REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY EVALUATION OF DEVICE (AMENDED IN ITS ENTIRETY)

NO.: NR-0271-D-101-E DATE: June 22, 2001 PAGE 1 OF 3 DEVICE TYPE:

Ionization Smoke Detector MODEL:

235 Series, 305 Series, 311 Series DISTRIBUTOR/MANUFACTURER:

Edwards Systems Technology (Formerly G.S. Building Systems Corp.)

5 N. Main Street Pittsfield, ME 04967-1500 SEALED SOURCE MODEL DESIGNATION:

NRD Model A001 ISOTOPE:

MAXIMUM ACTIVITY:

MODELS:

Americium-241 1.10 microcurie (40.70 kBq) 235 Series Americium-241 0.55 microcurie (20.35 kBq) 305 Series Americium-241 0.85 microcurie (31.45 kBq) 311 Series LEAK TEST FREQUENCY: Not Required PRINCIPAL USE: (P) Ion Generators, Smoke Detectors CUSTOM DEVICE: YES X NO

REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY EVALUATION OF DEVICE (AMENDED IN ITS ENTIRETY)

NO.: NR-0271-D-101-E DATE: June 22, 2001 PAGE 2 OF 3 DEVICE TYPE:

Ionization Smoke Detector DESCRIPTION:

The 305 Series are round, single station smoke detectors and consist of two models: the A chamber which is a low wall housing for duct detectors, and the B chamber which is a high wall housing for area detectors. These models are sold under various brand names which may have different plastic housings. All 305 Series models contain one source with nominal activity of 0.55 microcurie (20.35 kBq). The manufacturer, Edwards Systems Technology (EST),

may market the models in this series under different brand names. However, in all cases, the smoke detector design will not change and the label will reference ESTs license number.

The 235 Series are round, single station smoke detectors. The ion chamber in the 235 Series may contain any activity up to 1.1 microcurie (40.7 kBq). The models in this series differ only in the activity in the ion chamber. EST may market the models in this series under different brand names. However, in all cases, the smoke detector design will not change and the label will reference ESTs license number.

The 311 Series detectors are designed to be wired to the fire alarm panel of commercial/industrial fire protection systems. The ion chamber in the 311 Series may contain any activity up to 0.85 microcurie (31.45 kBq). The 311 Series is manufactured in two models: one with a factory set smoke sensitivity, the other with adjustable smoke sensitivity. The design of the ionization chamber and the radiation protection features of the two models are identical. EST may market the models in this series under different brand names. However, in all cases, the smoke detector design will not change and the label will reference ESTs license number.

The expected working life of the products is 20 years.

REGISTRY OF RADIOACTIVE SEALED SOURCES AND DEVICES SAFETY EVALUATION OF DEVICE (AMENDED IN ITS ENTIRETY)

NO.: NR-0271-D-101-E DATE: June 22, 2001 PAGE 3 OF 3 DEVICE TYPE:

Ionization Smoke Detector

REFERENCES:

The following supporting documents are hereby incorporated by reference and are made a part of this registry document.

G.S. Building Systems Corporations letters dated February 27, 1984, May 10, 1984, October 25, 1984, December 23, 1991, January 13, 1992, October 27, 1993, March 15, 1994, April 22, 1994, January 3, 1995, February 24, 1995, March 8, 1995,and June 27, 1997, with enclosures thereto.

ESTs letter dated April 24, 1998, with enclosures thereto.

ESTs letters dated March 23, 2001, May 29, 2001, and facsimile dated June 4, 2001, with enclosures thereto.

ESTs electronic mail dated June 20, 2001, with enclosures thereto.

ISSUING AGENCY:

U.S. Nuclear Regulatory Commission

/RA/

Date: June 22, 2001 Reviewer:

John P. Jankovich

/RA/

Date: June 22, 2001 Concurrence:

Seung J. Lee