In and Out
[SPACE BAR]: Silences Alarm
[F4]: Generate Report
[ALT] [P]: Print Generated Report
[ESC]: Previous Screen
[ALT] [C]: Clears OSCAR's Trail off MSP
[F8]: Transfers display source from EQE to TSC EP-AD-000-098, Revision 4, Page 4 of 4