Date Entered: Apr 12, 2002 TO:

USNRCIWASHINGTON JMCKNIGHT Copy Number:

145 TRANSMITAL NUMBER:

215216 PROCEDURE NUMBER: El-1 TITLE: EMERGENCY CLASSIFICATION AND ACTIONS TRANSMITTAL: LISTED BELOW ARE NEW/REVISED PROCEDURES WHICH MUST BE IMMEDIATELY INSERTED INTO OR DISCARDED FROM YOUR PROCEDURE MANUAL.

Action Required Section or Description REMOVE AND DESTROY El-I, R/39, ATTACHMENT 1, PAGE 17 REPLACE WITH El-i, R/39, ATTACHMENT 1, PAGE 17 REISSUED TO ADD NOTE THAT WAS INADVERTENTLY LEFT OFF OF PAGE 17 FROM REVISION 38 TO REVISION 39 SIGN, DATE, AND RETURN THE ACKNOWLEDGEMENT FORM WITHIN 10 DAYS TO THE PALISADES PLANT DOCUMENT CONTROL.

SIGNATURE OR INITIALS DATE f.

Proc k El-1 Revision 39 Page 17 of 26 SITE EMERGENCY PLAN CLASSIFICATION PRIMARY COOLANT SYSTEM INTEGRITY CLASSIFICATION EMERGENCY ACTION LEVEL METHOD OF DETECTION ACTIONS UNUSUAL EVENT Unidentified or pressure boundary Calculation, OR implementation of Mandatory: 1, 3, 4, 6, 7 leakage > 10 gpm.

Off Normal Procedure ONP-23.1, "Primary Coolant Leak," QR SED Subsequent: 15, 22 Identified leakage >25 gpm.

opinion that leak rate indications warrant activation of Emergency If Needed: None Plan.

Steam Generator secondary water S/G sample analysis.

activity > 0.1pCi/gm dose equivalent 1-131.

Primary to secondary leakage Calculation, DR implementation of through any one SG A432 gallons Off Normal Procedure ONP-23.2, per day (0.3 gpm) but < 50 gpm.

"Steam Generator Tube Leak."

ALERT NOTE: Refer to Fission Product Barrier/Fuel Damage SITE AREA EMERGENCY NOTE.: Refer to Fission Product Barrier/Fuel Damage GENERAL EMERGENCY NOTE: Refer to Fission Product Barrier/Fuel Damage NOTE:

1.

Lifting of RV-2006 (Letdown Relief) as expected for plant conditions or evolutions does not require activating the emergency plan.