ML020940461

From kanterella
Jump to navigation Jump to search
EN-02-012, Union Electric, Callaway (EA-02-046)
ML020940461
Person / Time
Site: Callaway 
Issue date: 04/04/2002
From: Luehman J
NRC/OE
To:
Union Electric Co
Shannon M
References
EA-02-046 EN-02-012
Download: ML020940461 (2)


Text

April 4, 2002 EN 02-012 OFFICE OF ENFORCEMENT NOTIFICATION OF SIGNIFICANT ENFORCEMENT ACTION Licensee:

Union Electric Company (SDP/EA-02-046)

Callaway Plant (Docket No. 50-483)

Subject:

ISSUANCE OF THE FINAL SIGNIFICANCE DETERMINATION FOR A WHITE FINDING AND NOTICE OF VIOLATION This is to inform the Commission that a Notice of Violation associated with a White Significance Determination Process (SDP) finding will be issued on or about April 9, 2002, to Union Electric Company. This White finding was the result of the staffs assessment of the significance of a condition that on multiple occasions the licensee failed to identify and correct a risk significant condition adverse to quality regarding the degraded condition of the condensate storage tank diaphragm seal. Foam from the degraded seal was eventually entrained in the auxiliary feedwater system suction piping and caused an on-demand failure of an auxiliary feedwater pump while the plant was operating at reduced power levels on December 3, 2001. This common mode failure condition resulted in a White finding under the Mitigation Systems Cornerstone in the Significance Determination Process.

It should be noted that the licensee has not yet been specifically informed of the enforcement action. The schedule of issuance and notification is:

Mailing of Notice April 9, 2002 Telephone Notification of licensee April 9, 2002 The State of Missouri will be notified.

Contacts: Mel Shannon, OE, 301-415-1003; James Luehman, OE, 301-415-2741 Distribution:

OWFN ______

OWFN ______

TWFN ______ Regional Offices Chairman Meserve EDO OCFO RI Comm. Dicus DEDR OP CTR RII Comm. Diaz DEDMRS NMSS RIII Comm. McGaffigan OE OCIO RIV Comm. Merrifield STP OIG OGC NRR RES MAIL SECY OI ACRS ADAMS/PUBLIC OCA IP PA PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION

Distribution:

OWFN ______

OWFN ______

TWFN ______ Regional Offices Chairman Meserve EDO OCFO RI Comm. Dicus DEDR OP CTR RII Comm. Diaz DEDMRS NMSS RIII Comm. McGaffigan OE OCIO RIV Comm. Merrifield STP OIG OGC NRR RES MAIL SECY OI ACRS ADAMS/PUBLIC OCA IP PA ADAMS ACCESSION NO.

Filename:C:\\ORPCheckout\\FileNET\\ML020940461.wpd OFFICE OE OE:DD NAME MShannon JLuehman DATE 04/ /02 04/ /02 PRELIMINARY INFORMATION - NOT FOR PUBLIC DISCLOSURE UNTIL VERIFICATION THAT LICENSEE HAS RECEIVED ACTION