February 2002 Monthly Operating Report for Calvert Cliffs Nuclear Power Plant, Units 1 and 2
ML020740236
Person / Time
Site: Calvert Cliffs  
(DPR-053, DPR-069)
Issue date: 03/08/2002
From: Katz P
Constellation Nuclear
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML020740236 (7)


Text

Peter E. Katz Plant General Manager 1650 Calvert Cliffs Parkway Lusby, Maryland 20657 410 495-4101 Constellation Nuclear Calvert Cliffs Nuclear Power Plant A Member of the Constellation Energy Group March 8, 2002 U. S. Nuclear Regulatory Commission Washington, DC 20555 ATTENTION:

SUBJECT:

Document Control Desk Calvert Cliffs Nuclear Power Plant Unit Nos. 1 & 2; Docket Nos. 50-317 & 50-318 February 2002 Operating Data Reports The subject reports are being sent to you as required by Technical Specification 5.6.4.

Should you have questions, please contact Mr. Bruce B. Mrowca at (410) 495-3989.

Very truly yours, PEK/TWG/bjd Attachments cc:

R. S. Fleishman, Esquire J. E. Silberg, Esquire Director, Project Directorate I-1, NRC D. M. Skay, NRC H. J. Miller, NRC Resident Inspector, NRC R. I. McLean, DNR J. Wright, INPO K. N. Larson, ANI

OPERATING DATA REPORT Docket No.

50-317 Calvert Cliffs Unit 1 March 2, 2002 Prepared by Herman 0. Olsen Telephone: (410)495-6734 REPORTING PERIOD DESIGN ELECTRICAL RATING (NET MWe)

MAXIMUM DEPENDABLE CAP'Y (NET MWe)

FEBRUARY 2002 845 825 This month NUMBER OF HOURS REACTOR WAS CRITICAL HOURS GENERATOR ON LINE UNIT RESERVE SHUTDOWN HOURS NET ELECTRICAL ENERGY GENERATED(MWH) 360.0 358.7 0.0 279,946 Year to-Date Cumulative to Date 1,104.0 178,836.1 1,102.7 175,718.4 0.0 0.0 921,814 143,443,897

1.
2.
3.

4.

UNIT SHUTDOWNS DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE 50-317 Calvert Cliffs - U1 March 5, 2002 Herman 0. Olsen (410) 495-6734 REPORTING MONTH February 2002 1

Reason:

A - Equipment Failure B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training & License Examination F - Administrative G - Operational Error H - Other 2

Method:

1 - Manual 2 - Manual Scram.

3 - Automatic Scram.

4 - Continued 5 - Other NO.

DATE TYPE DURATION REASON' METHOD OF CAUSE/CORRECTIVE ACTIONS F:

FORCED (HOURS)

SHUTTING S:

SCHEDULED DOWN 2 COMMENTS02-001 02/02/15 5

313.3 C

1 On 02/15/02 at 2005 a reduction in power was commenced in preparation for the scheduled refueling outage. The refueling outage commenced at 2243 when the unit was removed from the grid.

DOCKET NO. 50-317 CALVERT CLIFFS - UNIT 1 March 5, 2002

SUMMARY

OF OPERATING EXPERIENCE February 2002 The unit began the month at 97% reactor power while performing PSTP-10, end of fuel cycle coastdown.

On 02/15/02 at 2005 a reduction in power was commenced in preparation for the scheduled refueling outage. The unit was removed from the grid at 2243 and the reactor was shutdown at 2357.

The following significant work was completed or in progress during the month:

Reactor vessel head was removed.

CEA uncoupling was completed.

Main Transformers are ready for removal.

The reactor entered mode 6 on 02/24/02 at 0600. The unit remained in mode 6 for the remainder of the month.

OPERATING DATA REPORT Docket No.

50-318 Calvert Cliffs Unit 2 March 2, 2002 Prepared by Herman 0. Olsen Telephone: (410)495-6734 REPORTING PERIOD DESIGN ELECTRICAL RATING (NET MWe)

MAXIMUM DEPENDABLE CAP'Y (NET MWe)

FEBRUARY 2002 845 835 This month

1. NUMBER OF HOURS REACTOR WAS CRITICAL
2.

HOURS GENERATOR ON LINE

3. UNIT RESERVE SHUTDOWN HOURS
4. NET ELECTRICAL ENERGY GENERATED(MWH) 672.0 672.0 0.0 581,615 Year-Cumulative to-Date to Date 1,416.0 1,416.0 170,215.8 168,360.7 0.0 0.0 1,227,949 138,333,827

DOCKET NO.

UNIT NAME DATE COMPLETED BY TELEPHONE 50-318 Calvert Cliffs-U2 March 5, 2002 Herman 0. Olsen (410) 495-6734 REPORT MONTH February 2002 A - Equipment Failure B - Maintenance or Test C - Refueling D - Regulatory Restriction E - Operator Training & License Examination F - Administrative G - Operational Error H - Other 2

Method:

I - Manual 2 - Manual Scram.

3 - Automatic Scram.

4 - Continued 5 - Other UNIT SHUTDOWNS NO.

DATE TYPE DURATION REASON' METHOD OF CAUSE/CORRECTIVE ACTIONS F:

FORCED (HOURS)

SHUTTING S:

SCHEDULED DOWN 2 COMMENTS There were no shutdowns this month.

DOCKET NO. 50-318 CALVERT CLIFFS - UNIT 2 March 5, 2002

SUMMARY

OF OPERATING EXPERIENCE February 2002 The unit began the month at 100% reactor power.

On 02/01/02 at 2210 power was reduced to approximately 85% for Main Turbine Valve Testing. Testing was completed on 02/02/02 and power was returned to 100% at 0350.

The unit operated at 100% power for the remainder of the month.