ML021140075

From kanterella
Jump to navigation Jump to search

Technical Specifications for Amendment Nos 192 and 186, Revise Surveillance Requirements (SR) 3.0.3 to Extend Delay Period Before Entering Limiting Condition for Operation, Following Missed Surveillance
ML021140075
Person / Time
Site: Dresden  
Issue date: 04/08/2002
From: Rossbach L
NRC/NRR/DLPM
To: Skolds J
Exelon Generation Co, Exelon Nuclear
References
TAC MB3620, TAC MB3621
Download: ML021140075 (1)


Text

SR Applicability 3.0 3.0 SURVEILLANCE REQUIREMENT (SR)

APPLICABILITY SRs shall be met during the MODES or other specified conditions in the Applicability for individual

LCOs, unless otherwise stated in the SR.

Failure to meet a Surveillance, whether such failure is experienced during the performance of the Surveillance or between performances of the Surveillance, shall be failure to meet the LCO.

Failure to perform a Surveillance within the specified Frequency shall be failure to meet the LCO except as provided in SR 3.0.3.

Surveillances do not have to be performed on inoperable equipment or variables outside specified limits.

The specified Frequency for each SR is met if the Surveillance is performed within 1.25 times the interval specified in the Frequency, as measured from the previous performance or as measured from the time a specified condition of the Frequency is met.

For Frequencies specified as "once," the above interval extension does not apply.

If a Completion Time requires periodic performance on a "once per

." basis, the above Frequency extension applies to each performance after the initial performance.

Exceptions to this Specification are stated in the individual Specifications.

If it is discovered that a Surveillance was not performed within its specified Frequency, then compliance with the requirement to declare the LCO not met may be delayed, from the time of discovery, up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or up to the limit of the specified Frequency, whichever is greater.

This delay period is permitted to allow performance of the Surveillance.

A risk evaluation shall be performed for any Surveillance delayed greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and the risk impact shall be managed.

If the Surveillance is not performed within the delay period, the LCO must immediately be declared not met, and the applicable Condition(s) must be entered.

When the Surveillance is performed within the delay period and the Surveillance is not met, the LCO must immediately be declared not met, and the applicable Condition(s) must be entered.

(continued)

Amendment No.192/186 SR 3.0.1 SR 3.0.2 SR 3.0.3 Dresden 2 and 3 3.0-4