ML021020510

From kanterella
Jump to navigation Jump to search

E-Mail Discussing Ginna Nuclear Power Plant - Revised QA Program (Tac No. MB4239)
ML021020510
Person / Time
Site: Ginna 
Issue date: 04/12/2002
From: Clark R
Office of Nuclear Reactor Regulation
To: Flaherty M
Rochester Gas & Electric Corp
Clark R, NRR/DLPM, 415-2297
References
TAC MB4239
Download: ML021020510 (2)


Text

From:

Robert Clark To:

Mark Flaherty Date:

4/12/02 2:34PM

Subject:

Ginna Revised QA Program This e-mail conveys issues to be discussed in a future conference call (Monday 4/15/02). It does not state a formal NRC staff position, and does not formally request for additional information. Disposition of issues described in this e-mail will be discussed in the conference call.

QA Issues:

1. The compensatory actions should be implemented in conformance with your Appendix B quality assurance program. With respect to compensatory actions, discuss the following:
a. How the compensatory actions conform with your corrective action program, including provisions for cause determination, recurrence control, documentation, and reporting of significant conditions to appropriate levels of management.
b. How procurement documents are revised to reflect actions which compensate for deficiencies in a suppliers quality assurance program.
c. Provisions for revising vendor documents (e.g., design documents, vendor manuals) to reflect compensatory actions.
2. Records of audits are generated and retained as quality assurance records. Compensatory actions taken to resolve deficiencies in a suppliers quality assurance program should be retained as part of the audit record. Discuss the provisions that will ensure that a complete audit record is retained, including documentation of compensatory actions.
3. The proposed alternative compensates for a suppliers "failure to comply." Describe the audit process for reinspecting areas of noncompliance, with specific reference to ANSI N45.2.12, section 4.3.2.7 and Regulatory Guide 1.144, section 4.b.
4. The proposed alternative should be revised to address timeliness requirements and inclusion of completed compensatory actions in the followup report.

cc:

Thomas Harding

Mail Envelope Properties (3CB728CC.424 : 18 : 16965)

Subject:

Ginna Revised QA Program Creation Date:

4/12/02 2:34PM From:

Robert Clark Created By:

RLC2@nrc.gov Recipients Action Date & Time rge.com Transferred 04/12/02 02:35PM Mark_Flaherty (Mark Flaherty)

Thomas_Harding CC (Thomas Harding)

Post Office Delivered Route rge.com Files Size Date & Time MESSAGE 2659 04/12/02 02:34PM Options Auto Delete:

No Expiration Date:

None Notify Recipients:

Yes Priority:

Standard Reply Requested:

No Return Notification:

None Concealed

Subject:

No Security:

Standard To Be Delivered:

Immediate Status Tracking:

Delivered & Opened DISTRIBUTION:

PUBLIC PDI-1 R/F RClark Accession Number: ML021020510 OFFICIAL RECORD COPY