Request for Review of Common-Cause Failure Insights Reports for Emergency Diesel Generators, Pumps, Motor-Operated Valves, and Circuit Breakers
ML012710103
Person / Time
Issue date: 09/27/2001
From: Newberry S
Office of Nuclear Regulatory Research
To: King T, Mayfield M, Zwolinski J
Office of Nuclear Reactor Regulation, Division of Engineering Technology, NRC/RES/DSARE
References
Download: ML012710103 (6)


Text

September 27, 2001 MEMORANDUM TO: John A Zwolinski, Director, DLPM:NRR Thomas R. King, Director, DSARE:RES Michael E. Mayfield, Director, DET:RES FROM:

Scott F. Newberry, Director Division of Risk Analysis and Applications Office of Nuclear Regulatory Research

SUBJECT:

REQUEST FOR REVIEW OF COMMON-CAUSE FAILURE INSIGHTS REPORTS FOR EMERGENCY DIESEL GENERATORS, PUMPS, MOTOR-OPERATED VALVES, AND CIRCUIT BREAKERS Attached for your information and review are four draft reports on common-cause failure (CCF) insights for emergency diesel generators (EDGs), pumps, motor-operated valves (MOVs), and circuit breakers. These reports provide CCF trends and CCF engineering insights for these risk-important components from 1980 through 2000. The insights in these reports have been obtained from the same event data used to obtain quantitative CCF parameter estimates. This study is part of an ongoing program of risk-based analysis of reactor operating experience.

This effort is undertaken to systematically identify risk-significant insights and provide feedback to the regulatory process.

To serve the NRC staff more efficiently, the Operating Experience Risk Analysis Branch (OERAB) is streamlining its data collection and analysis activities to provide more up-to-date results that are readily available to the NRC staff. In the future, the information in these reports will be made available through a Web-based operating experience information/data system. In addition, the data and results typically presented in our reliability and component studies, ASP analyses, initiating event studies, and other efforts will be made available through a web page.

Therefore, we will not routinely produce hard copy NUREG reports of this nature.

The insights contained in these studies are meant to provide useful information to enhance the risk-informed planning of various inspection activities. These reports include engineering insights that may be used to improve the risk perspective of inspection activities associated with failure causes, coupling factors, detection methods, and subsystems that contribute most to CCF events.

For example, Inspection Manual Chapter 2515 outlines the latest inspection process. Appendix A to this chapter provides an overview of the Baseline Inspection Program, and Appendix B describes the Supplemental Inspection Program. The baseline inspection is contained in Inspection Procedure 71111 and its attachments. Several of these attachments advise the inspector to examine or be aware of conditions that lead to the potential for common-cause failure. They include the following:

CONTACT: Dale Rasmuson (dmr), OERAB:DRAA:RES (301) 415-7571

Multiple Addressees 2

  • 1111.07 Heat Sink Performance
  • 1111.12 Maintenance Rule Implementation
  • 1111.17 Permanent Plant Modifications
  • 1111.19 Post-Maintenance Testing
  • 1111.20 Refueling and Outage Activities The following procedures do not reference common-cause failures, but they can certainly be enhanced by an awareness of common-cause failures:
  • 1111.21 Safety System Design and Performance Capability
  • 1111.22 Surveillance Testing The following inspection procedures are part of the supplemental inspection program:

Inspection Procedure 93801 Safety System Functional Inspection (SSFI)

Inspection Procedure 93811 Electrical Distribution System Functional Inspection (EDSFI)

The common-cause failure insights in these reports can help enhance these inspection procedures and inspection plans. We have also attached a summary table containing preliminary high-level CCF insights for these four components.

A cooperative activity is underway between the OERAB and the NRRs Inspection Program Branch (IIPB) to make more effective use of pertinent insights from these other OERAB operating experience reports work in risk-informed inspection activities. OERAB is working with IIPB to develop and test a process to better capture risk-based operating experience insights and update risk-informed inspection activities using operating experience from system and component studies, common-cause failure insights, and accident sequence precursor events.

OERAB is ready and willing to assist other users of our operating experience reports as needed.

As noted below, these reports support the strategic goals of maintaining safety; improving regulatory effectiveness, efficiency, and realism; reducing unnecessary burden; and increasing public confidence. We briefly summarize them below as they pertain to the Agencys strategic goals.

Maintaining Safety These reports contain occurrence rate trends in time of CCF events and complete CCF events that could be useful for determining whether safety is improving, deteriorating, or remaining constant in light of both Agency and licensee safety initiatives.

The trends in the yearly occurrence rates for all CCF events for the four component types are decreasing and statistically significant.

About 32 percent of the plants have not experienced a CCF event involving the EDG. Approximately 34 percent of the plants have experience only one event

Multiple Addressees 3

during the study period. Less than 4 percent of the plants have experienced four or more EDG CCF events.

Regulatory Effectiveness and Efficiency The results, findings, and information in these insights reports are intended to support plant inspections. They provide information for risk-informed inspection activities to enhance the use of inspection resources. The reports indicate the most important causes of failure, detection methods, subsystems and/or subcomponents.

The dominant failure mode was fail to run for EDGs (56 percent) and pumps (54 percent). Fail to open was the dominant failure mode for MOVs (59 percent) and circuit breakers (54%).

For EDGs, 66 percent of the events were detected through testing while inspection and maintenance detected 27 percent of the events. Only 10 percent were discovered during an actual demand. This is as expected considering the extensive and frequent surveillance test requirements for EDGs contained in Technical Specifications. Similarly, 58 percent of the circuit breaker CCF events were detected by testing. Over 20 percent were discovered during an actual demand. Inspection and maintenance accounted for the other 20 percent of the events.

In contrast, only 35 percent of the pump CCF events 40 percent of the MOV CCF events were detected by testing. Thirty percent of the pump CCF events and 39 percent of the MOV CCF events were detected by an actual demand.

Inspection and maintenance account for the remaining 21 percent for both pumps and MOVs.

A review of the MOV CCF events by dates shows that, prior to 1990, 35 percent of the events were discovered by Testing and 45 percent by Demands. Since 1990, 59 percent have been discovered by Testing and 27 percent by Demands.

This tends to confirm the effectiveness of the impact of Generic Letter 89-10 and its follow-on activities.

The largest number of events (30 percent of the CCF events) affected the instrumentation and control (I&C) sub-system. The breaker, cooling, engine, fuel oil, and generator are significant contributors. Together, these five sub-systems are involved in over 80 percent of the EDG CCF events. The battery, exhaust, and lubricating oil sub-systems are minor contributors.

Reducing Unnecessary Burden These reports include engineering insights and associated information that may be used to focus inspection activities on the more-important areas identified by the CCF experience.

Multiple Addressees 4

Ensuring Public Confidence These reports demonstrate the Agencys ability to analyze operating experience independently of licensee-sponsored activities. These independent assessments allow the Agency to determine whether licensee assessments of risk and risk-informed activities are reasonable.

We are specifically interested in your review of:

The technical adequacy of data, specifically during the 1996-1998 update period, The appropriateness of the risk-important findings, and How the information contained in the report can be presented to better help you in your risk-informed regulatory activities.

It is our understanding that NRR will coordinate the review by and receipt of comments from the regions.

We appreciate receiving comments by 60 days from the receipt of this memorandum. If you have any questions regarding these reports, please contact Dr. Dale Rasmuson (301-415-7571) of my staff.

Attachments: As stated cc w/att.:

R. Zimmerman/A. Thadani, RES S. Collins, NRR J. Johnson, NRR B. Sheron, NRR R. Borchardt, NRR

Multiple Addressees 5

Memorandum Dated: / /01

SUBJECT:

REQUEST FOR REVIEW OF COMMON-CAUSE FAILURE INSIGHTS REPORTS FOR EMERGENCY DIESEL GENERATORS, PUMPS, MOTOR-OPERATED VALVES, AND CIRCUIT BREAKERS Distribution w/att.:

OERAB RF ARubin, RES MRubin, NRR TShedlosky, RI DRAA RF MCunningham, RES ECobey, NRR JTrapp, RI File Center NSiu, RES MReinhart, NRR PBernard, RII Public MDrouin, RES JCalvo, NRR WRogers, RII FGillespie, NRR WRaughley, RES PKoltay, NRR MParker, RIII JRosenthal, RES JVora, RES RBarrett, NRR SBurgess, RIII JFlack, RES RLloyd, RES PWilson, NRR TPruett, RIV MFields, NRR GParry, NRR DCoe, NRR LCollins, RIII ARamey-Smith, RES MCheok, RES WDean, NRR AMadison, NRR WScott, NRR DHickman, NRR AEl-Bassioni, NRR HVanderMolen, RES JLarkins, ACRS GLanik, RES MJohnson, NRR SShowe, HR JGiitter, NMSS MSatorius, NRR DThatcher, NRR, LMarsh, NRR GHolahan, NRR JStrosnider,NRR DMatthews, NRR BBoger, NRR WLanning, RGN-I ABlough, RGN-I VMcCree, RGN-II CCasto, RGN-II JGrobe, RGN-III GGrant, RGN-III AHowell, RGN-IV KBrockman, RGN-IV MMarkley, ACRS*

  • 15 copies to ACRS DOCUMENT NAME: A:\\CCF INSIGHTS PEER REVIEW LETTER-NRC.WPD To receive a copy of this document, indicate in the box C copy w/o attach/encls E copy w/attach/encls N no copy OFFICE OERAB C

OERAB C

OERAB C

RES C

NAME DRasmuson SMays PBaranowsky SNewberry DATE 9/26/01 9/26/01 9/26/01 9/27/01 OFFICIAL RECORD COPY OAR in ADAMS? (Y or N)

Y Publicly Available? (Y or N)

Y Template Number: RES-006 Accession Number: ML RES File Code: 2C-3

ROUTING AND TRANSMITTAL SLIP Date 09/26/01 TO: (Name, office symbol, room #, building, agency/post)

Initials Date

1. Dale Rasmuson - Concur - Fill in Y or N for OAR in ADAMS and Y or N for Publicly Available
2. Steve Mays - Concur
3. Pat Baranowsky - Concur
4. Scott Newberry - Concur/Signature
5. Nancy - Please Distribute and send 15 copies of the reports to Mike Markley of the ACRS - Fill in Template Number and Accession Number