TABLE 3.3-4 (Continued)
ENGINEERED SAFETY FEATURE ACTUATION SYSTEM INSTRUMENTATION TRIP VALUES FUNCTIONAL UNIT
- 4.
MAIN STEAM AND FEEDWATER ISOLATION (MSIS)
- a.
Manual (Trip Buttons)
- b.
Steam Generator Pressure -
Low
- 5.
CONTAINMENT COOLING (CCAS)
- a.
Manual (Trip Buttons
- b.
Containment Pressure -
High
- c.
Pressurizer Pressure -
Low
- 6.
RECIRCULATION (RAS)
- a.
Manual (Trip Buttons)
- b.
Refueling Water Tank -
Low
- 7.
LOSS OF POWER
- a.
4.16 kv Emergency Bus Undervoltage
- b.
480 volt Emergency Bus Undervoltage ARKANSAS -
UNIT 2 TRIP SETPOINT Not Applicable
> 751 psia (2)
Not Applicable
- 18.3 psia
Ž1675 psia Not Applicable 54,400 +/- 2,370 gallons (equivalent to 6.0 +/- 0.5%
indicated level)
(4)
(4) 3/4 3-17 ALLOWABLE VALUES Not Applicable
Ž738.6 psia (2)
Not Applicable
- 18.490 psia
Ž 1643.9 psia Not Applicable between 51,050 and 58,600 gallons (equivalent to between 5.111% and 6.889%
indicated level) 2300 +/- 699 volts with a 0.64 +/- 0.34 second time delay 429.6 +/- 6.4 volts I
with an 8.0 +/- 1.0 second time delay Amendment No.
2-4, 4--,,4-44,4-&9, 2 O, 2, 243