ML020720552

From kanterella
Jump to navigation Jump to search
Steam Generator Inspection Results -15 Day Report
ML020720552
Person / Time
Site: Prairie Island Xcel Energy icon.png
Issue date: 03/05/2002
From: Nazar M
Nuclear Management Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML020720552 (47)


Text

NMC Committed to Nuclear Excellence' Nuclear Management Company, LLC Prairie Island Nuclear Generating Plant 1717 Wakonade Dr. East

  • Welch MN 55089 March 5, 2002 Technical Specification 4.12.E U S Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT Docket No. 50-306 License No.

DPR-60 2002 Unit 2 Steam Generator Inspection Results - 15 Day Report In accordance with Technical Specification 4.12.E.1, the number of tubes plugged or sleeved in each steam generator is provided in Table 1.

Prairie Island Unit 2 RFO21 Plugs and Sleeves EOC 20 2002 Repairs BOC21 Type of Repair 21 SG 22 SG 21 SG 22 SG 21 SG 22 SG Tubes Plugged 211 217 12 23 223 240 Tubes Sleeved 0

0 0

0 0

0

"% Equivalent Plugged per SG 6.23%

6.40%

0.35%

0.68%

6.58%

7.08%

"% Equivalent Plugged per Unit 6.32%

6.83%

Delta % Plugging Between Loops 0.17%

0.50%

(28 Sleeves = 1 Plug)

Table 1 The results of the inspection of 21 Steam Generator and 22 Steam Generator were classified as Category C-3 in accordance with Technical Specification 4.12 because more than 1 % of the inspected tubes in each Steam Generator were defective. The NRC Staff was informed of the Category C-3 classification by telephone on February 12, 2002. In accordance with Technical Specification 4.12.E.3, a 30 day special report on the Category C-3 steam generator inspection will be provided by March 20, 2002.

In accordance with Technical Specification 4.12.E.2, this information will be expanded upon in the Inservice Inspection Report for Unit 2 which will be submitted within 90 days of the end of the current refueling outage.

USNRC NUCLEAR MANAGEMENT COMPANY March 5, 2002 Page 2 of 2 During the inspection and repair of tubes, F-Star (F*) and Elevated F-Star (EF*)

Alternate Repair Criteria were utilized. Elevated rerolling was done in 21 Steam Generator. There are 1858 tubes (in both steam generators) classified as F* tubes and 6 tubes (all in steam generator 21) classified as EF* tubes. In accordance with Technical Specification 4.12.E.4, the identification of F* and EF* tubes by Row and Column and the location and extent of degradation are included in Attachment 1 to this letter.

Steam generator tubing examination and repairs were conducted from February 5, 2002 through February 18, 2002. In this letter we have made no new Nuclear Regulatory Commission commitments. Please contact Jeff Kivi (651-388-1121) if you have any questions related to this letter.

Mano K. Nazar Site Vice President Prairie Island Nuclear Generating Plant c: Regional Administrator-Region Ill, NRC Senior Resident Inspector, NRC NRR Project Manager, NRC J E Silberg Attachments:

1. 21 and 22 Steam Generator EF* and F* Tube Report Unit 1 January 2001Steam Generator 15 Day and C

ATTACHMENT 1 21 and 22 Steam Generator EF* and F* Tube Report Unit 1January 2001Steam Generator 15 Day and C

CODES Landmarks TRH = TOP OF OEM HARD ROLL HOT LEG 1BH = BOTTOM OF ADDITIONAL HARD ROLL 1 2BH = BOTTOM OF ADDITIONAL HARD ROLL 2 EBH = BOTTOM OF ADDITIONAL ELEVATED HARD ROLL Types of F and EF Stars EF* = EF* TUBE WITH ELEVATED ADDITIONAL ROLL EXPANSION F*O = F* TUBE WITHOUT ADDITIONAL ROLL EXPANSION F*1 = F* TUBE WITH ONE ADDITIONAL ROLL EXPANSION F*2 = F* TUBE WITH SECOND HIGHER ADDITIONAL ROLL EXPANSION Indication Code MAD = MULTIPLE AXIAL INDICATION, No longer detectable MAI = MULTIPLE AXIAL INDICATION MAN = MULTIPLE AXIAL INDICATION, NO CHANGE SAD = SINGLE AXIAL INDICATION, No longer detectable SAI = SINGLE AXIAL INDICATION SAN = SINGLE AXIAL INDICATION, NO CHANGE SCI = SINGLE CIRCUMFERENTIAL INDICATION SVI = SINGLE VOLUMETRIC INDICATION March 5, 2002 Page 2 21 STEAM GENERATOR F*0 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 1

21 H

1 2

SAN TRH

-2.64

-2.47 F*0 2

21 H

3 3

SAN TRH

-2.72

-2.62 F*0 3

21 H

1 4

SAN TRH

-2.69

-2.36 F*0 4

21 H

1 5

SAI TRH

-2.81

-2.71 F*0 5

21 H

1 6

SAN TRH

-2.72

-2.43 F*O 6

21 H

3 6

MAN TRH

-2.31

-2.05 F*0 7

21 H

1 7

SAN TRH

-2.83

-2.72 F*0 8

21 H

2 7

MAN TRH

-2.73

-2.45 F*0 9

21 H

7 7

SAN TRH

-2.81

-2.64 F*0 10 21 H

2 8

SAN TRH

-2.77

-2.37 F*0 11 21 H

5 8

SAN TRH

-2.31

-2.04 F*0 12 21 H

4 9

SAN TRH

-2.73

-2.52 F*0 13 21 H

12 9

SAI TRH

-2.35

-2.31 F*0 14 21 H

25 9

SAI TRH

-2.75

-2.72 F*0 15 21 H

2 10 SAN TRH

-2.64

-2.43 F*0 16 21 H

15 10 SAN TRH

-2.19

-2.04 F*0 17 21 H

25 10 SAN TRH

-2.35

-2.21 F*0 18 21 H

26 10 SAI TRH

-2.73

-2.67 F*0 19 21 H

1 11 MAN TRH

-2.81

-2.47 F*0 20 21 H

3 11 MAN TRH

-2.74

-2.62 F*0 21 21 H

6 11 SAI TRH

-3.58

-3.41 F*0 22 21 H

7 11 SAI TRH

-1.61

-1.48 F*0 23 21 H

23 11 SAN TRH

-2.72

-2.6 F*0 24 21 H

27 11 SAN TRH

-2.56

-2.3 F*0 25 21 H

29 11 MAN TRH

-2.7

-2.58 F*0 26 21 H

2 12 SAN TRH

-2.6

-2.42 F*0 27 21 H

5 12 SAN TRH

-2.67

-2.58 F*0 28 21 H

15 12 SAN TRH

-2.67

-2.53 F*0 29 21 H

28 12 MAN TRH

-2.4

-2.3 F*0 30 21 H

1 13 MAN TRH

-2.94

-2.76 F*0 31 21 H

6 13 SAN TRH

-2.48

-2.36 F*0 32 21 H

7 13 MAN TRH

-2.89

-2.63 F*0 33 21 H

1 14 MAN TRH

-3.03

-2.8 F*0 34 21 H

7 15 SAN TRH

-2.83

-2.56 F*0 35 21 H

2 16 SAN TRH

-2.67

-2.52 F*0 36 21 H

3 16 SAN TRH

-2.71

-2.59 F*0 37 21 H

5 16 SAN TRH

-3.04

-2.86 F*0 38 21 H

6 16 SAI TRH

-2.7

-2.61 F*0 39 21 H

15 16 SAN TRH

-2.74

-2.59 F*0 40 21 H

5 17 MAN TRH

-2.66

-2.59 F*0 41 21 H

7 17 MAN TRH

-2.61

-2.43 F*0 42 21 H

7 18 SAI TRH

-2.5

-2.34 F*0 43 21 H

7 19 MAN TRH

-2.51

-2.41 F*0 44 21 H

8 19 SAN TRH

-2.42

-2.33 F*0 45 21 H

26 19 MAN TRH

-2.76

-2.66 F*0 46 21 H

8 20 SAI TRH

-2.71

-2.62 F*0 Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 3 21 STEAM GENERATOR F*0 TUBES, BOC21,2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 47 21 H

25 20 MAN TRH

-2.56

-2.38 F*0 48 21 H

31 20 SAI TRH

-2.75

-2.68 F*0 49 21 H

33 20 MAN TRH

-2.63

-2.52 F*0 50 21 H

32 21 MAI TRH

-2.75

-2.64 F*0 51 21 H

33 21 SAN TRH

-2.64

-2.55 F*0 52 21 H

6 22 MAI TRH

-2.47

-2.41 F*0 53 21 H

7 22 SAN TRH

-2.59

-2.47 F*0 54 21 H

7 23 SAI TRH

-2.54

-2.47 F*0 55 21 H

31 24 MAI TRH

-2.55

-2.47 F*0 56 21 H

33 24 SAN TRH

-2.52

-2.46 F*0 57 21 H

1 25 MAN TRH

-2.43

-2.37 F*0 58 21 H

24 25 MAN TRH

-2.49

-2.38 F*0 59 21 H

33 25 SAN TRH

-2.46

-2.35 F*0 60 21 H

31 28 SAN TRH

-2.45

-2.36 F*0 61 21 H

33 30 SAN TRH

-2.62

-2.37 F*0 62 21 H

17 32 SAN TRH

-2.24

-2.21 F*0 63 21 H

1 34 SAN TRH

-2.5

-2.4 F*0 64 21 H

33 34 SAN TRH

-2.62

-2.55 F*0 65 21 H

1 35 SAN TRH

-2.44

-2.37 F*0 66 21 H

25 41 SAN TRH

-2.42

-2.23 F*0 67 21 H

1 47 MAN TRH

-2.45

-2.22 F*O 68 21 H

21 47 MAN TRH

-2.5

-2.4 F*0 69 21 H

28 60 SAI TRH

-2.52

-2.34 F*0 70 21 H

26 61 SAI TRH

-2.56

-2.51 F*0 71 21 H

27 61 MAN TRH

-2.44

-2.35 F*0 72 21 H

15 62 SAN TRH

-2.58

-2.43 F*0 73 21 H

23 62 MAI TRH

-2.55

-2.43 F*0 74 21 H

28 62 SAI TRH

-2.45

-2.36 F*0 75 21 H

32 62 SAI TRH

-2.58

-2.45 F*0 76 21 H

33 62 SAI TRH

-2.66

-2.54 F*0 77 21 H

21 63 SAI TRH

-1.86

-1.74 F*0 78 21 H

26 63 SAI TRH

-2.42

-2.38 F*0 79 21 H

27 63 SAI TRH

-2.47

-2.41 F*0 80 21 H

29 63 SAN TRH

-2.62

-2.53 F*0 81 21 H

15 64 SAN TRH

-2.74

-2.63 F*0 82 21 H

23 64 SAI TRH

-2.57

-2.45 F*0 83 21 H

32 64 MAI TRH

-2.54

-2.41 F*0 84 21 H

33 64 SAI TRH

-2.5

-2.4 F*0 85 21 H

3 65 SAI TRH

-2.77

-2.74 F*0 86 21 H

15 65 SAI TRH

-2.7

-2.64 F*0 87 21 H

23 65 SAI TRH

-2.64

-2.57 F*0 88 21 H

24 65 SAI TRH

-2.63

-2.57 F*0 89 21 H

26 65 MAN TRH

-2.42

-2.32 F*0 90 21 H

30 65 SAN TRH

-2.57

-2.42 F*0 91 21 H

1 66 MAN TRH

-2.8

-2.58 F*0 92 21 H

2 66 SAN TRH

-1.92

-1.87 F*O 93 21 H

25 66 SAN TRH

-2.69

-2.49 F*0 Unit 1 January 2001 Steam Generator 15 Day and C March 5, 2002 Page 4 21 STEAM GENERATOR F*0 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 94 21 H

27 66 SAI TRH

-2.55

-2.44 F*0 95 21 H

17 67 SAN TRH

-1.57

-1.46 F*0 96 21 H

1 68 SAN TRH

-2.67

-2.55 F*0 97 21 H

6 68 SAI TRH

-2.63

-2.51 F*0 98 21 H

8 68 SAN TRH

-2.7

-2.61 F*0 99 21 H

27 68 SAN TRH

-2.56

-2.19 F*0 100 21 H

1 69 SAN TRH

-2.63

-2.48 F*0 101 21 H

24 69 MAN TRH

-2.49

-2.34 F*0 102 21 H

23 70 MAI TRH

-2.55

-2.5 F*0 103 21 H

24 70 SAN TRH

-2.31

-2.27 F*0 104 21 H

27 70 SAI TRH

-2.61

-2.51 F*0 105 21 H

30 70 SAN TRH

-2.43

-2.3 F*0 106 21 H

23 71 SAN TRH

-2.46

-2.39 F*0 107 21 H

29 71 SAI TRH

-2.55

-2.41 F*0 108 21 H

27 72 SAN TRH

-2.3

-2.23 F*0 109 21 H

31 72 MAI TRH

-2.43

-2.23 F*0 110 21 H

1 73 SAI TRH

-2.61

-2.55 F*0 111 21 H

25 73 SAN TRH

-2.48

-2.34 F*0 112 21 H

32 74 SAI TRH

-2.55

-2.51 F*0 113 21 H

1 75 SAN TRH

-2.58

-2.43 F*0 114 21 H

16 75 SAN TRH

-2.27

-2.04 F*0 115 21 H

1 76 SAN TRH

-2.57

-2.42 F*0 116 21 H

6 76 SAN TRH

-2.35

-2.09 F*0 117 21 H

16 76 SAN TRH

-2.35

-1.88 F*0 118 21 H

21 76 SAI TRH

-2.56

-2.52 F*0 119 21 H

26 76 SAI TRH

-2.33

-2.27 F*0 120 21 H

27 76 MAN TRH

-2.53

-2.4 F*0 121 21 H

1 77 SAN TRH

-2.52

-2.38 F*0 122 21 H

1 78 MAN TRH

-2.56

-2.46 F*0 123 21 H

22 78 SAI TRH

-2.34

-2.27 F*0 124 21 H

14 79 SAI TRH

-2.38

-2.18 F*0 125 21 H

20 79 SAN TRH

-2.19

-1.99 F*0 126 21 H

25 80 MAI TRH

-2.75

-2.65 F*0 127 21 H

5 81 SAI TRH

-2.64

-2.52 F*0 128 21 H

25 81 SAI TRH

-2.34

-2.31 F*0 129 21 H

16 82 SAI TRH

-2.18

-2.09 F*0 130 21 H

22 82 SAI TRH

-2.32

-2.25 F*0 131 21 H

1 83 SAI TRH

-2.57

-2.42 F*0 132 21 H

6 93 SAN TRH

-2.28

-2.21 F*0 Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 5 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. SIG LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 1

21 H

14 3

MAD IBH

-1.63 F*1 2

21 H

6 4

SAD 1BH

-1.16 F*1 3

21 H

7 4

SAD 1BH

-1 F*1 4

21 H

7 5

MAD 1BH

-1.16 F*1 5

21 H

17 7

MAD 1BH

-1.16 F*1 6

21 H

1 8

MAD 1BH

-1.31 F*1 7

21 H

13 8

MAN 1BH

-1.41

-1.33 F*1 8

21 H

5 9

SAD 1BH

-1.37 F*I 9

21 H

7 9

MAD 1BH

-1.22 F*1 10 21 H

11 9

MAN 1BH

-1.34

-1.27 F*I 11 21 H

13 9

SAD 1BH

-1.27 F*1 12 21 H

1 10 MAD 1BH

-1.39 F*1 13 21 H

4 10 SAD 1BH

-1.39 F*1 14 21 H

5 10 SAD 1BH

-1.1 F*1 15 21 H

12 10 SAD 1BH

-1.25 F*I 16 21 H

19 10 SAD 1BH

-1.05 F*I 17 21 H

20 10 SAD 1BH

-1.33 F*I 18 21 H

2 11 SAD 1BH

-0.9 F*I 19 21 H

5 11 MAN 1BH

-1.37

-1.2 F*I 20 21 H

10 11 SAD 1BH

-1.14 F*I 21 21 H

13 11 SAD 1BH

-0.79 F*I 22 21 H

14 11 MAD 1BH

-1.12 F*I 23 21 H

24 11 MAD 1BH

-1.3 F*1 24 21 H

1 12 SAD 1BH

-1.32 F*1 25 21 H

7 12 SAD 1BH

-1.07 F*I 26 21 H

9 12 SAD 1BH

-1.33 F*I 27 21 H

11 12 SAD 1BH

-1.06 F*I 28 21 H

14 12 MAN 1BH

-1.23

-0.99 F*1 29 21 H

22 12 SAD 1BH

-1.4 F*1 30 21 H

2 13 MAN 1BH

-1.38

-0.97 F*1 31 21 H

4 13 SAN 1BH

-1.3

-1.16 F*1 32 21 H

13 13 SAD 1BH

-1.4 F*1 33 21 H

14 13 SAD IBH

-1.33 F*1 34 21 H

15 13 MAN 1BH

-1.23

-1.12 F*I 35 21 H

2 14 SAN IBH

-3.61

-3.43 F*1 36 21 H

4 14 MAD 1BH

-1.22 F*1 37 21 H

5 14 SAD 1BH

-2.14 F*I 38 21 H

6 14 SAD 1BH

-1.3 F*I 39 21 H

7 14 SAN 1BH

-3.82

-3.68 F*1 40 21 H

9 14 MAD 1BH

-1.35 F*1 41 21 H

11 14 MAN 1BH

-1.14

-0.92 F*1 42 21 H

13 14 SAD IBH

-1.17 F*1 43 21 H

15 14 MAD 1BH

-1.21 F*I 44 21 H

22 14 SAD 1BH

-1.17 F*I 45 21 H

1 15 MAN 1BH

-1.04

-0.84 F*I 46 21 H

2 15 SAD 1BH

-1.38 F*1 Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 6 21 STEAM GENERATOR F*1 TUBES. BOC21. 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 47 21 H

5 15 SAD 1BH

-1.17 F*I 48 21 H

8 15 SAD 1BH

-1.21 F*1 49 21 H

10 15 SAD 1BH

-1.37 F*1 50 21 H

11 15 SAD 1BH

-0.89 F*1 51 21 H

13 15 MAN 1BH

-1.31

-0.94 F*I 52 21 H

14 15 SAD 1BH

-1.26 F*I 53 21 H

15 15 SAD 1BH

-0.9 F*I 54 21 H

16 15 MAN 1BH

-1.13

-1.02 F*1 55 21 H

18 15 MAN 1BH

-1.24

-1.13 F*I 56 21 H

19 15 MAD IBH

-1.21 F*1 57 21 H

22 15 SAD IBH

-1.22 F*1 58 21 H

23 15 SAN IBH

-1.18

-1.07 F*1 59 21 H

26 15 SAD 1BH

-0.85 F*1 60 21 H

27 15 SAD 1BH

-1.31 F*1 61 21 H

1 16 SAD 1BH

-1.34 F*1 62 21 H

4 16 MAN 1BH

-1.27

-1.13 F*1 63 21 H

7 16 SAD 1BH

-0.8 F*I 64 21 H

8 16 MAD 1BH

-1.2 F*1 65 21 H

10 16 SAD IBH

-0.88 F*I 66 21 H

12 16 MAD 1BH

-1.23 F*I 67 21 H

13 16 MAD 1BH

-1.16 F*I 68 21 H

14 16 MAD 1BH

-1.35 F*I 69 21 H

17 16 SAD 1BH

-1.28 F*I 70 21 H

18 16 SAD 1BH

-1.24 F*I 71 21 H

24 16 MAD 1BH

-1.39 F*I 72 21 H

26 16 MAD 1BH

-1.4 F*I 73 21 H

29 16 MAN 1BH

-1.04

-0.93 F*I 74 21 H

1 17 MAN 1BH

-1.17

-0.88 F*I 75 21 H

2 17 SAN 1BH

-1.42

-1.36 F*I 76 21 H

6 17 SAD 1BH

-0.92 F*1 77 21 H

10 17 SAD 1BH

-1.37 F*1 78 21 H

11 17 SAD 1BH

-1.32 F*I 79 21 H

13 17 SAD 1BH

-1.31 F*I 80 21 H

18 17 SAD 1BH

-1.27 F*I 81 21 H

19 17 SAD 1BH

-1.32 F*I 82 21 H

25 17 SAI 1BH

-1.06

-0.94 F*I 83 21 H

1 18 MAD 1BH

-1.21 F*I 84 21 H

2 18 SAD 1BH

-0.89 F*I 85 21 H

3 18 SAN 1BH

-1.09

-0.96 F*I 86 21 H

4 18 MAN 1BH

-1.29

-1.07 F*1 87 21 H

5 18 MAN IBH

-1.06

-0.84 F*I 88 21 H

10 18 MAD 1BH

-1.25 F*I 89 21 H

11 18 SAD 1BH

-1.4 F*1 90 21 H

13 18 SAD 1BH

-1.3 F*1 91 21 H

16 18 SAD 1BH

-1.44 F*I 92 21 H

18 18 MAD 1BH

-0.82 F*1 93 21 H

19 18 SAD 1BH

-1.29 F*I Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 7 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 94 21 H

20 18 SAD 1BH

-0.85 F*I 95 21 H

25 18 SAN 1BH

-2.11

-2.07 F*I 96 21 H

27 18 SAD 1BH

-1.19 F*1 97 21 H

33 18 SAN IBH

-1.34

-1.28 F*1 98 21 H

1 19 MAN 1BH

-1.16

-0.82 F*I 99 21 H

2 19 SAD 1BH

-1.39 F*1 100 21 H

4 19 SAD IBH

-1.2 F*I 101 21 H

6 19 SAD 1BH

-1.23 F*I 102 21 H

9 19 MAD 1BH

-1.2 F*1 103 21 H

11 19 MAD 1BH

-1.37 F*1 104 21 H

12 19 MAN 1BH

-1.2

-1.09 F*I 105 21 H

14 19 SAD 1BH

-0.85 F*1 106 21 H

16 19 SAD 1BH

-1.2 F*1 107 21 H

17 19 MAD 1BH

-0.86 F*1 108 21 H

19 19 MAN 1BH

-1.13

-1.04 F*I 109 21 H

20 19 SAN 1BH

-1.21

-1.15 F*I 110 21 H

22 19 MAD IBH

-0.93 F*I 111 21 H

23 19 SAD 1BH

-1.06 F*I 112 21 H

24 19 SAD 1BH

-0.9 F*I 113 21 H

25 19 MAD IBH

-1.25 F*I 114 21 H

27 19 MAD 1BH

-1.1 F*I 115 21 H

30 19 SAD 1BH

-1.37 F*I 116 21 H

31 19 MAD 1BH

-1.3 F*I 117 21 H

32 19 SAD 1BH

-1.42 F*1 118 21 H

33 19 SAD 1BH

-1.38 F*I 119 21 H

4 20 SAD IBH

-0.95 F*I 120 21 H

6 20 SAD 1BH

-0.9 F*1 121 21 H

7 20 MAN 1BH

-1.14

-0.92 F*1 122 21 H

9 20 SAD 1BH

-1.16 F*1 123 21 H

13 20 MAN 1BH

-1.2

-0.85 F*1 124 21 H

16 20 SAD 1BH

-1.2 F*I 125 21 H

17 20 MAN 1BH

-0.99

-0.89 F*I 126 21 H

18 20 SAD 1BH

-1.29 F*1 127 21 H

19 20 SAD 1BH

-1.4 F*1 128 21 H

20 20 SAN 1BH

-1.29

-1.23 F*I 129 21 H

23 20 MAD IBH

-1.42 F*1 130 21 H

27 20 MAN IBH

-1.15

-1.02 F*I 131 21 H

29 20 MAN 1BH

-1.19

-1.07 F*1 132 21 H

30 20 SAD 1BH

-1.4 F*1 133 21 H

34 20 SAD 1BH

-1.34 F*1 134 21 H

36 20 MAD 1BH

-1.37 F*1 135 21 H

37 20 MAD 1BH

-1.35 F*1 136 21 H

6 21 MAN IBH

-1.26

-1.19 F*I 137 21 H

8 21 SAD IBH

-1.15 F*I 138 21 H

11 21 SAD 1BH

-1.21 F*I 139 21 H

12 21 MAN 1BH

-1.27

-1.21 F*1 140 21 H

14 21 MAI 1BH

-0.56

-0.21 F*I Unit 1 January 2001 Steam Generator 15 Day and C March 5, 2002 Page 8 21 STEAM GENERATOR F*1 TUBES. BOC21. 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 141 21 H

16 21 MAN 1BH

-1.18

-1.12 F*l 142 21 H

17 21 MAN 1BH

-1.16

-1.07 F*1 143 21 H

20 21 MAD 1BH

-0.88 F*I 144 21 H

23 21 MAD 1BH

-1.41 F*I 145 21 H

24 21 MAN IBH

-1.21

-1.09 F*I 146 21 H

26 21 SAD 1BH

-1.25 F*1 147 21 H

27 21 SAD 1BH

-1.47 F*l 148 21 H

28 21 SAD 1BH

-0.85 F*I 149 21 H

30 21 SAD 1BH

-1.4 F*I 150 21 H

31 21 SAD 1BH

-1.27 F*1 151 21 H

1 22 MAN 1BH

-1.11

-0.99 F*I 152 21 H

2 22 MAN 1BH

-1.17

-1.05 F*I 153 21 H

4 22 MAN 1BH

-1.17

-1.07 F*I 154 21 H

5 22 SAD 1BH

-0.84 F*I 155 21 H

8 22 MAN 1BH

-1.25

-1.09 F*I 156 21 H

9 22 SAD 1BH

-1.16 F*I 157 21 H

10 22 SAD 1BH

-0.9 F*I 158 21 H

13 22 MAD 1BH

-1.2 F*I 159 21 H

14 22 MAN 1BH

-1.17

-1.08 F*I 160 21 H

16 22 MAN 1BH

-1.2

-1.11 F*I 161 21 H

17 22 MAN 1BH

-1.16

-1.02 F*I 162 21 H

18 22 SAD 1BH

-1.16 F*I 163 21 H

19 22 MAD 1BH

-1.2 F*I 164 21 H

20 22 SAD 1BH

-0.88 F*I 165 21 H

21 22 MAD 1BH

-1.31 F*I 166 21 H

24 22 MAD 1BH

-0.85 F*I 167 21 H

26 22 MAD 1BH

-0.87 F*I 168 21 H

32 22 SAD 1BH

-1.39 F*I 169 21 H

37 22 MAN 1BH

-1.49

-1.36 F*I 170 21 H

1 23 MAD 1BH

-1 F*I 171 21 H

3 23 MAN 1BH

-1.12

-0.87 F*1 172 21 H

5 23 MAN 1BH

-1.45

-1.39 F*1 173 21 H

6 23 MAN IBH

-1.21

-1.12 F*1 174 21 H

8 23 MAD 1BH

-1.3 F*1 175 21 H

9 23 MAI 1BH

-0.41

-0.19 F*1 176 21 H

10 23 SAD 1BH

-0.87 F*1 177 21 H

12 23 MAD IBH

-1.21 F*I 178 21 H

14 23 MAN 1BH

-1.2

-1.05 F*I 179 21 H

16 23 MAN 1BH

-1.22

-1.11 F*I 180 21 H

17 23 MAD 1BH

-1.3 F*I 181 21 H

19 23 MAN 1BH

-1.18

-1.07 F*I 182 21 H

23 23 MAD 1BH

-1.22 F*I 183 21 H

24 23 MAD 1BH

-0.83 F*I 184 21 H

25 23 MAD 1BH

-0.78 F*I 185 21 H

27 23 SAD 1BH

-1.17 F*I 186 21 H

30 23 MAD 1BH

-0.97 F*I 187 21 H

31 23 SAD 1BH

-1.23 F*I Unit 1 January 2001 Steam Generator 15 Day and C March 5, 2002 Page 9 21 STEAM GENERATOR F*1 TUBES. BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 188 21 H

34 23 SAD 1BH

-1.17 F*I 189 21 H

37 23 SAD 1BH

-1.38 F*1 190 21 H

38 23 MAD IBH

-1.29 F*1 191 21 H

39 23 MAD IBH

-1.38 F*1 192 21 H

4 24 MAD 1BH

-1.23 F*1 193 21 H

5 24 MAN 1BH

-1.17

-0.99 F*I 194 21 H

6 24 MAN 1BH

-1.23

-1.07 F*1 195 21 H

7 24 SAD 1BH

-1.32 F*I 196 21 H

8 24 SAD 1BH

-1.26 F*1 197 21 H

9 24 SAN IBH

-1.13

-1.03 F*1 198 21 H

11 24 MAD 1BH

-1.16 F*I 199 21 H

12 24 MAN 1BH

-1.24

-1.12 F*I 200 21 H

15 24 SAD 1BH

-0.89 F*1 201 21 H

16 24 MAD 1BH

-1.2 F*I 202 21 H

19 24 MAD 1BH

-0.82 F*I 203 21 H

20 24 MAD 1BH

-1.34 F*1 204 21 H

25 24 SAD 1BH

-1.25 F*1 205 21 H

28 24 SAD 1BH

-0.93 F*I 206 21 H

29 24 SAD 1BH

-1.14 F*1 207 21 H

30 24 MAD 1BH

-1.31 F*I 208 21 H

35 24 SAD 11BH

-0.83 F*I 209 21 H

37 24 SAD IBH

-1.32 F*I 210 21 H

5 25 SAD IBH

-1.17 F*1 211 21 H

6 25 MAD 1BH

-1.2 F*1 212 21 H

7 25 SAD 1BH

-1.3 F*I 213 21 H

8 25 SAD 1BH

-1.49 F*I 214 21 H

9 25 SAD 1BH

-0.82 F*I 215 21 H

10 25 SAD 1BH

-1.29 F*I 216 21 H

14 25 MAD 1BH

-1.29 F*I 217 21 H

16 25 SAN 1BH

-1.22

-1.12 F*I 218 21 H

17 25 SAD 1BH

-1.21 F*1 219 21 H

20 25 MAD 1BH

-1.26 F*I 220 21 H

23 25 SAD IBH

-1.21 F*I 221 21 H

28 25 SAD 1BH

-1.06 F*I 222 21 H

30 25 MAD 1BH

-1.39 F*I 223 21 H

38 25 MAD 1BH

-0.89 F*1 224 21 H

4 26 SAD 1BH

-1.32 F*1 225 21 H

5 26 SAD 1BH

-1.27 F*1 226 21 H

7 26 MAD 1BH

-1.32 F*I 227 21 H

8 26 SAD 1BH

-1.25 F*1 228 21 H

10 26 MAD 1BH

-0.91 F*1 229 21 H

13 26 MAD IBH

-1.27 F*I 230 21 H

15 26 MAD 1BH

-0.85 F*1 231 21 H

16 26 SAD 1BH

-1.26 F*I 232 21 H

17 26 SAN 1BH

-1.12

-1 F*1 233 21 H

18 26 SAD IBH

-1.32 F*I 234 21 H

19 26 MAD IBH

-1.27 F*1 Unit IJanuary 2001 Steam Generator 15 Day and C March 5, 2002 Page 10 21 STEAM GENERATOR F*l TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 235 21 H

25 26 SAD 1BH

-1.13 F*I 236 21 H

28 26 SAD 1BH

-0.93 F*I 237 21 H

34 26 SAD 1BH

-1.1 F*1 238 21 H

2 27 SAD IBH

-1.2 F*I 239 21 H

4 27 MAI 1BH

-0.72

-0.29 F*I 240 21 H

6 27 SAD 1BH

-0.87 F*I 241 21 H

8 27 SAN 1BH

-1.2

-1.11 F*I 242 21 H

9 27 SAD 1BH

-1.23 F*l 243 21 H

13 27 SAD IBH

-1.28 F*I 244 21 H

16 27 SAD 1BH

-1.21 F*I 245 21 H

17 27 MAN 1BH

-1.34

-0.98 F*I 246 21 H

26 27 MAD IBH

-1.27 F*1 247 21 H

27 27 MAD 1BH

-1.3 F*I 248 21 H

31 27 MAD 1BH

-0.79 F*1 249 21 H

32 27 SAN 1BH

-1.18

-1.06 F*1 250 21 H

35 27 SAD 1BH

-1.06 F*1 251 21 H

36 27 MAD 1BH

-1.18 F*I 252 21 H

37 27 MAD 1BH

-0.9 F*I 253 21 H

1 28 MAN IBH

-1.17

-0.96 F*1 254 21 H

3 28 MAN 1BH

-1.15

-0.97 F*l 255 21 H

5 28 MAN 1BH

-1.15

-1.03 F*I 256 21 H

6 28 SAD 1BH

-1.3 F*l 257 21 H

8 28 SAD 1BH

-1.2 F*I 258 21 H

11 28 SAD 1BH

-0.77 F*I 259 21 H

15 28 SAN 1BH

-1.16

-1.07 F*I 260 21 H

16 28 MAN 1BH

-1.28

-1.14 F*l 261 21 H

17 28 MAD 1BH

-1.17 F*1 262 21 H

18 28 MAD IBH

-1.23 F*1 263 21 H

19 28 MAN 1BH

-1.12

-0.65 F*1 264 21 H

20 28 SAD 1BH

-1.25 F*I 265 21 H

21 28 MAN 1BH

-1.36

-0.97 F*l 266 21 H

23 28 MAN 1BH

-1.31

-0.94 F*I 267 21 H

28 28 SAD 1BH

-1.18 F*I 268 21 H

30 28 SAD 1BH

-1.15 F*I 269 21 H

32 28 SAD 1BH

-0.96 F*l 270 21 H

38 28 MAN 1BH

-1.17

-1.04 F*I 271 21 H

39 28 SAD 1BH

-1.32 F*I 272 21 H

4 29 MAN 1BH

-1.2

-1.1 F*1 273 21 H

5 29 SAD 1BH

-0.89 F*1 274 21 H

7 29 MAN 1BH

-1.05

-1.01 F*1 275 21 H

8 29 MAD 1BH

-1.27 F*1 276 21 H

9 29 SAD 1BH

-0.9 F*I 277 21 H

10 29 MAD 1BH

-1.31 F*I 278 21 H

16 29 MAN IBH

-1.26

-1.13 F*l 279 21 H

18 29 MAN 1BH

-1.38

-0.95 F*I 280 21 H

19 29 MAD 1BH

-1.3 F*I 281 21 H

22 29 MAD 1BH

-1.09 F*I Unit 1 January 2001 Steam Generator 15 Day and C March 5, 2002 Page 11 21 STEAM GENERATOR F*I TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 282 21 H

23 29 MAD 1BH

-1.26 F*I 283 21 H

26 29 SAD IBH

-1.22 F*I 284 21 H

27 29 MAD 1BH

-1.27 F*t 285 21 H

28 29 MAD 1BH

-1.16 F*I 286 21 H

31 29 MAD 1BH

-1.29 F*I 287 21 H

35 29 SAD 11BH

-0.86 F*1 288 21 H

1 30 MAD 1BH

-1.42 F*1 289 21 H

3 30 MAD 1BH

-1.26 F*1 290 21 H

4 30 MAN 1BH

-0.48

-0.31 F*1 291 21 H

6 30 MAN 1BH

-1.29

-1.15 F*1 292 21 H

8 30 SAN 1BH

-1.2

-1.13 F*1 293 21 H

10 30 SAD 1BH

-1.12 F*I 294 21 H

21 30 MAD 1BH

-1.25 F*1 295 21 H

22 30 MAD 1BH

-1.2 F*1 296 21 H

26 30 SAD 1BH

-0.79 F*I 297 21 H

29 30 MAD 1BH

-0.88 F*1 298 21 H

31 30 MAD IBH

-1.2 F*I 299 21 H

38 30 SAD 1BH

-1.13 F*I 300 21 H

1 31 SAD 1BH

-1.21 F*I 301 21 H

2 31 MAD 1BH

-1 F*I 302 21 H

3 31 MAN 1BH

-0.91

-0.85 F*I 303 21 H

4 31 MAN 1BH

-1.44

-0.92 F*I 304 21 H

5 31 SAD 1BH

-1.08 F*1 305 21 H

6 31 SAN 1BH

-0.96

-0.8 F*1 306 21 H

10 31 SAD 1BH

-1.26 F*I 307 21 H

22 31 SAD 1BH

-1.27 F*I 308 21 H

26 31 SAD IBH

-0.84 F*1 309 21 H

27 31 SAD 1BH

-1.29 F*1 310 21 H

32 31 SAD 1BH

-1.36 F*I 311 21 H

34 31 MAD 1BH

-0.82 F*I 312 21 H

35 31 SAD IBH

-0.9 F*I 313 21 H

37 31 MAD 1BH

-1.23 F*I 314 21 H

1 32 MAN 1BH

-1.16

-1.02 F*1 315 21 H

3 32 MAD IBH

-1.5 F*I 316 21 H

5 32 SAD 1BH

-1.45 F*I 317 21 H

6 32 MAN 1BH

-1.42

-0.95 F*1 318 21 H

8 32 SAD 1BH

-0.97 F*1 319 21 H

24 32 MAD 1BH

-1.29 F*1 320 21 H

25 32 SAD 1BH

-1.26 F*I 321 21 H

26 32 SAD IBH

-1.18 F*1 322 21 H

27 32 SAD 1BH

-1.27 F*1 323 21 H

30 32 SAN 1BH

-1.31

-1.11 F*1 324 21 H

32 32 SAN IBH

-1.22

-1.13 F*I 325 21 H

36 32 MAD 1BH

-0.9 F*1 326 21 H

3 33 MAN 1BH

-1.18

-1.07 F*I 327 21 H

4 33 SAD 1BH

-1.3 F*I 328 21 H

7 33 MAN 1BH

-1.25

-1.14 F*I Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 12 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 329 21 H

8 33 MAN 1BH

-1.2

-1.09 F*I 330 21 H

11 33 SAD 1BH

-1.24 F*I 331 21 H

21 33 MAN 1BH

-1.35

-1.11 F*I 332 21 H

22 33 SAD 1BH

-1.27 F*I 333 21 H

23 33 SAD 1BH

-0.88 F*I 334 21 H

24 33 SAD 1BH

-1.31 F*I 335 21 H

27 33 MAN 1BH

-1.35

-1.17 F*I 336 21 H

37 33 MAD 1BH

-1.38 F*I 337 21 H

2 34 SAD 1BH

-1.24 F*1 338 21 H

3 34 SAN 1BH

-0.92

-0.82 F*I 339 21 H

4 34 SAN 1BH

-1.17

-1.11 F*I 340 21 H

7 34 SAD 1BH

-1.42 F*I 341 21 H

8 34 MAN 1BH

-1.12

-1.01 F*I 342 21 H

10 34 MAN 1BH

-1.23

-0.87 F*I 343 21 H

27 34 SAD 1BH

-0.87 F*I 344 21 H

28 34 SAD 1BH

-0.88 F*I 345 21 H

29 34 MAD 1BH

-1.22 F*I 346 21 H

34 34 MAN 1BH

-1.23

-1.2 F*1 347 21 H

37 34 MAD 1BH

-1.38 F*I 348 21 H

41 34 MAD 1BH

-1.22 F*I 349 21 H

4 35 MAD 1BH

-0.95 F*I 350 21 H

5 35 MAD 1BH

-1.18 F*I 351 21 H

8 35 MAN IBH

-1.18

-1.07 F*I 352 21 H

11 35 SAD 1BH

-1.28 F*I 353 21 H

13 35 MAN 1BH

-1.18

-1.08 F*I 354 21 H

21 35 MAD 1BH

-1.21 F*1 355 21 H

27 35 MAD 1BH

-1.2 F*I 356 21 H

29 35 SAD 1BH

-1.29 F*I 357 21 H

30 35 SAD 1BH

-1.31 F*I 358 21 H

31 35 SAD 1BH

-1.36 F*I 359 21 H

37 35 SAD 1BH

-1.45 F*I 360 21 H

3 36 SAD 1BH

-1.3 F*1 361 21 H

4 36 MAD IBH

-1.27 F*I 362 21 H

6 36 MAN 1BH

-1.16

-1.05 F*I 363 21 H

7 36 SAD 1BH

-1.27 F*I 364 21 H

8 36 MAN 1BH

-1.15

-1.03 F*I 365 21 H

9 36 SAD 1BH

-1.42 F*I 366 21 H

10 36 SAD 1BH

-1.35 F*1 367 21 H

12 36 SAD 1BH

-1.55 F*1 368 21 H

20 36 MAN IBH

-1.16

-1.04 F*1 369 21 H

22 36 SAN 1BH

-1.18

-1.09 F*1 370 21 H

23 36 MAD IBH

-1.3 F*1 371 21 H

29 36 SAD 1BH

-1.31 F*1 372 21 H

35 36 MAD 1BH

-0.86 F*1 373 21 H

36 36 SAD 1BH

-0.9 F*I 374 21 H

38 36 MAD IBH

-1.22 F*1 375 21 H

4 37 SAD 1BH

-1.33 F*1 Unit IJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 13 21 STEAM GENERATOR F*I TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 376 21 H

6 37 MAN 1BH

-1.17

-1.03 F*I 377 21 H

8 37 MAN 1BH

-0.91

-0.83 F*I 378 21 H

9 37 SAD 1BH

-0.9 F*I 379 21 H

10 37 SAD 1BH

-0.9 F*l 380 21 H

13 37 MAN 1BH

-1.16

-1.03 F*I 381 21 H

21 37 SAN 1BH

-1.12

-1.01 F*1 382 21 H

22 37 SAD 1BH

-0.8 F*I 383 21 H

25 37 SAD 1BH

-1.2 F*I 384 21 H

27 37 MAD 1BH

-1.25 F*I 385 21 H

28 37 MAD 1BH

-0.84 F*1 386 21 H

32 37 SAD 1BH

-1.2 F*I 387 21 H

33 37 SAD 1BH

-0.88 F*I 388 21 H

36 37 MAD 1BH

-1.27 F*1 389 21 H

1 38 MAD 1BH

-1.25 F*I 390 21 H

3 38 MAN 1BH

-1.19

-1.08 F*I 391 21 H

5 38 SAD 1BH

-1.35 F*1 392 21 H

7 38 MAN 1BH

-1.15

-1.07 F*1 393 21 H

8 38 MAD 1BH

-0.93 F*I 394 21 H

9 38 MAN 1BH

-1.21

-1.11 F*I 395 21 H

12 38 SAD 1BH

-1.5 F*1 396 21 H

13 38 SAN 1BH

-1.16

-1.06 F*I 397 21 H

23 38 MAD 1BH

-0.91 F*I 398 21 H

24 38 SAD 1BH

-1.18 F*I 399 21 H

30 38 MAD IBH

-1.11 F*1 400 21 H

31 38 SAD 1BH

-1.25 F*I 401 21 H

35 38 MAD 1BH

-1.26 F*1 402 21 H

37 38 MAD 1BH

-1.22 F*l 403 21 H

2 39 SAD 1BH

-1.36 F*1 404 21 H

4 39 MAN 1BH

-1.25

-0.98 F*1 405 21 H

7 39 SAD IBH

-1.35 F*1 406 21 H

9 39 SAD 1BH

-1.24 F*1 407 21 H

12 39 SAN 1BH

-1.1

-1.01 F*I 408 21 H

15 39 SAD 1BH

-0.91 F*I 409 21 H

19 39 SAD 1BH

-1.29 F*I 410 21 H

20 39 SAN 1BH

-1.27

-1.14 F*I 411 21 H

21 39 SAN 1BH

-1.2

-1.11 F*I 412 21 H

22 39 SAD 1BH

-1.28 F*I 413 21 H

24 39 SAD 1BH

-1.13 F*I 414 21 H

25 39 MAN 1BH

-1.08

-1.02 F*I 415 21 H

26 39 SAD 1BH

-1.22 F*I 416 21 H

30 39 MAD 1BH

-1.17 F*I 417 21 H

32 39 MAD 1BH

-1.23 F*I 418 21 H

35 39 SAD 1BH

-1.13 F*I 419 21 H

36 39 SAD 1BH

-1.43 F*I 420 21 H

2 40 SAN 1BH

-1.4

-1.34 F*1 421 21 H

3 40 MAD 1BH

-1.26 F*1 422 21 H

6 40 MAD IBH

-1.3 F*1 Unit IJanuary 2001 Steam Generator 15 Day and C March 5, 2002 Page 14 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 423 21 H

10 40 MAN 1BH

-1.23

-1.1 F*1 424 21 H

12 40 MAD 1BH

-1.3 F*I 425 21 H

13 40 MAD IBH

-1.56 F*1 426 21 H

26 40 MAD IBH

-1.28 F*1 427 21 H

29 40 SAD 1BH

-1.3 F*I 428 21 H

30 40 SAD IBH

-0.8 F*I 429 21 H

32 40 MAD 1BH

-1.23 F*I 430 21 H

33 40 SAD 1BH

-1.2 F*1 431 21 H

37 40 MAD 1BH

-1.14 F*1 432 21 H

1 41 SAN 1BH

-1.3

-1.24 F*1 433 21 H

2 41 SAD 1BH

-0.93 F*1 434 21 H

3 41 SAD 1BH

-1.31 F*I 435 21 H

4 41 MAN IBH

-1.44

-0.94 F*1 436 21 H

5 41 MAN 1BH

-0.97

-0.87 F*1 437 21 H

7 41 MAN 1BH

-1.23

-1.12 F*1 438 21 H

8 41 MAD 1BH

-1.27 F*1 439 21 H

11 41 SAD 1BH

-1.37 F*I 440 21 H

12 41 MAN 1BH

-1.19

-1.09 F*1 441 21 H

14 41 MAN 1BH

-0.88

-0.1 F*I 442 21 H

23 41 SAD 1BH

-0.98 F*I 443 21 H

33 41 MAD 1BH

-1.2 F*I 444 21 H

1 42 SAN 1BH

-1.39

-1.33 F*1 445 21 H

3 42 MAD 1BH

-1.22 F*1 446 21 H

5 42 MAD 1BH

-0.92 F*I 447 21 H

7 42 SAN 1BH

-1.17

-1.06 F*I 448 21 H

8 42 MAD IBH

-1.23 F*1 449 21 H

9 42 SAD 1BH

-1.23 F*I 450 21 H

10 42 SAD 1BH

-1.28 F*I 451 21 H

12 42 MAN 1BH

-1.17

-1.11 F*I 452 21 H

15 42 MAN 1BH

-1.19

-1.09 F*1 453 21 H

16 42 SAD IBH

-1.31 F*I 454 21 H

17 42 SAD 1BH

-0.8 F*I 455 21 H

20 42 SAD 1BH

-1.3 F*I 456 21 H

21 42 SAI 1BH

-0.38

-0.25 F*I 457 21 H

24 42 SAD 1BH

-1.25 F*1 458 21 H

25 42 SAD 1BH

-0.85 F*I 459 21 H

28 42 SAD 1BH

-1.05 F*1 460 21 H

36 42 MAD 1BH

-1.37 F*1 461 21 H

5 43 SAN 1BH

-1.22

-1.12 F*1 462 21 H

7 43 MAN IBH

-1.16

-1.07 F*I 463 21 H

8 43 SAN 1BH

-1.24

-1.09 F*I 464 21 H

9 43 MAN 1BH

-1.19

-1.08 F*I 465 21 H

10 43 MAN 1BH

-1.37

-1.28 F*I 466 21 H

12 43 SAN IBH

-0.93

-0.89 F*I 467 21 H

21 43 SAD IBH

-1.23 F*I 468 21 H

23 43 MAN 1BH

-1.34

-1.07 F*1 469 21 H

24 43 MAN 1BH

-1.5

-0.82 F*I Unit 1 January 2001Steam Generator 15 Day and C March 5, 2002 Page 15 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 470 21 H

30 43 SAD 1BH

-0.8 F*I 471 21 H

32 43 SAD 1BH

-1.1 F*1 472 21 H

35 43 SAD 1BH

-1.18 F*I 473 21 H

1 44 MAD 1BH

-1.32 F*1 474 21 H

3 44 SAD IBH

-1.3 F*1 475 21 H

4 44 MAD 1BH

-1.25 F*1 476 21 H

8 44 SAD 1BH

-0.9 F*1 477 21 H

9 44 MAD 1BH

-1.25 F*1 478 21 H

12 44 MAD 1BH

-0.95 F*I 479 21 H

13 44 SAD 1BH

-0.93 F*I 480 21 H

19 44 SAD 1BH

-1.3 F*I 481 21 H

21 44 SAD 1BH

-1.3 F*I 482 21 H

22 44 SAD 1BH

-0.9 F*I 483 21 H

24 44 MAN 1BH

-1.33

-1.08 F*I 484 21 H

1 45 SAD 1BH

-1.36 F*I 485 21 H

3 45 MAN 1BH

-1.38

-0.97 F*I 486 21 H

6 45 SAD 1BH

-1.18 F*I 487 21 H

9 45 SAN 1BH

-1.22

-1.1 F*1 488 21 H

10 45 MAD 1BH

-0.89 F*I 489 21 H

13 45 MAN 1BH

-1.4

-0.85 F*I 490 21 H

14 45 SAN 1BH

-0.88

-0.82 F*I 491 21 H

16 45 SAD 1BH

-1.3 F*I 492 21 H

21 45 MAD 1BH

-1.22 F*1 493 21 H

23 45 SAD IBH

-1.33 F*I 494 21 H

32 45 MAD IBH

-1.26 F*1 495 21 H

34 45 SAD 1BH

-1.07 F*1 496 21 H

1 46 SAN 1BH

-1.25

-1.19 F*I 497 21 H

3 46 MAN 1BH

-1.2

-1 F*I 498 21 H

4 46 MAN 1BH

-1.24

-1.12 F*I 499 21 H

5 46 SAD 1BH

-1.35 F*1 500 21 H

6 46 MAD 1BH

-1.55 F*I 501 21 H

7 46 SAD 1BH

-1.43 F*I 502 21 H

8 46 MAN 1BH

-1.31

-1.15 F*I 503 21 H

10 46 MAD 1BH

-1.49 F*1 504 21 H

14 46 MAN 1BH

-1.29

-1.07 F*I 505 21 H

15 46 SAD 1BH

-0.93 F*I 506 21 H

16 46 MAD 1BH

-1.36 F*I 507 21 H

17 46 SAD 1BH

-1.25 F*1 508 21 H

19 46 SAD 1BH

-1.18 F*I 509 21 H

21 46 SAD IBH

-1.25 F*1 510 21 H

22 46 MAI IBH

-0.33

-0.04 F*1 511 21 H

24 46 MAN 1BH

-0.62

-0.12 F*1 512 21 H

27 46 SAD 1BH

-0.85 F*I 513 21 H

28 46 MAD IBH

-1.28 F*1 514 21 H

34 46 MAD 1BH

-1.27 F*I 515 21 H

3 47 MAD 1BH

-1.41 F*I 516 21 H

4 47 MAN 1BH

-1.29

-1.07 F*I Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 16 21 STEAM GENERATOR F*I TUBES, BOC21, 2002 NO. SIG LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 517 21 H

8 47 SAN IBH

-1.12

-1.06 F*1 518 21 H

9 47 SAD 1BH

-0.75 F*I 519 21 H

11 47 MAD 1BH

-1.18 F*I 520 21 H

12 47 SAN 1BH

-0.86

-0.73 F*I 521 21 H

13 47 MAN 1BH

-1.31

-1.01 F*I 522 21 H

19 47 MAD 1BH

-1.28 F*I 523 21 H

22 47 MAD 1BH

-1.27 F*I 524 21 H

23 47 MAD 1BH

-1.19 F*I 525 21 H

24 47 MAD 1BH

-1.32 F*1 526 21 H

27 47 SAD 1BH

-1.47 F*1 527 21 H

31 47 SAD 1BH

-1.31 F*1 528 21 H

34 47 SAD 1BH

-1.2 F*1 529 21 H

36 47 MAD IBH

-1.1 F*I 530 21 H

37 47 SAD 1BH

-1.6 F*I 531 21 H

1 48 SAD IBH

-1.29 F*1 532 21 H

3 48 SAD IBH

-1.34 F*I 533 21 H

4 48 MAN 1BH

-1.27

-0.85 F*I 534 21 H

5 48 SAD 1BH

-1.36 F*I 535 21 H

6 48 SAN 1BH

-1.09

-1.02 F*I 536 21 H

9 48 SAD 1BH

-1.36 F*I 537 21 H

11 48 MAD 1BH

-1.41 F*I 538 21 H

12 48 MAD 1BH

-1.31 F*1 539 21 H

16 48 SAD 1BH

-0.89 F*1 540 21 H

18 48 SAN 1BH

-0.45

-0.24 F*1 541 21 H

20 48 MAN 1BH

-1.31

-1.24 F*1 542 21 H

22 48 MAD 1BH

-1.15 F*I 543 21 H

23 48 MAD 1BH

-1.31 F*I 544 21 H

28 48 SAD 1BH

-0.92 F*I 545 21 H

30 48 MAD 1BH

-1.16 F*I 546 21 H

1 49 MAD 1BH

-0.91 F*I 547 21 H

3 49 SAD 1BH

-1.36 F*I 548 21 H

4 49 MAD 1BH

-1.39 F*I 549 21 H

7 49 MAD 1BH

-1.39 F*I 550 21 H

11 49 MAD 1BH

-1.36 F*I 551 21 H

12 49 MAI 1BH

-0.25

-0.16 F*1 552 21 H

13 49 MAN IBH

-1.31

-1.01 F*1 553 21 H

14 49 SAN 1BH

-0.65

-0.49 F*I 554 21 H

23 49 SAD 1BH

-0.88 F*1 555 21 H

24 49 SAD 1BH

-0.87 F*I 556 21 H

25 49 MAD 1BH

-0.88 F*I 557 21 H

28 49 SAD 1BH

-1.33 F*I 558 21 H

29 49 MAD 1BH

-1.26 F*1 559 21 H

31 49 SAD 1BH

-1.26 F*I 560 21 H

36 49 SAD 1BH

-1.26 F*1 561 21 H

2 50 MAN 1BH

-1.41

-0.88 F*1 562 21 H

3 50 SAD 1BH

-0.9 F*1 563 21 H

4 50 MAN 1BH

-1.31

-0.89 F*I Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 17 21 STEAM GENERATOR F*1 TUBES, BOC21,2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 564 21 H

5 50 MAN 1BH

-1.25

-1.05 F*I 565 21 H

7 50 MAN 1BH

-1.09

-0.96 F*I 566 21 H

8 50 MAD 1BH

-0.93 F*I 567 21 H

10 50 MAN 1BH

-1.09

-1.02 F*I 568 21 H

12 50 MAN 1BH

-0.44

-0.23 F*I 569 21 H

18 50 MAD 1BH

-1.21 F*I 570 21 H

19 50 MAD 1BH

-0.9 F*I 571 21 H

21 50 SAD 1BH

-1.3 F*I 572 21 H

24 50 MAN 1BH

-0.62

-0.24 F*I 573 21 H

25 50 SAD IBH

-1.26 F*I 574 21 H

37 50 SAD 1BH

-0.9 F*I 575 21 H

1 51 SAN 1BH

-1.03

-0.99 F*I 576 21 H

2 51 SAD 1BH

-1.37 F*1 577 21 H

4 51 MAN 1BH

-1.05

-0.98 F*I 578 21 H

5 51 MAN 1BH

-1.15

-1.04 F*1 579 21 H

6 51 MAD 1BH

-1.27 F*1 580 21 H

8 51 MAN 1BH

-1.34

-0.86 F*1 581 21 H

11 51 SAD 1BH

-1.75 F*1 582 21 H

12 51 MAD 1BH

-1.3 F*1 583 21 H

13 51 SAD 1BH

-1.41 F*I 584 21 H

14 51 SAD 1BH

-1.35 F*I 585 21 H

15 51 SAD IBH

-1.28 F*I 586 21 H

16 51 MAD 1BH

-1.28 F*I 587 21 H

18 51 MAD IBH

-1.3 F*I 588 21 H

23 51 MAD 1BH

-0.88 F*I 589 21 H

26 51 SAD IBH

-1.34 F*1 590 21 H

29 51 MAN 1BH

-1.3

-1.26 F*I 591 21 H

34 51 MAD 1BH

-0.84 F*I 592 21 H

35 51 SAD 1BH

-0.86 F*I 593 21 H

37 51 MAD 1BH

-1.31 F*I 594 21 H

1 52 SAN 1BH

-1

-0.93 F*I 595 21 H

2 52 MAN 1BH

-1.47

-0.93 F*I 596 21 H

3 52 MAN 1BH

-1.21

-1.11 F*I 597 21 H

4 52 MAN IBH

-1.21

-1.12 F*I 598 21 H

5 52 MAD 1BH

-1.38 F*I 599 21 H

7 52 SAD IBH

-1.31 F*1 600 21 H

9 52 SAD IBH

-1.34 F*1 601 21 H

10 52 SAD 1BH

-1.36 F*1 602 21 H

11 52 SAD 1BH

-1.34 F*I 603 21 H

14 52 MAN IBH

-1.26

-0.89 F*1 604 21 H

15 52 MAD 1BH

-1.31 F*I 605 21 H

16 52 SAD 1BH

-0.88 F*I 606 21 H

18 52 SAD 1BH

-0.9 F*I 6 0 7 21 H

19 52 MAN 1BH

-1.4

-1.33 F*I 608 21 H

20 52 MAD 1BH

-0.89 F*I 609 21 H

22 52 SAD 1BH

-1.27 F*1 610 21 H

25 52 SAD 1BH

-1.36 F*1 Unit 1 January 2001 Steam Generator 15 Day and C March 5, 2002 Page 18 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 611 21 H

30 52 MAD 1BH

-1.34 F*I 612 21 H

35 52 SAD 1BH

-0.9 F*I 613 21 H

2 53 SAD tBH

-0.93 F*I 614 21 H

3 53 MAD 1BH

-1.4 F*I 615 21 H

4 53 SAN 1BH

-1.32

-1.21 F*I 616 21 H

7 53 MAN 1BH

-0.71

-0.43 F*I 617 21 H

10 53 SAN 1BH

-1.13

-1.01 F*l 618 21 H

11 53 SAN 1BH

-1.47

-1.42 F*1 619 21 H

12 53 SAN 1BH

-1.23

-1.06 F*1 620 21 H

13 53 MAD 1BH

-1.33 F*1 621 21 H

14 53 MAN 1BH

-1.5

-1.33 F*1 622 21 H

18 53 SAD 1BH

-1.1 F*1 623 21 H

20 53 SAD 1BH

-1.3 F*I 624 21 H

21 53 SAD 1BH

-0.95 F*1 625 21 H

22 53 SAD 1BH

-0.85 F*1 626 21 H

27 53 MAD 1BH

-0.88 F*I 627 21 H

35 53 SAD 1BH

-0.84 F*I 628 21 H

1 54 SAN 1BH

-1.21

-1.14 F*I 629 21 H

2 54 SAD 1BH

-1.48 F*I 630 21 H

7 54 MAN 1BH

-1.19

-1.08 F*I 631 21 H

10 54 SAD 1BH

-0.92 F*1 632 21 H

13 54 MAD 1BH

-1.38 F*I 633 21 H

14 54 SAD 1BH

-1.37 F*1 634 21 H

17 54 MAD 1BH

-1.16 F*1 635 21 H

18 54 SAD 1BH

-1.21 F*1 636 21 H

19 54 MAN 1BH

-1.26

-1.13 F*I 637 21 H

20 54 SAD 1BH

-1.32 F*I 638 21 H

21 54 MAD 1BH

-1.1 F*I 639 21 H

27 54 SAD IBH

-1.31 F*I 640 21 H

29 54 MAD 1BH

-1.32 F*I 641 21 H

34 54 SAD 1BH

-1.29 F*I 642 21 H

7 55 SAD 1BH

-1.58 F*I 643 21 H

10 55 MAN 1BH

-1.27

-0.84 F*I 644 21 H

12 55 SAD 1BH

-1.4 F*1 645 21 H

15 55 MAD 1BH

-1.33 F*I 646 21 H

18 55 MAD 1BH

-0.85 F*I 647 21 H

23 55 MAD 1BH

-1.19 F*1 648 21 H

29 55 SAD 1BH

-1.3 F*I 649 21 H

31 55 SAD 1BH

-0.85 F*I 650 21 H

33 55 SAD 1BH

-0.9 F*1 651 21 H

2 56 MAN IBH

-0.41

-0.24 F*I 652 21 H

4 56 MAD 1BH

-1.54 F*I 653 21 H

6 56 MAN 1BH

-1.16

-1.04 F*I 654 21 H

9 56 MAD 1BH

-1.27 F*I 655 21 H

10 56 MAN 1BH

-1.29

-0.91 F*I 656 21 H

13 56 SAD IBH

-0.85 F*1 657 21 H

18 56 SAD IBH

-1.35 F*I Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 19 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 658 21 H

22 56 SAD 1BH

-1.35 F*I 659 21 H

27 56 SAD 1BH

-0.88 F*1 660 21 H

29 56 SAD 1BH

-1.31 F*1 661 21 H

34 56 MAD 1BH

-0.85 F*I 662 21 H

2 57 MAD 1BH

-1.43 F*1 663 21 H

3 57 MAN 1BH

-1.29

-1.22 F*1 664 21 H

4 57 SAD 1BH

-1.28 F*I 665 21 H

5 57 SAD 1BH

-1.5 F*I 666 21 H

6 57 MAN 1BH

-1.2

-1.01 F*1 667 21 H

7 57 MAD 1BH

-1.36 F*1 668 21 H

8 57 MAN 1BH

-0.72

-0.02 F*I 669 21 H

12 57 MAD 1BH

-1.38 F*1 670 21 H

13 57 MAN IBH

-1.22

-0.76 F*1 671 21 H

14 57 SAD 1BH

-1.3 F*1 672 21 H

15 57 MAD IBH

-1.37 F*1 673 21 H

17 57 SAD 1BH

-1.3 F*1 674 21 H

18 57 MAD IBH

-1.3 F*1 675 21 H

19 57 SAD 1BH

-1.28 F*I 676 21 H

21 57 MAD IBH

-0.87 F*1 677 21 H

23 57 MAN IBH

-1.17

-0.96 F*1 678 21 H

25 57 SAN 1BH

-1.31

-1.25 F*1 679 21 H

27 57 SAD 1BH

-1.11 F*1 680 21 H

2 58 SAD 1BH

-1.39 F*1 681 21 H

3 58 SAD 1BH

-1 F*I 682 21 H

4 58 MAD 1BH

-1.41 F*I 683 21 H

5 58 MAN IBH

-1.32

-1.08 F*1 684 21 H

11 58 SAD IBH

-1.2 F*I 685 21 H

14 58 MAN 1BH

-1.17

-1.1 F*1 686 21 H

16 58 MAN 1BH

-1.31

-0.85 F*1 687 21 H

18 58 SAD 1BH

-1.32 F*1 688 21 H

21 58 MAN 1BH

-1.36

-1.02 F*1 689 21 H

23 58 SAD 1BH

-1.32 F*1 690 21 H

1 59 MAD 1BH

-1.37 F*1 691 21 H

3 59 SAD 1BH

-1.29 F*1 692 21 H

6 59 MAD 1BH

-1.38 F*1 693 21 H

8 59 MAN 1BH

-1.35

-0.96 F*1 694 21 H

9 59 MAD 1BH

-1.39 F*1 695 21 H

10 59 MAN 1BH

-1.13

-1.01 F*1 696 21 H

11 59 MAN 1BH

-1.19

-1.11 F*1 697 21 H

12 59 MAN 1BH

-1.44

-1.38 F*1 698 21 H

13 59 MAN 1BH

-1.28

-0.96 F*1 699 21 H

14 59 MAN 1BH

-1.3

-1.26 F*1 700 21 H

17 59 SAD IBH

-1.32 F*I 701 21 H

21 59 SAD 1BH

-1.28 F*I 702 21 H

27 59 SAD 1BH

-0.96 F*I 703 21 H

28 59 SAD 1BH

-1.2 F*I 704 21 H

31 59 MAD 1BH

-1.34 F*I Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 20 21 STEAM GENERATOR F*1 TUBES. BOC21. 2002

° Unit lJanuary 2001Steam Generator 15 Day and C NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 705 21 H

33 59 SAD 1BH

-1.39 F*1 706 21 H

3 60 MAN 1BH

-1.29

-1.18 F*I 707 21 H

5 60 MAN 1BH

-1.33

-1.14 F*1 708 21 H

7 60 SAN IBH

-1.18

-0.99 F*I 709 21 H

9 60 MAN 1BH

-1.23

-1.11 F*I 710 21 H

11 60 MAN 1BH

-1.27

-0.91 F*I 711 21 H

14 60 MAN 1BH

-1.19

-1.04 F*1 712 21 H

16 60 MAN 1BH

-1.15

-1 F*I 713 21 H

17 60 MAD 1BH

-1.34 F*I 714 21 H

23 60 MAD 1BH

-1.29 F*1 715 21 H

24 60 SAD IBH

-0.93 F*1 716 21 H

25 60 MAD 1BH

-0.98 F*I 717 21 H

29 60 MAD IBH

-1.27 F*I 718 21 H

2 61 MAN 1BH

-1.32

-1.07 F*1 719 21 H

3 61 MAN 1BH

-1.39

-1.29 F*I 720 21 H

4 61 SAD IBH

-1.26 F*1 721 21 H

5 61 MAN 1BH

-1.3

-1.24 F*1 722 21 H

6 61 MAN 1BH

-1.95

-1.65 F*1 723 21 H

9 61 MAN 1BH

-1.2

-1.13 F*1 724 21 H

10 61 MAN 1BH

-1.21

-1.09 F*I 725 21 H

13 61 MAI 1BH

-0.55

-0.21 F*I 726 21 H

17 61 MAN 1BH

-1.23

-1.13 F*I 727 21 H

19 61 SAD 1BH

-1.32 F*I 728 21 H

23 61 SAD IBH

-1.35 F*1 729 21 H

24 61 SAD 1BH

-1.32 F*I 730 21 H

31 61 SVI 1BH

-1.64

-1.39 F*I 731 21 H

33 61 MAD 1BH

-1.42 F*1 732 21 H

37 61 SAD 1BH

-1.33 F*1 733 21 H

1 62 SAN 1BH

-1.46

-1.4 F*I 734 21 H

2 62 MAN IBH

-1.12

-1.02 F*I 735 21 H

3 62 SAN 1BH

-1.36

-1.29 F*1 736 21 H

5 62 MAN 1BH

-1.22

-1.11 F*I 737 21 H

6 62 SAN 1BH

-1.47

-1.4 F*I 738 21 H

8 62 MAN 1BH

-1.24

-1.16 F*t 739 21 H

12 62 SAN 1BH

-1.25

-1.15 F*I 740 21 H

13 62 MAD IBH

-1.34 F*I 741 21 H

14 62 MAN 1BH

-1.28

-1.06 F*1 742 21 H

17 62 MAD IBH

-1.42 F*1 743 21 H

21 62 SAD 1BH

-1.1 F*1 744 21 H

27 62 MAD 1BH

-0.83 F*1 745 21 H

35 62 MAD 1BH

-1.35 F*1 746 21 H

36 62 SAD 1BH

-1.35 F*I 747 21 H

37 62 SAD IBH

-0.9 F*I 748 21 H

38 62 SAN IBH

-1.32

-1.27 F*1 749 21 H

3 63 MAN 1BH

-1.17

-0.97 F*I 750 21 H

5 63 MAN 1BH

-1.22

-1.09 F*1 751 21 H

7 63 SAD IBH

-1.4 F*I

Aftachment 1 March 5, 2002 Page 21 21 STEAM GENERATOR F*1 TUBES. BOC2I. 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 752 21 H

9 63 SAD 1BH

-1.34 F*I 753 21 H

11 63 SAD 1BH

-1.39 F*I 754 21 H

14 63 MAD IBH

-1.37 F*I 755 21 H

16 63 SAD 1BH

-1.33 F*I 756 21 H

18 63 SAD IBH

-0.89 F*I 757 21 H

19 63 MAI 1BH

-0.69

-0.16 F*I 758 21 H

25 63 MAD 1BH

-1.3 F*I 759 21 H

28 63 MAD 1BH

-1.3 F*I 760 21 H

34 63 SAD 1BH

-1.32 F*I 761 21 H

36 63 SAD 1BH

-0.89 F*I 762 21 H

37 63 MAD 1BH

-1.38 F*I 763 21 H

1 64 SAD 1BH

-1.31 F*I 764 21 H

3 64 SAN IBH

-1.18

-1.11 F*I 765 21 H

4 64 MAN 1BH

-1.19

-1.09 F*I 766 21 H

5 64 MAN 1BH

-1.49

-1.12 F*I 767 21 H

6 64 MAN 1BH

-1.05

-0.97 F*I 768 21 H

7 64 MAN 1BH

-1.2

-1.1 F*I 769 21 H

10 64 MAD 1BH

-1.28 F*I 770 21 H

11 64 MAN 1BH

-1.59

-1.54 F*I 771 21 H

12 64 MAN 1BH

-1.12

-1 F*I 772 21 H

14 64 MAN 1BH

-1.21

-1.11 F*I 773 21 H

19 64 MAD 1BH

-1.38 F*1 774 21 H

22 64 SAD IBH

-1.35 F*1 775 21 H

29 64 SAD 1BH

-0.8 F*I 776 21 H

34 64 MAD 1BH

-1.22 F*I 777 21 H

35 64 SAD 1BH

-1.28 F*I 778 21 H

37 64 SAD 1BH

-1.34 F*I 779 21 H

1 65 MAN 1BH

-1.25

-1.22 F*I 780 21 H

2 65 SAD 1BH

-1.42 F*I 781 21 H

4 65 SAD 1BH

-1.4 F*I 782 21 H

5 65 MAN 1BH

-1.23

-1.13 F*1 783 21 H

8 65 SAN IBH

-1.24

-1.13 F*I 784 21 H

10 65 MAN 1BH

-1.24

-1.17 F*I 785 21 H

12 65 MAN IBH

-1.22

-1.07 F*I 786 21 H

13 65 MAD 1BH

-1.27 F*I 787 21 H

14 65 SAD 1BH

-1.19 F*I 788 21 H

16 65 SAN 1BH

-1.14

-1.06 F*I 789 21 H

17 65 MAD 1BH

-1.33 F*I 790 21 H

18 65 SAD 1BH

-1.36 F*1 791 21 H

20 65 SAD 1BH

-1 F*I 792 21 H

25 65 SAD 1BH

-0.79 F*1 793 21 H

40 65 MAD 1BH

-1.32 F*I 794 21 H

3 66 MAN 1BH

-1.32

-1.25 F*1 795 21 H

5 66 MAN 1BH

-1.15

-1.06 F*1 796 21 H

7 66 SAD 1BH

-1.27 F*1 797 21 H

12 66 MAD 1BH

-1.33 F*1 798 21 H

14 66 SAD 1BH

-1.29 F*1 Unit IJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 22 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 799 21 H

15 66 MAD 1BH

-1.41 F*1 800 21 H

16 66 SAN 1BH

-2.03

-1.95 F*I 801 21 H

17 66 SAD 1BH

-1.4 F*1 802 21 H

18 66 SAD 1BH

-1.36 F*I 803 21 H

19 66 SAD 1BH

-0.82 F*I 804 21 H

21 66 SAD 1BH

-1.24 F*1 805 21 H

35 66 SAD 1BH

-1.35 F*I 806 21 H

1 67 MAD 1BH

-1.31 F*1 807 21 H

2 67 SAD 1BH

-1.42 F*I 808 21 H

3 67 MAD 1BH

-1.36 F*I 809 21 H

5 67 MAD 1BH

-1.35 F*I 810 21 H

6 67 SAD 1BH

-1.33 F*I 811 21 H

8 67 SAD 1BH

-0.86 F*I 812 21 H

11 67 SAD 1BH

-1.34 F*I 813 21 H

12 67 MAD 1BH

-1.36 F*I 814 21 H

16 67 SAN 1BH

-3.51

-3.43 F*I 815 21 H

19 67 SAD 1BH

-0.79 F*I 816 21 H

20 67 SAD 1BH

-0.92 F*I 817 21 H

21 67 MAD 1BH

-1.3 F*I 818 21 H

24 67 MAN IBH

-1.15

-1.01 F*I 819 21 H

25 67 SAN 1BH

-3.78

-3.66 F*I 820 21 H

34 67 MAD 1BH

-1.41 F*I 821 21 H

4 68 MAN 1BH

-1.35

-0.83 F*I 822 21 H

5 68 MAN IBH

-1.17

-1.05 F*I 823 21 H

7 68 MAN IBH

-1.18

-1.06 F*I 824 21 H

12 68 MAN IBH

-0.46

-0.22 F*I 825 21 H

13 68 MAD IBH

-1.39 F*I 826 21 H

14 68 MAD 1BH

-1.35 F*I 827 21 H

15 68 MAD 1BH

-1.44 F*I 828 21 H

19 68 SAD 1BH

-0.85 F*1 829 21 H

20 68 SAD 1BH

-0.85 F*1 830 21 H

34 68 MAN 1BH

-1.17

-0.97 F*1 831 21 H

4 69 MAD 1BH

-1.42 F*1 832 21 H

5 69 SAD 1BH

-1.35 F*1 833 21 H

8 69 SAD 1BH

-1.4 F*1 834 21 H

11 69 SAN IBH

-1.14

-1.05 F*I 835 21 H

12 69 MAD 1BH

-1.33 F*I 836 21 H

13 69 SAD 1BH

-1.39 F*I 837 21 H

14 69 SAD 1BH

-1.34 F*I 838 21 H

15 69 MAD IBH

-1.47 F*I 839 21 H

16 69 SAD 1BH

-1.35 F*I 840 21 H

17 69 SAD 1BH

-1.3 F*I 841 21 H

20 69 MAD 1BH

-1.41 F*I 842 21 H

25 69 SAD 1BH

-1.42 F*I 843 21 H

26 69 SAD 1BH

-1.41 F*I 844 21 H

33 69 SAD IBH

-1.48 F*1 845 21 H

35 69 SAD 1BH

-1.32 F*1 Unit 1 January 2001 Steam Generator 15 Day and C

Attachment I March 5, 2002 Page 23 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 846 21 H

2 70 SAD 1BH

-1.23 F*1 847 21 H

5 70 MAN 1BH

-1.17

-1.07 F*I 848 21 H

6 70 SAD 1BH

-1.41 F*I 849 21 H

7 70 SAD 1BH

-0.86 F*I 850 21 H

9 70 MAD 1BH

-1.2 F*I 851 21 H

11 70 MAD 1BH

-0.87 F*I 852 21 H

13 70 MAD 1BH

-1.4 F*I 853 21 H

16 70 MAD 1BH

-1.4 F*I 854 21 H

17 70 MAI 1BH

-0.52

-0.2 F*1 855 21 H

25 70 SAD 1BH

-1.49 F*1 856 21 H

2 71 MAD IBH

-0.92 F*1 857 21 H

3 71 MAN 1BH

-1.11

-1.03 F*I 858 21 H

4 71 MAD 1BH

-0.96 F*I 859 21 H

5 71 MAD 1BH

-1.41 F*I 860 21 H

7 71 MAN 1BH

-1.55

-1.49 F*I 861 21 H

8 71 MAD 1BH

-1.36 F*I 862 21 H

9 71 SAD IBH

-1.46 F*I 863 21 H

10 71 MAN 1BH

-1.15

-1.02 F*I 864 21 H

11 71 MAN 1BH

-1.17

-1.04 F*I 865 21 H

12 71 SAD 1BH

-1.28 F*I 866 21 H

16 71 SAD 1BH

-0.87 F*I 867 21 H

17 71 MAD 1BH

-1.34 F*I 868 21 H

21 71 MAD 1BH

-1.42 F*I 869 21 H

22 71 MAD 1BH

-0.86 F*I 870 21 H

31 71 SAD 1BH

-1.37 F*I 871 21 H

34 71 MAD 1BH

-1.33 F*I 872 21 H

2 72 MAD 1BH

-1.37 F*I 873 21 H

4 72 SAD 1BH

-1 F*1 874 21 H

5 72 SAD 1BH

-1.41 F*I 875 21 H

8 72 MAN 1BH

-1.09

-1.02 F*I 876 21 H

11 72 MAN 1BH

-1.16

-1.09 F*I 877 21 H

12 72 SAD 1BH

-1.46 F*1 878 21 H

16 72 SAD IBH

-1.42 F*1 879 21 H

17 72 SAD IBH

-1.39 F*1 880 21 H

18 72 MAD IBH

-1.48 F*1 881 21 H

36 72 MAD 1BH

-1.46 F*1 882 21 H

38 72 SAD 1BH

-1.31 F*1 883 21 H

2 73 SAD 1BH

-0.95 F*I 884 21 H

3 73 MAN 1BH

-1.29

-1.17 F*I 885 21 H

5 73 MAN 1BH

-1.14

-1.07 F*I 886 21 H

10 73 SAD IBH

-1.48 F*I 887 21 H

11 73 MAN 1BH

-1.17

-1.09 F*I 888 21 H

12 73 MAD 1BH

-0.89 F*I 889 21 H

16 73 MAD 1BH

-0.86 F*1 890 21 H

17 73 MAD 1BH

-0.88 F*I 891 21 H

18 73 MAN 1BH

-1.45

-1.34 F*I 892 21 H

23 73 SAD 1BH

-0.82 F*1 Unit 1 January 2001 Steam Generator 15 Day and C March 5, 2002 Page 24 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 893 21 H

1 74 SAD 1BH

-1.41 F*I 894 21 H

3 74 SAN 1BH

-1.21

-1.04 F*1 895 21 H

4 74 MAD 1BH

-1.43 F*1 896 21 H

5 74 MAN IBH

-1.21

-1.12 F*1 897 21 H

6 74 SAD 1BH

-1.32 F*1 898 21 H

7 74 MAD 1BH

-1.34 F*1 899 21 H

9 74 MAN 1BH

-1.14

-1.06 F*1 900 21 H

11 74 MAN 1BH

-1.29

-1.14 F*1 901 21 H

13 74 SAN 1BH

-1.38

-1.32 F*1 902 21 H

15 74 SAD 1BH

-1.37 F*I 903 21 H

19 74 SAN 1BH

-1.41

-1.37 F*I 904 21 H

25 74 SAD 1BH

-0.85 F*1 905 21 H

28 74 SAD 1BH

-0.94 F*I 906 21 H

29 74 SAD 1BH

-1.49 F*I 907 21 H

4 75 SAD 1BH

-1.34 F*I 908 21 H

5 75 MAN 1BH

-1.3

-1.23 F*I 909 21 H

8 75 MAD 1BH

-0.9 F*I 910 21 H

11 75 SAD 1BH

-1.36 F*I 911 21 H

17 75 MAD 1BH

-1.4 F*I 912 21 H

21 75 SAD 1BH

-1.47 F*I 913 21 H

22 75 SAD 1BH

-1.46 F*1 914 21 H

2 76 SAD 1BH

-1.38 F*I 915 21 H

3 76 SAD 1BH

-1.37 F*I 916 21 H

5 76 SAD 1BH

-1.31 F*I 917 21 H

7 76 MAD IBH

-1.41 F*1 918 21 H

9 76 MAD IBH

-1.39 F*I 919 21 H

10 76 MAD 1BH

-1.3 F*I 920 21 H

11 76 SAD IBH

-1.38 F*1 921 21 H

18 76 SAD IBH

-0.87 F*1 922 21 H

24 76 SAD 1BH

-1.33 F*1 923 21 H

3 77 MAD 1BH

-0.93 F*1 924 21 H

4 77 SAD IBH

-1.33 F*1 925 21 H

5 77 SAN 1BH

-1.77

-1.64 F*I 926 21 H

6 77 MAD 1BH

-1.4 F*I 927 21 H

7 77 SAN IBH

-1.17

-1.11 F*1 928 21 H

10 77 MAD IBH

-1.33 F*I 929 21 H

11 77 SAD 1BH

-1.44 F*1 930 21 H

16 77 SAD 1BH

-0.87 F*1 931 21 H

17 77 SAD 1BH

-1.36 F*I 932 21 H

22 77 SAD 1BH

-1.16 F*I 933 21 H

3 78 MAD 1BH

-1.53 F*1 934 21 H

4 78 MAD IBH

-1.08 F*I 935 21 H

5 78 MAD 1BH

-1.44 F*1 936 21 H

7 78 MAN 1BH

-1.28

-1.15 F*1 937 21 H

9 78 MAD 1BH

-1.39 F*1 938 21 H

11 78 MAN 1BH

-1.14

-1.05 F*I 939 21 H

2 79 MAN 1BH

-1.44

-1.38 F*I Unit 1January 2001 Steam Generator 15 Day and C March 5, 2002 Page 25 21 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 940 21 H

4 79 SAD 1BH

-1.37 F*I 941 21 H

5 79 MAD 1BH

-1.37 F*1 942 21 H

7 79 MAN 1BH

-1.28

-1.21 F*1 943 21 H

8 79 SAD 1BH

-0.93 F*I 944 21 H

10 79 SAN IBH

-1.39

-1.35 F*1 945 21 H

11 79 SAD 1BH

-1.47 F*1 946 21 H

17 79 MAD 1BH

-1.42 F*1 947 21 H

19 79 MAD 1BH

-1.52 F*1 948 21 H

21 79 SAN 1BH

-1.29

-1.22 F*1 949 21 H

3 80 SAD 1BH

-1.31 F*1 950 21 H

5 80 SAD 1BH

-1.56 F*1 951 21 H

9 80 SAD 1BH

-1.38 F*I 952 21 H

11 80 MAD 1BH

-1.37 F*I 953 21 H

12 80 SAD 1BH

-1.26 F*I 954 21 H

28 80 SAN 1BH

-1.3

-1.24 F*1 955 21 H

1 81 MAD 1BH

-0.9 F*1 956 21 H

11 81 SAD 1BH

-1.45 F*I 957 21 H

19 81 SAD 1BH

-1.32 F*I 958 21 H

21 81 SAD 1BH

-1.3 F*1 959 21 H

1 82 SAD 1BH

-1.4 F*I 960 21 H

7 82 SAD 1BH

-1.52 F*I 961 21 H

9 82 MAD 1BH

-0.88 F*I 962 21 H

11 82 SAD tBH

-1.36 F*I 963 21 H

12 82 SAD 1BH

-1.44 F*I 964 21 H

2 83 SAD 1BH

-0.94 F*I 965 21 H

4 83 SAN 1BH

-1.3

-1.27 F*I 966 21 H

9 83 MAD 1BH

-1.52 F*I 967 21 H

4 84 SAN 1BH

-1.43

-1.37 F*1 968 21 H

5 84 MAD 1BH

-1 F*1 969 21 H

9 84 SAN 1BH

-1.48

-1.42 F*I 970 21 H

11 84 MAD IBH

-1.45 F*1 971 21 H

12 84 MAD IBH

-0.9 F*1 972 21 H

7 85 SAN 1BH

-1.49

-1.4 F*1 973 21 H

9 85 MAN 1BH

-1.35

-1.27 F*I 974 21 H

13 85 MAN 1BH

-1.39

-1.33 F*1 975 21 H

18 86 SAN 1BH

-1.12

-1.06 F*1 976 21 H

3 87 SAN 1BH

-1.34

-1.31 F*I Unit 1January 2001Steam Generator 15 Day and C March 5, 2002 Page 26 21 STEAM GENERATOR F*2 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 1

21 H

4 11 SAN 2BH

-1.12

-1.01 F*2 2

21 H

4 17 SAD 2BH

-3.11 F*2 3

21 H

14 17 SAN 2BH

-1.14

-1.08 F*2 4

21 H

2 21 SAN 2BH

-1.18

-1.09 F*2 5

21 H

9 21 SAN 2BH

-1.05

-0.77 F*2 6

21 H

3 22 SAN 2BH

-0.55

-0.48 F*2 7

21 H

3 24 SAN 2BH

-1.06

-0.95 F*2 8

21 H

19 25 MAD 2BH

-3.03 F*2 9

21 H

12 27 MAN 2BH

-0.73

-0.64 F*2 10 21 H

28 27 SAN 2BH

-1.28

-0.88 F*2 11 21 H

30 27 SAN 2BH

-0.71

-0.59 F*2 12 21 H

9 28 MAN 2BH

-2.29

-1.97 F*2 13 21 H

13 29 SAN 2BH

-3.3

-3.24 F*2 14 21 H

9 30 SAN 2BH

-0.83

-0.53 F*2 15 21 H

18 30 SAN 2BH

-1.33

-1.22 F*2 16 21 H

23 34 SAN 2BH

-0.95

-0.81 F*2 17 21 H

5 36 MAN 2BH

-2.49

-1.86 F*2 18 21 H

14 36 MAD 2BH

-3 F*2 19 21 H

4 38 SAN 2BH

-1

-0.93 F*2 20 21 H

14 40 MAN 2BH

-2.88

-1.35 F*2 21 21 H

2 42 SAN 2BH

-1.12

-1.08 F*2 22 21 H

10 44 SAD 2BH

-2.9 F*2 23 21 H

30 45 SAN 2BH

-1.05

-0.99 F*2 24 21 H

9 46 SAN 2BH

-2.23

-1.46 F*2 25 21 H

12 46 MAN 2BH

-2.67

-1.83 F*2 26 21 H

20 46 SAD 2BH

-1.5 F*2 27 21 H

6 47 SAN 2BH

-2.88

-1.89 F*2 28 21 H

7 47 SAN 2BH

-0.72

-0.55 F*2 29 21 H

14 47 SAN 2BH

-2.86

-1.48 F*2 30 21 H

18 47 MAD 2BH

-3.12 F*2 31 21 H

10 48 MAN 2BH

-2.81

-2.74 F*2 32 21 H

8 49 MAN 2BH

-2.57

-1.64 F*2 33 21 H

15 49 MAD 2BH

-3.35 F*2 34 21 H

14 50 SAN 2BH

-2.17

-1.8 F*2 35 21 H

17 50 SAN 2BH

-3.58

-3.52 F*2 36 21 H

12 52 SAD 2BH

-1.81 F*2 37 21 H

4 55 SAN 2BH

-0.67

-0.54 F*2 38 21 H

11 55 MAN 2BH

-0.68

-0.58 F*2 39 21 H

7 56 SAN 2BH

-0.59

-0.52 F*2 40 21 H

11 56 SAN 2BH

-0.75

-0.64 F*2 41 21 H

1 57 SAN 2BH

-1.12

-0.93 F*2 42 21 H

11 57 SAN 2BH

-1.18

-1.09 F*2 43 2i H

2 60 MAN 2BH

-0.68

-0.36 F*2 44 21 H

4 60 SAN 2BH

-0.61

-0.5 F*2 45 21 H

6 60 SAD 2BH

-1.11 F*2 46 21 H

4 62 SAN 2BH

-0.86

-0.71 F*2 Unit 1January 2001Steam Generator 15 Day and C March 5, 2002 Page 27 21 STEAM GENERATOR F*2 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 47 21 H

10 62 SAN 2BH

-1.02

-0.93 F*2 48 21 H

25 62 SAN 2BH

-1.2

-1.08 F*2 49 21 H

8 63 MAN 2BH

-1.1

-0.88 F*2 50 21 H

8 64 SAN 2BH

-0.62

-0.5 F*2 51 21 H

17 64 MAN 2BH

-1.14

-1.03 F*2 52 21 H

10 66 SAN 2BH

-0.75

-0.63 F*2 53 21 H

14 67 SAD 2BH

-3.02 F*2 Unit lJanuary 2001 Steam Generator 15 Day and C March 5, 2002 Page 28 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 1

21 H

3 17 SAD EBH

-13.35 EF*

2 21 H

9 18 SAD EBH

-13.43 EF*

3 21 H

13 30 SAD EBH

-13.71 EF*

4 21 H

16 56 SAN EBH

-9.3

-9.27 EF*

5 21 H

7 61 SAN EBH

-9.16

-9.05 EF*

6 21 H

7 67 SAN EBH

-9.3

-9.08 EF*

Unit 1January 2001 Steam Generator 15 Day and C 21 STEAM GENERATOR EF* TUBES, BOC21, 2002 March 5, 2002 Page 29 22 STEAM GENERATOR F*0 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 1

22 H

4 1

SAN TRH

-2.20

-2.13 F*0 2

22 H

1 2

SAI TRH

-1.93

-1.87 F*0 3

22 H

1 7

SAN TRH

-2.48

-2.23 F*0 4

22 H

3 10 SAI TRH

-2.37

-2.29 F*0 5

22 H

35 20 SAN TRH

-2.20

-2.12 F*0 6

22 H

35 23 SAI TRH

-2.13

-2.04 F*0 7

22 H

37 25 SAI TRH

-2.19

-2.09 F*0 8

22 H

1 27 SAN TRH

-2.54

-2.43 F*0 9

22 H

8 27 SAI TRH

-2.57

-2.38 F*0 10 22 H

1 28 SAI TRH

-2.43

-2.38 F*0 11 22 H

3 28 SAI TRH

-2.37

-2.23 F*0 12 22 H

2 29 SAN TRH

-2.35

-2.25 F*0 13 22 H

3 29 SAI TRH

-2.32

-2.21 F*0 14 22 H

2 30 SAI TRH

-2.51

-2.48 F*0 15 22 H

1 33 MAN TRH

-2.28

-2.15 F*0 16 22 H

1 34 SAN TRH

-2.34

-2.17 F*0 17 22 H

42 35 SAN TRH

-2.40

-2.30 F*0 18 22 H

1 37 MAN TRH

-2.35

-2.21 F*0 19 22 H

2 39 SCI TRH

-2.21

-2.14 F*0 20 22 H

2 45 SAN TRH

-2.15

-2.11 F*0 21 22 H

1 46 SAI TRH

-2.53

-2.43 F*0 22 22 H

7 48 SAI TRH

-2.50

-2.40 F*0 23 22 H

9 48 SAN TRH

-2.30

-2.06 F*0 24 22 H

10 48 SAN TRH

-2.47

-2.35 F*0 25 22 H

5 49 SAN TRH

-2.84

-2.69 F*0 26 22 H

7 49 SAN TRH

-2.47

-2.32 F*0 27 22 H

3 50 SAI TRH

-2.67

-2.58 F*0 28 22 H

4 50 SAI TRH

-2.75

-2.66 F*0 29 22 H

6 50 SAI TRH

-2.75

-2.66 F*0 30 22 H

7 50 SAN TRH

-2.55

-2.40 F*0 31 22 H

10 50 SAN TRH

-2.83

-2.74 F*0 32 22 H

1 51 MAN TRH

-2.75

-2.52 F*0 33 22 H

3 51 SAN TRH

-2.75

-2.61 F*0 34 22 H

4 51 MAN TRH

-2.78

-2.69 F*0 35 22 H

7 51 SAN TRH

-2.59

-2.47 F*0 36 22 H

1 52 MAN TRH

-2.94

-2.70 F*0 37 22 H

10 52 SAN TRH

-2.81

-2.71 F*0 38 22 H

1 53 MAN TRH

-2.88

-2.76 F*0 39 22 H

6 53 SAI TRH

-2.70

-2.64 F*0 40 22 H

7 53 SAN TRH

-2.67

-2.59 F*0 41 22 H

34 53 MAI TRH

-2.16

-2.12 F*0 42 22 H

37 53 MAN TRH

-2.39

-2.21 F*0 43 22 H

5 54 MAN TRH

-2.62

-2.56 F*0 44 22 H

34 55 MAN TRH

-2.17

-2.06 F*0 45 22 H

1 56 MAN TRH

-2.75

-2.63 F*0 46 22 H

2 56 SAN TRH

-2.63

-2.54 F*0 Unit 1January 2001Steam Generator 15 Day and C March 5, 2002 Page 30 22 STFAM flENERATOR F*O TUBES. BOC21. 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 47 22 H

34 56 MAN TRH

-2.25

-2.11 F*0 48 22 H

3 57 SAI TRH

-2.68

-2.60 F*0 49 22 H

37 57 MAN TRH

-2.25

-2.07 F*0 50 22 H

9 58 SAI TRH

-2.71

-2.60 F*0 51 22 H

34 58 MAN TRH

-2.15

-2.03 F*0 52 22 H

7 59 SAI TRH

-2.69

-2.64 F*0 53 22 H

26 59 MAN TRH

-2.13

-1.98 F*0 54 22 H

37 59 MAI TRH

-2.21

-2.12 F*0 55 22 H

34 60 MAN TRH

-2.30

-2.20 F*0 56 22 H

11 61 SAN TRH

-2.74

-2.66 F*0 57 22 H

1 62 MAN TRH

-2.74

-2.49 F*0 58 22 H

7 63 SAI TRH

-2.68

-2.62 F*0 59 22 H

8 63 SAI TRH

-2.66

-2.58 F*0 60 22 H

17 63 MAI TRH

-2.14

-2.06 F*0 61 22 H

34 63 MAN TRH

-2.13

-1.98 F*0 62 22 H

5 64 SAN TRH

-2.31

-2.27 F*O 63 22 H

8 64 SAI TRH

-2.39

-2.33 F*O 64 22 H

7 65 MAN TRH

-2.54

-2.31 F*0 65 22 H

8 66 SAN TRH

-2.37

-2.27 F*0 66 22 H

18 66 SAI TRH

-1.42

-1.32 F*0 67 22 H

8 67 SAI TRH

-2.28

-2.23 F*0 68 22 H

8 68 SAN TRH

-2.36

-2.25 F*0 69 22 H

34 68 MAN TRH

-2.32

-2.10 F*0 70 22 H

1 69 MAN TRH

-2.71

-2.59 F*0 71 22 H

1 70 MAN TRH

-2.71

-2.56 F*0 72 22 H

37 70 MAN TRH

-2.20

-2.07 F*0 73 22 H

6 71 SAI TRH

-2.19

-2.14 F*0 74 22 H

7 71 SAI TRH

-2.39

-2.32 F*0 75 22 H

11 71 SAN TRH

-2.40

-2.30 F*0 76 22 H

24 71 MAN TRH

-2.18

-2.03 F*0 77 22 H

1 72 MAN TRH

-2.73

-2.41 F*0 78 22 H

5 72 SAN TRH

-2.51

-2.44 F*0 79 22 H

34 72 SAI TRH

-2.13

-2.10 F*0 80 22 H

37 72 SAN TRH

-2.20

-2.01 F*0 81 22 H

1 74 MAN TRH

-2.72

-2.65 F*0 82 22 H

4 74 MAI TRH

-2.25

-2.19 F*0 83 22 H

5 74 SAN TRH

-2.42

-2.32 F*0 84 22 H

6 74 MAN TRH

-2.20

-2.11 F*0 85 22 H

4 75 SAN TRH

-2.33

-2.24 F*0 86 22 H

6 75 SAI TRH

-2.16

-2.07 F*0 87 22 H

1 76 MAN TRH

-2.80

-2.61 F*0 88 22 H

1 77 MAN TRH

-2.78

-2.65 F*0 89 22 H

4 77 SAN TRH

-2.40

-2.31 F*0 90 22 H

6 77 MAI TRH

-2.19

-2.13 F*0 91 22 H

1 78 MAN TRH

-2.80

-2.46 F*0 92 22 H

4 78 SAN TRH

-2.22

-2.14 F*0 93 22 H

1 79 MAN TRH

-2.59

-2.43 F*0 Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 31 22 STEAM GENERATOR F*0 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 94 22 H

3 79 SAN TRH

-2.62

-2.43 F*O 95 22 H

1 80 MAN TRH

-2.61

-2.29 F*0 96 22 H

4 80 SAN TRH

-2.28

-2.22 F*0 97 22 H

5 80 SAN TRH

-2.52

-2.39 F*0 98 22 H

4 81 SAI TRH

-2.18

-2.12 F*0 99 22 H

1 82 MAN TRH

-2.66

-2.45 F*0 100 22 H

5 82 SAN TRH

-2.55

-2.38 F*0 101 22 H

1 83 SAN TRH

-2.62

-2.38 F*0 102 22 H

6 85 SAN TRH

-2.34

-2.16 F*0 103 22 H

7 85 SAI TRH

-2.30

-2.19 F*0 104 22 H

6 86 SAI TRH

-2.17

-2.13 F*0 105 22 H

1 87 SAN TRH

-2.67

-2.45 F*0 106 22 H

4 88 SAN TRH

-2.37

-2.30 F*0 107 22 H

6 91 SAN TRH

-2.52

-2.49 F*0 108 22 H

6 94 MAN TRH

-2.41

-2.24 F*0 Unit 1January 2001Steam Generator 15 Day and C March 5, 2002 Page 32 22 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 1

22 H

15 7

SAD 1BH

-1.05 F*1 2

22 H

1 10 SAN 1BH

-2.4

-2.29 F*1 3

22 H

24 13 SAN 1BH

-1.58

-1.38 F*1 4

22 H

4 14 SAN 1BH

-2.41

-2.33 F*1 5

22 H

17 14 MAD 1BH

-1.32 F*1 6

22 H

18 14 SAN 1BH

-1.47

-1.43 F*1 7

22 H

25 14 SAN 1BH

-1.65

-1.57 F*1 8

22 H

2 15 SAN 1BH

-2.32

-2.22 F*I 9

22 H

4 15 SAD 1BH

-1.25 F*I 10 22 H

9 15 SAD 1BH

-1.16 F*1 11 22 H

14 15 SAD 1BH

-1.06 F*1 12 22 H

24 15 MAN 1BH

-1.55

-1.27 F*I 13 22 H

25 15 SAD 1BH

-1.49 F*1 14 22 H

13 16 SAD 1BH

-1.32 F*1 15 22 H

18 16 SAD 1BH

-1.34 F*1 16 22 H

25 16 SAD 1BH

-1.07 F*I 17 22 H

1 17 MAN 1BH

-2.22

-2.01 F*1 18 22 H

4 17 MAD 1BH

-1.3 F*I 19 22 H

14 17 SAN 1BH

-1.32

-1.25 F*I 20 22 H

25 17 SAD 1BH

-1.4 F*1 21 22 H

1 18 MAN IBH

-2.16

-2.05 F*I 22 22 H

2 18 MAN 1BH

-2.19

-2.1 F*I 23 22 H

4 18 MAD 1BH

-1.19 F*I 24 22 H

14 18 MAD 1BH

-1.37 F*I 25 22 H

4 19 SAN 1BH

-2.18

-2.09 F*I 26 22 H

15 19 MAD IBH

-1.08 F*I 27 22 H

21 19 SVI 1BH

-2.5

-2.29 F*I 28 22 H

1 20 MAN 1BH

-2.21

-2.05 F*I 29 22 H

3 20 SAN 1BH

-2.3

-2.22 F*I 30 22 H

12 20 SAN 1BH

-1.44

-1.37 F*1 31 22 H

14 20 SAD 1BH

-0.91 F*1 32 22 H

18 20 SAN 1BH

-1.63

-1.55 F*1 33 22 H

20 20 MAD IBH

-1.4 F*1 34 22 H

24 20 SAD 1BH

-1.32 F*1 35 22 H

29 20 SAN 1BH

-1.57

-1.47 F*1 36 22 H

1 21 MAN 1BH

-2.2

-2.07 F*I 37 22 H

4 21 MAN 1BH

-2.4

-2.3 F*1 38 22 H

10 21 SAN 1BH

-1.34

-1.24 F*1 39 22 H

31 21 SAD 1BH

-1.4 F*I 40 22 H

18 22 SAN 1BH

-1.37

-1.28 F*1 41 22 H

23 22 SAD IBH

-1.31 F*I 42 22 H

25 22 MAD 1BH

-1.3 F*I 43 22 H

28 22 SAD IBH

-1.47 F*I 44 22 H

32 22 SAD 1BH

-1.22 F*I 45 22 H

33 22 SAD 1BH

-1.28 F*I 46 22 H

22 23 SAN 1BH

-1.55

-1.4 F*1 Unit 1January 200lSteam Generator 15 Day and C March 5, 2002 Page 33 22 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 47 22 H

32 23 SAD 1BH

-1.24 F*I 48 22 H

1 24 SAN 1BH

-1.42

-1.36 F*I 49 22 H

15 24 MAD 1BH

-0.9 F*I 50 22 H

21 24 MAD 1BH

-1.31 F*I 51 22 H

25 24 MAD IBH

-1.37 F*I 52 22 H

27 24 MAD 1BH

-1.57 F*1 53 22 H

28 24 SAN 1BH

-1.38

-1.22 F*l 54 22 H

34 24 SAD lBH

-1.02 F*I 55 22 H

35 24 SAN 1BH

-1.35

-1.31 F*I 56 22 H

16 25 SAD 1BH

-1.27 F*1 57 22 H

19 25 SAD 1BH

-1.24 F*1 58 22 H

20 25 MAD 1BH

-0.96 F*1 59 22 H

21 25 SAD 1BH

-1.51 F*I 60 22 H

23 25 MAN 1BH

-1.53

-1.37 F*1 61 22 H

26 25 SAN 1BH

-1.12

-1.06 F*1 62 22 H

28 25 SAD 1BH

-1.27 F*1 63 22 H

31 25 SAD 1BH

-1 F*1 64 22 H

32 25 SAD 1BH

-1.4 F*1 65 22 H

33 25 SAD 1BH

-1 F*1 66 22 H

35 25 SAD 1BH

-1.56 F*1 67 22 H

1 26 SAN IBH

-0.53

-0.34 F*1 68 22 H

18 26 SAD 1BH

-1.27 F*I 69 22 H

19 26 MAD 1BH

-1.67 F*I 70 22 H

21 26 SAD 1BH

-1.36 F*I 71 22 H

22 26 SAD 1BH

-1.56 F*I 72 22 H

24 26 MAN 1BH

-1.45

-1.39 F*I 73 22 H

25 26 SAD 1BH

-1.31 F*1 74 22 H

27 26 SAN 1BH

-1.52

-1.48 F*1 75 22 H

28 26 SAN tBH

-0.98

-0.91 F*I 76 22 H

33 26 SAD 1BH

-1.33 F*I 77 22 H

13 27 MAD IBH

-1.29 F*I 78 22 H

14 27 SAD IBH

-0.95 F*t 79 22 H

15 27 SAD 1BH

-1.59 F*I 80 22 H

20 27 SAD 1BH

-1.52 F*I 81 22 H

24 27 SAD 1BH

-1.35 F*I 82 22 H

25 27 SAD 1BH

-1.22 F*I 83 22 H

28 27 MAD 1BH

-1.24 F*1 84 22 H

31 27 MAD IBH

-1.29 F*I 85 22 H

7 28 MAN 1BH

-1.51

-1.4 F*I 86 22 H

20 28 SAD 1BH

-1.21 F*1 87 22 H

23 28 SAD IBH

-1.34 F*1 88 22 H

31 28 SAD 1BH

-1.34 F*1 89 22 H

1 29 MAD 1BH

-1.35 F*I 90 22 H

7 29 SAD 1BH

-1.18 F*I 91 22 H

19 29 SAD 1BH

-1.72 F*I 92 22 H

24 29 SAD 1BH

-1.57 F*I 93 22 H

26 29 MAN 1BH

-1.46

-1.4 F*1 Unit 1 January 2001 Steam Generator 15 Day and C March 5, 2002 Page 34 22 STEAM GENERATOR F*I TUBES. BOC21. 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 94 22 H

27 29 MAD IBH

-1.23 F*I 95 22 H

29 29 MAN 1BH

-0.78

-0.02 F*I 96 22 H

32 29 SAD IBH

-1.52 F*I 97 22 H

5 30 SAN 1BH

-0.35

-0.17 F*I 98 22 H

9 30 SAD 1BH

-1.61 F*I 99 22 H

21 30 SAD 1BH

-1.29 F*I 100 22 H

32 30 MAD IBH

-1.4 F*I 101 22 H

35 30 SAD 1BH

-1.4 F*I 102 22 H

3 31 MAN 1BH

-1.56

-1.17 F*I 103 22 H

27 31 SAD 1BH

-1.25 F*1 104 22 H

28 31 SAN 1BH

-1.49

-1.46 F*I 105 22 H

32 31 SAD 1BH

-1.4 F*I 106 22 H

33 31 SAD 1BH

-1.32 F*I 107 22 H

35 31 SAN 1BH

-1.55

-1.52 F*I 108 22 H

1 32 MAN 1BH

-1.38

-1.31 F*I 109 22 H

9 32 MAD 1BH

-1.18 F*I 110 22 H

20 32 MAN 1BH

-1.35

-1.22 F*I 111 22 H

21 32 SAD 1BH

-1.36 F*I 112 22 H

28 32 SAD 1BH

-1.17 F*I 113 22 H

31 32 SAN IBH

-1.48

-1.28 F*I 114 22 H

32 32 SAD IBH

-1.44 F*I 115 22 H

33 32 MAD 1BH

-1.46 F*I 116 22 H

18 33 SAD IBH

-1.41 F*I 117 22 H

23 33 SAN IBH

-1.57

-1.51 F*I 118 22 H

25 33 SAD 1BH

-0.9 F*I 119 22 H

32 33 MAD 1BH

-1.49 F*I 120 22 H

33 33 SAD 1BH

-1 F*1 121 22 H

7 34 SAN 1BH

-1.25

-1.19 F*I 122 22 H

22 34 MAN 1BH

-1.47

-1.37 F*I 123 22 H

28 34 MAN 1BH

-1.52

-1.42 F*I 124 22 H

30 34 MAN IBH

-1.62

-1.59 F*I 125 22 H

33 34 SAD 1BH

-0.97 F*I 126 22 H

12 35 MAD 1BH

-1.21 F*I 127 22 H

13 35 MAN 1BH

-1.49

-1.26 F*I 128 22 H

22 35 SAD 1BH

-0.9 F*I 129 22 H

28 35 MAN 1BH

-1.63

-1.45 F*I 130 22 H

29 35 SAD 1BH

-1.27 F*I 131 22 H

1 36 SAD 1BH

-1.3 F*I 132 22 H

7 36 SAD 1BH

-1.35 F*1 133 22 H

20 36 MAD 1BH

-1.47 F*I 134 22 H

23 36 MAN 1BH

-1.47

-1.24 F*I 135 22 H

27 36 SAD 1BH

-1.48 F*1 136 22 H

29 36 SAD 1BH

-1.22 F*I 137 22 H

32 36 SAN 1BH

-0.99

-0.81 F*1 138 22 H

33 36 SAD 1BH

-1.23 F*1 139 22 H

35 36 SAN 1BH

-1.51

-1.48 F*I 140 22 H

2 37 SAD IBH

-1.25 F*I Unit 1January 2001 Steam Generator 15 Day and C March 5, 2002 Page 35 22 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 141 22 H

20 37 SAD 1BH

-1.48 F*l 142 22 H

23 37 SAD 1BH

-1.51 F*I 143 22 H

24 37 SAN IBH

-1.55

-1.48 F*I 144 22 H

30 37 SAD 1BH

-1.29 F*I 145 22 H

33 37 MAI 1BH

-0.51

-0.03 F*I 146 22 H

37 37 SAD 1BH

-1.4 F*1 147 22 H

19 38 MAN 1BH

-1.37

-1.21 F*1 148 22 H

33 38 MAN 1BH

-1.53

-1.45 F*I 149 22 H

37 38 SAD 1BH

-1.37 F*I 150 22 H

1 39 MAN tBH

-1.55

-1.52 F*1 151 22 H

23 39 SAN 1BH

-1.5

-1.47 F*I 152 22 H

33 39 SAD IBH

-1.31 F*1 153 22 H

'37 39 SAD 1BH

-1.33 F*1 154 22 H

1 40 MAD 1BH

-1.34 F*1 155 22 H

12 40 SAD 1BH

-1.03 F*1 156 22 H

20 40 SAD 1BH

-1.41 F*1 157 22 H

21 40 SAD 1BH

-1.36 F*I 158 22 H

22 40 MAD 1BH

-0.95 F*I 159 22 H

23 40 SAD 1BH

-1 F*1 160 22 H

32 40 SAN IBH

-1.52

-1.49 F*1 161 22 H

33 40 SAD 1BH

-1 F*I 162 22 H

1 41 MAD 1BH

-1.63 F*1 163 22 H

5 41 SAD 1BH

-1.16 F*1 164 22 H

19 41 SAD 1BH

-1.54 F*I 165 22 H

21 41 SAD 1BH

-1.58 F*I 166 22 H

22 41 SAD 1BH

-1.47 F*I 167 22 H

27 41 MAN 1BH

-1.53

-1.4 F*I 168 22 H

28 41 SAD 1BH

-0.92 F*I 169 22 H

29 41 SAD IBH

-1.28 F*1 170 22 H

33 41 MAD 1BH

-1.41 F*I 171 22 H

37 41 MAD 1BH

-1.45 F*I 172 22 H

1 42 SAD 1BH

-1.35 F*I 173 22 H

2 42 SAD IBH

-1.32 F*1 174 22 H

13 42 SAD 1BH

-1.28 F*I 175 22 H

21 42 MAD 1BH

-0.95 F*I 176 22 H

22 42 SAD IBH

-1.49 F*1 177 22 H

24 42 SAD 1BH

-1.71 F*I 178 22 H

29 42 SAD IBH

-1.5 F*1 179 22 H

33 42 MAN IBH

-1.49

-1.38 F*1 180 22 H

1 43 SAD IBH

-1.63 F*1 181 22 H

3 43 SAD 1BH

-1.22 F*I 182 22 H

12 43 MAD IBH

-1.17 F*1 183 22 H

13 43 SAD IBH

-1.18 F*1 184 22 H

22 43 MAD 1BH

-1.44 F*1 185 22 H

33 43 MAN 1BH

-1.4

-1.27 F*1 186 22 H

37 43 SAN 1BH

-0.42

-0.26 F*1 187 22 H

13 44 MAN 1BH

-1.3

-1.17 F*1 Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 36 22 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 188 22 H

14 44 SAD 1BH

-1.58 F*I 189 22 H

17 44 SAN IBH

-1.2

-1.13 F*1 190 22 H

18 44 SAD IBH

-0.93 F*I 191 22 H

23 44 MAN IBH

-1.52

-1.42 F*1 192 22 H

27 44 SAD IBH

-1.55 F*1 193 22 H

30 44 SAD 1BH

-1.5 F*I 194 22 H

33 44 SAD 1BH

-1.36 F*I 195 22 H

1 45 MAD IBH

-0.75 F*1 196 22 H

6 45 SAD 1BH

-1.34 F*1 197 22 H

13 45 SAN 1BH

-1.36

-1.2 F*1 198 22 H

15 45 MAD 1BH

-1.52 F*1 199 22 H

19 45 MAD 1BH

-0.9 F*1 200 22 H

28 45 MAD 1BH

-1.57 F*l 201 22 H

10 46 SAD 1BH

-1.18 F*1 202 22 H

12 46 SAD 1BH

-1.38 F*1 203 22 H

14 46 SAD 1BH

-1.2 F*1 204 22 H

16 46 MAN 1BH

-1.35

-1.29 F*I 205 22 H

17 46 SAN 1BH

-1.02

-0.87 F*1 206 22 H

19 46 SAD IBH

-1.47 F*1 207 22 H

26 46 MAN 1BH

-1.49

-1.29 F*I 208 22 H

6 47 SAD 1BH

-1.29 F*I 209 22 H

12 47 SAD 1BH

-1.43 F*1 210 22 H

20 47 SAD 1BH

-0.93 F*I 211 22 H

28 47 SAD 1BH

-0.99 F*I 212 22 H

2 48 MAN 1BH

-1.14

-1.04 F*I 213 22 H

3 48 MAD 1BH

-1.17 F*I 214 22 H

21 48 SAD IBH

-1 F*I 215 22 H

22 48 SAD 1BH

-1.52 F*I 216 22 H

23 48 MAN IBH

-1.47

-1.19 F*I 217 22 H

28 48 MAN IBH

-1.58

-1.23 F*I 218 22 H

29 48 SAD IBH

-1.59 F*1 219 22 H

37 48 SAD IBH

-1.43 F*I 220 22 H

1 49 SAN 1BH

-0.87

-0.81 F*I 221 22 H

4 49 SAD 1BH

-1.28 F*I 222 22 H

9 49 SAN 1BH

-1.32

-1.29 F*1 223 22 H

10 49 SAD 1BH

-1.35 F*1 224 22 H

11 49 MAD 1BH

-1.36 F*I 225 22 H

12 49 SAN 1BH

-0.19

-0.01 F*I 226 22 H

13 49 SAD 1BH

-1.53 F*1 227 22 H

14 49 MAN 1BH

-1.27

-0.88 F*I 228 22 H

18 49 MAN 1BH

-1.38

-1.05 F*I 229 22 H

21 49 SAD IBH

-0.86 F*I 230 22 H

23 49 MAN 1BH

-1.52

-1.17 F*I 231 22 H

28 49 SAN 1BH

-1.48

-1.35 F*I 232 22 H

32 49 MAN 1BH

-1.65

-1.26 F*I 233 22 H

41 49 SAN 1BH

-1.29

-1.18 F*I 234 22 H

1 50 SAD 1BH

-1.44 F*1 Unit IJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 37 22 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 235 22 H

9 50 MAN 1BH

-1.01

-0.99 F*I 236 22 H

11 50 SAD IBH

-1.18 F*I 237 22 H

15 50 SAD IBH

-1.2 F*I 238 22 H

18 50 MAD 1BH

-0.94 F*1 239 22 H

22 50 SAD IBH

-0.99 F*1 240 22 H

23 50 MAD IBH

-0.97 F*1 241 22 H

24 50 MAN 1BH

-1.52

-1.29 F*I 242 22 H

25 50 SAN IBH

-2.35

-2.28 F*I 243 22 H

27 50 MAD IBH

-1.51 F*I 244 22 H

28 50 SAN IBH

-1.45

-1.38 F*I 245 22 H

29 50 SAD IBH

-1.6 F*I 246 22 H

30 50 SAD IBH

-1.22 F*I 247 22 H

32 50 MAN IBH

-1.53

-1.19 F*I 248 22 H

33 50 SAN 1BH

-1.5

-1.34 F*I 249 22 H

34 50 SAD IBH

-1.55 F*I 250 22 H

35 50 SAD 1BH

-1.56 F*1 251 22 H

9 51 MAN 1BH

-1.27

-1.22 F*I 252 22 H

10 51 SAD 1BH

-1.19 F*1 253 22 H

12 51 SAD 1BH

-1.17 F*I 254 22 H

13 51 MAN 1BH

-1.29

-1.21 F*I 255 22 H

18 51 MAD 1BH

-1.37 F*I 256 22 H

21 51 SAD IBH

-1.33 F*1 257 22 H

28 51 SAD 1BH

-1.47 F*I 258 22 H

32 51 SAN 1BH

-1.4

-1.3 F*I 259 22 H

37 51 SAN 1BH

-1.59

-1.55 F*I 260 22 H

3 52 SAD 1BH

-1.35 F*I 261 22 H

7 52 SAD 1BH

-1.03 F*I 262 22 H

9 52 SAD 1BH

-1.15 F*I 263 22 H

28 52 SAN IBH

-1.57

-1.34 F*I 264 22 H

29 52 SAN 1BH

-1.54

-1.47 F*I 265 22 H

33 52 SAN IBH

-1.54

-1.41 F*1 266 22 H

13 53 MAN IBH

-1.3

-0.73 F*I 267 22 H

18 53 SAD IBH

-1.33 F*I 268 22 H

24 53 SAD 1BH

-1.46 F*I 269 22 H

25 53 SAN IBH

-1.42

-1.36 F*I 270 22 H

29 53 MAN IBH

-1.53

-1.46 F*I 271 22 H

30 53 SAN IBH

-1.65

-1.58 F*I 272 22 H

32 53 SAD 1BH

-1.35 F*I 273 22 H

33 53 SAD 1BH

-1.34 F*I 274 22 H

40 53 SAN 1BH

-1.41

-1.3 F*I 275 22 H

1 54 MAN 1BH

-1.17

-0.9 F*1 276 22 H

15 54 SAD 1BH

-1.07 F*1 277 22 H

16 54 MAN IBH

-0.65

-0.13 F*1 278 22 H

18 54 MAD 1BH

-1.41 F*I 279 22 H

23 54 SAN 1BH

-1.38

-1.29 F*1 280 22 H

24 54 SAD 1BH

-1.46 F*1 281 22 H

25 54 SAD 1BH

-1.33 F*I Unit lJanuary 2001Steam Generator 15 Day and C March 5, 2002 Page 38 22 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 282 22 H

27 54 SAD 1BH

-1.45 F*I 283 22 H

28 54 SAN 1BH

-1.44

-1.37 F*I 284 22 H

34 54 SAD IBH

-0.93 F*I 285 22 H

10 55 MAN IBH

-1.22

-1.02 F*I 286 22 H

13 55 MAN 1BH

-1.16

-0.73 F*I 287 22 H

19 55 MAD 1BH

-1.25 F*1 288 22 H

20 55 SAD 1BH

-1.23 F*I 289 22 H

21 55 MAD 1BH

-1.41 F*1 290 22 H

22 55 SAN 1BH

-1.39

-1.3 F*1 291 22 H

23 55 SAN 1BH

-1.38

-1.32 F*1 292 22 H

24 55 SAN 1BH

-1.58

-1.52 F*I 293 22 H

28 55 SVI 1BH

-1.38

-1.24 F*1 294 22 H

29 55 SAD IBH

-1.39 F*1 295 22 H

32 55 SAD 1BH

-1.3 F*1 296 22 H

33 55 SAN 1BH

-1.55

-1.3 F*1 297 22 H

37 55 MAN 1BH

-1.49

-1.44 F*I 298 22 H

4 56 MAN 1BH

-1.34

-0.91 F*I 299 22 H

6 56 SAD 1BH

-1.26 F*I 300 22 H

7 56 SAD 1BH

-1.36 F*I 301 22 H

10 56 MAD IBH

-1.2 F*1 302 22 H

11 56 MAD 1BH

-1.19 F*I 303 22 H

12 56 MAD 1BH

-1.24 F*1 304 22 H

13 56 SAD IBH

-1.41 F*I 305 22 H

16 56 SAD 1BH

-1.25 F*1 306 22 H

27 56 SAD 1BH

-1.6 F*I 307 22 H

28 56 SAD IBH

-1.55 F*I 308 22 H

29 56 SAD 1BH

-1.5 F*I 309 22 H

5 57 SAN 1BH

-1.43

-1.34 F*I 310 22 H

7 57 SAN 1BH

-1.23

-1.13 F*1 311 22 H

10 57 SAD IBH

-1.24 F*1 312 22 H

13 57 MAD IBH

-1.31 F*1 313 22 H

15 57 SAD 1BH

-1.06 F*I 314 22 H

18 57 MAD 1BH

-0.92 F*1 315 22 H

21 57 MAN 1BH

-1.15

-1.03 F*I 316 22 H

23 57 SAN 1BH

-1.56

-1.43 F*I 317 22 H

25 57 SAD 1BH

-1.44 F*I 318 22 H

27 57 SAD IBH

-1.37 F*I 319 22 H

28 57 MAD 1BH

-1.41 F*1 320 22 H

34 57 SAD 1BH

-1.45 F*I 321 22 H

1 58 SAD 1BH

-1.3 F*I 322 22 H

3 58 SAD 1BH

-1.27 F*1 323 22 H

14 58 SAD 1BH

-1.31 F*1 324 22 H

18 58 MAD 1BH

-1.31 F*1 325 22 H

20 58 SAD 1BH

-1.4 F*I 326 22 H

23 58 SAN 1BH

-1.42

-1.32 F*I 327 22 H

24 58 SAN 1BH

-1.58

-1.51 F*1 328 22 H

37 58 SAN IBH

-1.46

-1.3 F*I Unit 1January 2001 Steam Generator 15 Day and C

Attachment I March 5, 2002 Page 39 22 STEAM GENERATOR F*1 TUBES. BOC2I. 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 329 22 H

4 59 SAD 1BH

-1.26 F*1 330 22 H

5 59 SAD 1BH

-1.42 F*1 331 22 H

9 59 SAD IBH

-1.3 F*I 332 22 H

15 59 MAD 1BH

-1.34 F*1 333 22 H

16 59 MAD 1BH

-1.16 F*I 334 22 H

20 59 SAD 1BH

-1.43 F*I 335 22 H

23 59 SAN 1BH

-1.55

-1.48 F*I 336 22 H

24 59 SAN IBH

-1.54

-1.51 F*1 337 22 H

25 59 SAD 1BH

-1.4 F*I 338 22 H

27 59 SAD 1BH

-1.41 F*I 339 22 H

28 59 MAN 1BH

-1.42

-1.26 F*I 340 22 H

29 59 SAN 1BH

-1.53

-1.5 F*1 341 22 H

30 59 MAN IBH

-1.35

-1.25 F*I 342 22 H

34 59 SAD 1BH

-1.39 F*I 343 22 H

5 60 SAD 1BH

-1.35 F*I 344 22 H

6 60 SAD IBH

-1.34 F*I 345 22 H

7 60 SAD 1BH

-1.35 F*I 346 22 H

13 60 SAN 1BH

-1.47

-1.43 F*I 347 22 H

15 60 SAN 1BH

-1.38

-1.26 F*I 348 22 H

18 60 SAD 1BH

-1.42 F*I 349 22 H

19 60 MAD 1BH

-1.41 F*I 350 22 H

23 60 SAN 1BH

-1.54

-1.48 F*I 351 22 H

32 60 SAN 1BH

-1.41

-1.31 F*I 352 22 H

37 60 SAD 1BH

-1.45 F*I 353 22 H

7 61 MAD 1BH

-1.26 F*1 354 22 H

12 61 SAD 1BH

-1.29 F*1 355 22 H

18 61 MAD 1BH

-1.43 F*1 356 22 H

20 61 SAD 1BH

-1.35 F*1 357 22 H

22 61 MAN 1BH

-1.43

-1.27 F*1 358 22 H

23 61 SAN IBH

-1.42

-1.3 F*1 359 22 H

25 61 SAN 1BH

-1.53

-1.48 F*1 360 22 H

27 61 MAN 1BH

-0.54

-0.27 F*1 361 22 H

32 61 SAD 1BH

-1.47 F*I 362 22 H

5 62 MAD 1BH

-1.62 F*I 363 22 H

7 62 SAD 1BH

-1.23 F*I 364 22 H

10 62 SAD 1BH

-1.38 F*I 365 22 H

12 62 SAN 1BH

-1.48

-1.42 F*I 366 22 H

13 62 MAD 1BH

-1.26 F*I 367 22 H

16 62 MAN 1BH

-1.23

-1.17 F*I 368 22 H

18 62 SAD 1BH

-1.34 F*I 369 22 H

19 62 MAN 1BH

-1.21

-0.99 F*1 370 22 H

23 62 MAD 1BH

-1.55 F*1 371 22 H

24 62 SAN 1BH

-1.39

-1.36 F*I 372 22 H

25 62 SAI 1BH

-0.61

-0.45 F*I 373 22 H

34 62 SAD 1BH

-1.46 F*1 374 22 H

37 62 SAN 1BH

-1.44

-1.34 F*I 375 22 H

42 62 SAD 1BH

-1.26 F*I Unit IJanuary 2001 Steam Generator 15 Day and C March 5, 2002 Page 40 22 STEAM GENERATOR F*I TUBES. BOC21. 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 376 22 H

1 63 SAD 1BH

-1.24 F*1 377 22 H

11 63 SAD 1BH

-1.3 F*1 378 22 H

12 63 SAN 1BH

-1.49

-1.38 F*I 379 22 H

23 63 SAD IBH

-1.16 F*I 380 22 H

24 63 SAD 1BH

-1.38 F*I 381 22 H

33 63 SAN IBH

-1.53

-1.5 F*I 382 22 H

37 63 SAN IBH

-1.31

-1.22 F*I 383 22 H

1 64 SAD 1BH

-1.21 F*I 384 22 H

2 64 SAD 1BH

-1.26 F*I 385 22 H

7 64 SAN 1BH

-1.62

-1.52 F*I 386 22 H

9 64 SAN 1BH

-1.23

-1.1 F*I 387 22 H

18 64 SAN 1BH

-1.37

-1.3 F*I 388 22 H

32 64 MAD 1BH

-1.5 F*I 389 22 H

34 64 MAN 1BH

-1.41

-1.29 F*I 390 22 H

37 64 SAD IBH

-1.18 F*I 391 22 H

6 65 MAD 1BH

-1.27 F*1 392 22 H

8 65 SAD 1BH

-1.18 F*I 393 22 H

10 65 MAN 1BH

-1.21

-1.15 F*I 394 22 H

11 65 SAD 1BH

-1.33 F*I 395 22 H

12 65 MAN 1BH

-1.21

-1.13 F*I 396 22 H

15 65 MAN 1BH

-1.13

-1.06 F*I 397 22 H

19 65 SAD IBH

-1.29 F*I 398 22 H

24 65 MAN 1BH

-1.43

-1.31 F*I 399 22 H

27 65 SAN IBH

-1.4

-1.27 F*I 400 22 H

33 65 SAN 1BH

-1.55

-1.48 F*I 401 22 H

34 65 SAD 1BH

-1.23 F*I 402 22 H

36 65 SAN IBH

-1.56

-1.46 F*I 403 22 H

37 65 SAD IBH

-1.28 F*I 404 22 H

9 66 SAD 1BH

-1.15 F*1 405 22 H

11 66 MAN 1BH

-1.29

-1.03 F*1 406 22 H

12 66 MAD 1BH

-1.5 F*1 407 22 H

13 66 SAD 1BH

-1.28 F*I 408 22 H

21 66 MAD IBH

-1.03 F*1 409 22 H

24 66 SAN 1BH

-1.43

-1.33 F*I 410 22 H

31 66 SAN 1BH

-1.52

-1.46 F*I 411 22 H

37 66 SAN 1BH

-1.37

-1.24 F*I 412 22 H

7 67 SAD 1BH

-1.31 F*1 413 22 H

9 67 MAN 1BH

-1.28

-1.03 F*I 414 22 H

16 67 SAN 1BH

-1.08

-1.03 F*I 415 22 H

17 67 SAD 1BH

-1.39 F*I 416 22 H

24 67 MAN IBH

-1.35

-1.23 F*I 417 22 H

27 67 MAN 1BH

-1.54

-1.33 F*I 418 22 H

31 67 SAD 1BH

-1 F*I 419 22 H

32 67 SAD IBH

-1.22 F*I 420 22 H

34 67 SAD 1BH

-1.48 F*I 421 22 H

37 67 SAN 1BH

-1.56

-1.47 F*1 422 22 H

9 68 SAN 1BH

-1.59

-1.52 F*1 Unit I January 2001Steam Generator 15 Day and C March 5, 2002 Page 41 22 STEAM GENERATOR F*1 TUBES, BOC21, 2002 NO. SIG LEG ROW COL PERCENT LOCATION ELEV FROM ELEV TO STATUS 423 22 H

10 68 SAD IBH

-1.24 F*I 424 22 H

13 68 SAD 1BH

-1.17 F*I 425 22 H

21 68 MAD 1BH

-1.33 F*I 426 22 H

24 68 MAN 1BH

-1.36

-1.25 F*I 427 22 H

27 68 SAN 1BH

-1.48

-1.38 F*I 428 22 H

31 68 SAD 1BH

-0.9 F*I 429 22 H

32 68 SAD 1BH

-1.32 F*1 430 22 H

33 68 SAD 1BH

-1.27 F*I 431 22 H

37 68 MAN 1BH

-1.5

-1.37 F*I 432 22 H

9 69 SAD 1BH

-1.34 F*I 433 22 H

15 69 MAD 1BH

-0.94 F*I 434 22 H

16 69 MAD 1BH

-1.3 F*1 435 22 H

25 69 MAN 1BH

-1.34

-1.21 F*1 436 22 H

27 69 SAD 1BH

-1.51 F*I 437 22 H

31 69 SAD 1BH

-1.46 F*I 438 22 H

37 69 SAD 1BH

-1.43 F*I 439 22 H

11 70 SAD 1BH

-0.95 F*1 440 22 H

21 70 SAD 1BH

-1.47 F*1 441 22 H

22 70 SAD 1BH

-1.19 F*1 442 22 H

23 70 SAD 1BH

-1.14 F*1 443 22 H

24 70 SAN 1BH

-1.57

-1.45 F*1 444 22 H

27 70 SAN 1BH

-1.38

-1.29 F*I 445 22 H

31 70 MAI 1BH

-0.47

-0.34 F*I 446 22 H

32 70 MAN 1BH

-1.52

-1.47 F*1 447 22 H

12 71 MAD IBH

-1.11 F*1 448 22 H

14 71 SAD 1BH

-1.36 F*I 449 22 H

17 71 MAD 1BH

-1.35 F*I 450 22 H

18 71 SAD 1BH

-1.28 F*I 451 22 H

20 71 SAD 1BH

-1.29 F*I 452 22 H

22 71 MAD 1BH

-1.24 F*I 453 22 H

23 71 MAD 1BH

-1.42 F*I 454 22 H

26 71 SAN IBH

-1.51

-1.43 F*I 455 22 H

27 71 SAD IBH

-0.9 F*1 456 22 H

8 72 SAD 1BH

-1.28 F*1 457 22 H

9 72 MAD 1BH

-1.2 F*I 458 22 H

11 72 MAN 1BH

-1.41

-1.28 F*I 459 22 H

12 72 MAN 1BH

-1.22

-1.12 F*I 460 22 H

13 72 SAD 1BH

-1.37 F*I 461 22 H

16 72 SAD 1BH

-1.4 F*I 462 22 H

24 72 SAN 1BH

-0.47

-0.15 F*I 463 22 H

27 72 MAD 1BH

-1.32 F*I 464 22 H

9 73 SAD 1BH

-1.27 F*I 465 22 H

12 73 MAN 1BH

-1.14

-1.08 F*1 466 22 H

14 73 MAD IBH

-1.13 F*1 467 22 H

15 73 MAN 1BH

-1.06

-0.99 F*1 468 22 H

16 73 MAD 1BH

-1.43 F*I 469 22 H

17 73 MAD 1BH

-1.3 F*I Unit 1January 2001 Steam Generator 15 Day and C March 5, 2002 Page 42 22 STEAM GENERATOR F*I TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 470 22 H

18 73 SAD 1BH

-1.3 F*I 471 22 H

19 73 SAD 1BH

-1.22 F*I 472 22 H

25 73 SAD 1BH

-1.49 F*I 473 22 H

12 74 MAI 1BH

-0.56

-0.38 F*I 474 22 H

14 74 MAD 1BH

-1.34 F*I 475 22 H

15 74 MAD 1BH

-1.29 F*I 476 22 H

17 74 MAN 1BH

-0.78

-0.34 F*I 477 22 H

18 74 SAD 1BH

-0.94 F*I 478 22 H

24 74 SAD 1BH

-1.54 F*I 479 22 H

10 75 MAD 1BH

-1.24 F*I 480 22 H

12 75 MAD 1BH

-1.22 F*I 481 22 H

13 75 SAN 1BH

-1.12

-1.04 F*I 482 22 H

14 75 MAD 1BH

-1.33 F*I 483 22 H

15 75 MAD 1BH

-1.3 F*I 484 22 H

22 75 SAN 1BH

-1.63

-1.59 F*1 485 22 H

27 75 MAD 1BH

-0.9 F*I 486 22 H

8 76 SAD 1BH

-1.29 F*I 487 22 H

11 76 MAN 1BH

-1.09

-0.96 F*I 488 22 H

13 76 SAD 1BH

-1.48 F*I 489 22 H

17 76 MAD 1BH

-1.13 F*I 490 22 H

18 76 SAD 1BH

-1.42 F*I 491 22 H

20 76 SAD IBH

-1.38 F*I 492 22 H

22 76 SAN 1BH

-0.71

-0.12 F*I 493 22 H

26 76 MAD 1BH

-1.5 F*I 494 22 H

8 77 SAD 1BH

-1.26 F*I 495 22 H

11 77 SAD 1BH

-1.39 F*I 496 22 H

12 77 MAD 1BH

-1.49 F*I 497 22 H

13 77 SAN 1BH

-1.06

-0.99 F*I 498 22 H

14 77 SAD 1BH

-1.3 F*I 499 22 H

15 77 SAD 1BH

-1.33 F*I 500 22 H

16 77 MAD 1BH

-1.27 F*1 501 22 H

17 77 MAD 1BH

-1.1 F*I 502 22 H

18 77 MAD IBH

-1.43 F*I 503 22 H

22 77 SAN 1BH

-1.34

-1.16 F*I 504 22 H

25 77 SAD IBH

-0.94 F*1 505 22 H

11 78 SAD 1BH

-1.36 F*1 506 22 H

12 78 SAD 1BH

-0.95 F*I 507 22 H

17 78 SAD IBH

-1.4 F*1 508 22 H

18 78 SAD 1BH

-1.38 F*1 509 22 H

22 78 SAD 1BH

-1.53 F*1 510 22 H

23 78 SAN 1BH

-1.44

-1.41 F*I 511 22 H

26 78 MAN 1BH

-1.13

-1.03 F*I 512 22 H

12 79 SAN 1BH

-0.59

-0.28 F*I 513 22 H

13 79 MAN 1BH

-1.19

-1.14 F*1 514 22 H

14 79 MAN 1BH

-1.17

-0.99 F*I 515 22 H

15 79 MAD 1BH

-1.29 F*1 516 22 H

19 79 SAD 1BH

-1.2 F*I Unit 1 January 2001 Steam Generator 15 Day and C March 5, 2002 Page 43 22 STEAM GENERATOR F*I TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 517 22 H

22 79 SAD 1BH

-1.31 F*I 518 22 H

25 79 SAD IBH

-1.36 F*I 519 22 H

26 79 SAD 1BH

-1.49 F*I 520 22 H

9 80 MAN 1BH

-1.26

-1.12 F*1 521 22 H

10 80 MAD 1BH

-1.36 F*I 522 22 H

12 80 MAD 1BH

-1.36 F*I 523 22 H

13 80 MAN 1BH

-1.22

-1.13 F*I 524 22 H

15 80 SAD 1BH

-1.32 F*I 525 22 H

17 80 MAD 1BH

-1.27 F*I 526 22 H

9 81 MAD 1BH

-1.3 F*I 527 22 H

12 81 SAD 1BH

-0.88 F*I 528 22 H

13 81 SAD 1BH

-1.38 F*1 529 22 H

15 81 MAD 1BH

-0.94 F*I 530 22 H

18 81 SAD 1BH

-1.26 F*1 531 22 H

22 81 SAN IBH

-1.44

-1.34 F*1 532 22 H

26 81 MAN 1BH

-1.53

-1.47 F*1 533 22 H

12 82 SAD IBH

-1.3 F*1 534 22 H

13 82 MAD 1BH

-1 F*I 535 22 H

17 82 MAD 1BH

-1.3 F*I 536 22 H

15 83 SAD 1BH

-0.9 F*I 537 22 H

17 83 SAD 1BH

-0.86 F*1 538 22 H

22 83 SAD 1BH

-1.44 F*1 539 22 H

10 84 SAD 1BH

-1.48 F*I 540 22 H

15 84 SAD 1BH

-1.48 F*I 541 22 H

18 84 MAD 1BH

-0.92 F*I 542 22 H

12 85 SAD 1BH

-1.45 F*I 543 22 H

15 85 SAD 1BH

-1.25 F*I 544 22 H

13 86 SAD 1BH

-1.32 F*I 545 22 H

15 86 MAD 1BH

-1.49 F*I 546 22 H

14 88 SAD 1BH

-1.27 F*1 Unit lJanuary 2001Steam Generator 15 Day and C

Attachment I March 5, 2002 Page 44 22 STEAM GENERATOR F*2 TUBES, BOC21, 2002 NO. S/G LEG ROW COL PERCENT LOCATION ELEV FROM ELEVTO STATUS 1

22 H

21 22 SAD 2BH

-3.51 F*2 2

22 H

16 23 MAN 2BH

-2.64

-1.94 F*2 3

22 H

17 28 SAD 21BH

-2.12 F*2 4

22 H

20 29 SAD 2BH

-3.16 F*2 5

22 H

27 30 SAN 2BH

-1.99

-1.8 F*2 6

22 H

15 31 SAD 2BH

-0.31 F*2 7

22 H

14 35 SAN 2BH

-3.21

-3.1 F*2 8

22 H

19 35 SAD 2BH

-3.18 F*2 9

22 H

37 35 SAD 2BH

-0.88 F*2 10 22 H

19 36 SAD 2BH

-3.32 F*2 11 22 H

18 39 SAD 2BH

-3.16 F*2 12 22 H

14 40 SAI 2BH

-1.51

-1.37 F*2 13 22 H

13 41 MAN 2BH

-3.56

-3.52 F*2 14 22 H

12 42 SAN 2BH

-0.75

-0.64 F*2 15 22 H

15 43 SAN 2BH

-2.04

-1.96 F*2 16 22 H

1 44 MAD 2BH

-3.24 F*2 17 22 H

16 44 SAD 2BH

-3.4 F*2 18 22 H

17 45 MAN 2BH

-3.27

-2.85 F*2 19 22 H

15 46 MAD 2BH

-3.28 F*2 20 22 H

23 46 SAD 2BH

-3.38 F*2 21 22 H

18 47 MAD 2BH

-3.37 F*2 22 22 H

21 47 SAD 2BH

-3.2 F*2 23 22 H

18 48 SAD 2BH

-2.96 F*2 24 22 H

20 48 SAD 2BH

-3.2 F*2 25 22 H

27 48 SAD 2BH

-3.08 F*2 26 22 H

3 49 SAN 2BH

-0.73

-0.61 F*2 27 22 H

26 50 MAD 2BH

-3.14 F*2 28 22 H

11 51 SAD 2BH

-3.16 F*2 29 22 H

18 52 SAD 2BH

-3.1 F*2 30 22 H

24 52 MAN 2BH

-3.54

-3.21 F*2 31 22 H

10 53 MAD 2BH

-3.29 F*2 32 22 H

12 53 SAN 2BH

-2.97

-2.85 F*2 33 22 H

16 53 SAD 2BH

-3.48 F*2 34 22 H

17 53 MAN 2BH

-1.85

-1.73 F*2 35 22 H

20 53 MAD 2BH

-3.16 F*2 36 22 H

15 56 SAN 2BH

-0.8

-0.75 F*2 37 22 H

37 56 SAD 2BH

-3 F*2 38 22 H

13 58 SAN 2BH

-0.44

-0.4 F*2 39 22 H

9 60 SAN 2BH

-1.52

-1.34 F*2 40 22 H

20 60 SAD 2BH

-3.25 F*2 41 22 H

16 65 MAD 2BH

-3.04 F*2 42 22 H

24 69 SAN 2BH

-0.69

-0.6 F*2 43 22 H

19 74 SAN 2BH

-2.02

-1.85 F*2 Unit 1January 2001Steam Generator 15 Day and C