VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 March 22, 2002 United States Nuclear Regulatory Commission Serial No.:
02-159 Attention: Document Control Desk NLOS/mm Washington, DC 20555-0001 Docket Nos.:
50-338/339 License Nos.:
NPF-4/7 Gentlemen:
VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
NORTH ANNA POWER STATION UNITS I AND 2 EMERGENCY RESPONSE DATA SYSTEM DATABASE UPDATES Modifications to four Emergency Response Data System (ERDS) points have been implemented at North Anna Power Station as a result of replacement of the process vent radiation monitors.
The radiation monitors are common to both units. The changes are detailed in the Data Point Library (DPL) reference file forms provided in Attachments 1 and 2. Attachment 3 provides the revision summary (change report) for the affected points.
No new commitments are intended by this letter.
If you have any questions concerning these results, please contact us.
Very truly yours, S. P. Sarver Director - Nuclear Licensing and Operations Support Attachments
- 1. North Anna Unit 1 Updated Data Point Library Sheets
- 2. North Anna Unit 2 Updated Data Point Library Sheets
- 3. Revision Summary
cc:
U.S. Nuclear Regulatory Commission Region II Sam Nunn Atlanta Federal Center 61 Forsyth St., SW, Suite 23 T85 Atlanta, GA 30303-8931 Mr. M. J. Morgan NRC Senior Resident Inspector North Anna Power Station Ms. K. Lynne Saul, Program Manager (diskette enclosed)
Engineering, Scientific, & Management Services Scientech, Inc.
440 West Broadway Idaho Falls, ID 83402
ATTACHMENT 1 NORTH ANNA UNIT 1 UPDATED DATA POINT LIBRARY SHEETS
STATION: North Anna DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
PRINTED UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE 03/11/2002 NAl N/A EFF GAS RAD R3RM226C VS A HIGH RAD MON RADIOACTIVITY OF RELEASED GASES A
UCI/CC N/A 1.OE-4 1.0E+5 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A".
This is the high range instrument for this data.
03/11/2002
STATION: North Anna DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
PRINTED UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE 03/11/2002 NAl N/A EFF GAS RAD R3RM227C VS A HIGH RADN RATE MON RADIOACTIVITY OF RELEASED GASES A
UCI/S N/A 1.0E+3 1.0E+13 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A" and provides a signal to RG-VG179-2A's microcomputer for determination of radiation release rate.
This is the high range instrument for this data.
03/11/2002
STATION: North Anna DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
PRINTED UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE 03/11/2002 NAl N/A EFF GAS RAD R3RM228C VS A NORMAL RAD MON RADIOACTIVITY OF RELEASED GASES A
UCI/CC N/A 1.OE-7 1.OE-2 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A".
This is the normal range instrument for this data.
03/11/2002
STATION: North Anna DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
PRINTED UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE 03/11/2002 NAl N/A EFF GAS RAD R3RM229C VS A NORM RADN RATE MON RADIOACTIVITY OF RELEASED GASES A
UCI/S N/A 1.0E-i 1.0E+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A" and provides a signal to RG-VG179-1A's microcomputer for determination of radiation release rate.
This is the normal range instrument for this data.
03/11/2002
ATTACHMENT 2 NORTH ANNA UNIT 2 UPDATED DATA POINT LIBRARY SHEETS
STATION: North Anna DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
PRINTED UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE 03/11/2002 NA2 N/A EFF GAS RAD R3RM226C VS A HIGH RAD MON RADIOACTIVITY OF RELEASED GASES A
UCI/CC N/A 1.0E-4 1.0E+5 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A".
This is the high range instrument for this data.
03/11/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
03/11/2002 NA2 N/A EFF GAS RAD R3RM227C VS A HIGH RADN RATE MON RADIOACTIVITY OF RELEASED GASES A
UCI/S N/A 1.OE+3 1.OE+13 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A" and provides a signal to RG-VG179-2A's microcomputer for determination of radiation release rate.
This is the high range instrument for this data.
PRINTED 03/11/2002
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
PRINTED 03/11/2002 03/11/2002 NA2 N/A EFF GAS RAD R3RM228C VS A NORMAL RAD MON RADIOACTIVITY OF RELEASED GASES A
UCI/CC N/A 1.OE-7 1.OE-2 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A".
This is the normal range instrument for this data.
STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE DATE:
REACTOR UNIT:
DATA FEEDER:
NRC ERDS PARAMETER:
POINT ID:
PLANT SPEC POINT DESC:
GENERIC/COND DESC:
ANALOG/DIGITAL:
ENGR UNITS/DIG STATES:
ENGR UNITS CONVERSION:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
ZERO POINT
REFERENCE:
REFERENCE POINT NOTES:
PROC OR SENS:
NUMBER OF SENSORS:
HOW PROCESSED:
SENSOR LOCATIONS:
ALARM/TRIP SETPOINTS:
NI DETECTOR POWER SUPPLY CUT-OFF POWER LEVEL:
NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:
INSTRUMENT FAILURE MODE:
TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:
LEVEL REFERENCE LEG:
UNIQUE SYSTEM DESC:
03/11/2002 NA2 N/A EFF GAS RAD R3RM229C VS A NORM RADN RATE MON RADIOACTIVITY OF RELEASED GASES A
UCI/S N/A 1.0E-I 1.0E+7 N/A N/A P
1 EXPONENTIATED VALUE OF LOGARITHMIC INPUT TURB BLDG ELEV 303 VARIABLE N/A N/A N/A N/A Senses radiation level in a sample taken from vent stack "A" and provides a signal to RG-VG179-lA's microcomputer for determination of radiation release rate.
This is the normal range instrument for this data.
PRINTED 03/11/2002
ATTACHMENT 3 REVISION
SUMMARY
Page No.
1 STATION: North Anna PRINTED UNIT:
1 03/11/2002 PWR DATA POINT LIBRARY REFERENCE PILE CHANGE REPORT CHANGED POINT R3RM226C AT 10:06 ON 03/11/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 03/11/2002 MINIMUM INSTR RANGE:
WAS: 3.162E-4 IS: 1.OE-4
Page No.
2 STATION: North Anna PRINTED UNIT:
i 03/11/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM227C AT 10:07 ON 03/11/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 03/11/2002 MINIMUM INSTR RANGE:
WAS: 1.259E+5 IS: 1.0E+3
Page No.
3 PRINTED 03/11/2002 STATION: North Anna UNIT:
1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM228C AT 10:08 ON 03/11/2002.
CHANGES WERE AS FOLLOWS:
DATE:
MAXIMUM INSTR RANGE:
WAS: 03/21/1991 IS: 03/11/2002 WAS:
10.0 IS: 1.OE-2
Page No.
4 CHANGED POINT R3RM229C AT DATE:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
PRINTED 03/11/2002 STATION: North Anna UNIT: 1 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT 10:09 ON 03/11/2002.
CHANGES WERE AS FOLLOWS:
WAS: 03/21/1991 IS: 03/11/2002 WAS: 1.OE-2 IS: 1.0E-1 WAS: 1.0E+6 IS: 1.0E+7
Page No.
1 STATION: North Anna PRINTED UNIT: 2 03/11/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM226C AT 10:06 ON 03/11/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 03/11/2002 MINIMUM INSTR RANGE:
WAS: 3.162E-4 IS: 1.OE-4
Page No.
2 STATION: North Anna PRINTED UNIT: 2 03/11/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM227C AT 10:07 ON 03/11/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 03/11/2002 MINIMUM INSTR RANGE:
WAS: 1.259E+5 IS: 1.OE+3
Page No.
3 STATION: North Anna PRINTED UNIT: 2 03/11/2002 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM228C AT 10:08 ON 03/11/2002.
CHANGES WERE AS FOLLOWS:
DATE:
WAS: 03/21/1991 IS: 03/11/2002 MAXIMUM INSTR RANGE:
WAS:
10.0 IS: 1.0E-2
Page No.
4 PRINTED 03/11/2002 STATION: North Anna UNIT:
2 PWR DATA POINT LIBRARY REFERENCE FILE CHANGE REPORT CHANGED POINT R3RM229C DATE:
MINIMUM INSTR RANGE:
MAXIMUM INSTR RANGE:
AT 10:09 ON 03/11/2002.
CHANGES WERE AS FOLLOWS:
WAS: 03/21/1991 IS: 03/11/2002 WAS: 1.0E-2 IS: 1.0E-1 WAS:
1.OE+6 IS: 1.OE+7