U.S. NUCLEAR REGULATORY COMMISSION

Revision 2 November 1978 REGULATORY GUIDE

OFFICE OF 'STANDARDS DEVELOPMENT

REGULATORY GUIDE 1.72 SPRAY POND PIPING MADE FROM

FIBERGLASS-REINFORCED THERMOSETTING RESIN

A.

INTRODUCTION

General Design Criterion 1, "Quality Stand ards and Records," of Appendix A, "General Design Criteria for Nuclear Power Plants," to

10 CFR Part 50, "Domestic Licensing of Pro

"-duction and Utilization Facilities,"

requires that structures, systems, ý and .components important ..to safety be designed, fabricated, erected, and tested to quality standards com mensurate with the importance of the safety functions to be performed. Appendix B, "Qual ity Assurance Criteria for Nuclear Power Plants and Fuel Reprocessing Plants," to

10 CFR

Part 50 requires that measures be established to ensure materials control and control of special processes such as resin molding.

Section 50.55a, "Codes and Standards," of

10 CFR Part 50 requires that design, fabrica tion, installation, testing, or inspection of the specified system or component be in accordance with generally recognized codes and staridards.

Footnote 6 to § 50.55a states that the use of specific Code Cases may be authorized by the Commission upon request pursuant to § 50.55a (a)(2)(ii), which requires that proposed alter natives to the described requirements or por tions thereof provide an acceptable, level of quality and safety.

This guide describes a method acceptable to the NRC staff for implementing these require ments with regard to the design, fabrication, and testing of fiberglass-reinforced thermo setting resin (RTR)

piping for spray pond applications. This guide applies to light-water cooled and gas-cooled reactors. .The Advisory Committee on Reactor Safeguards has been con sulted concerning this guide and has concurred in the regulatory position.

  • Lines indicate substantive changes tram previous issue.

USNRC REGULATORY GUIDES

Regulatory Guides eam issued So descilbe end make svalable ID ft publi methods acCeptable w to NRC staff al ill*em ntig apeodf pIne o .on Com

'laln rguatl Io denwte lecdn-,=

wed by 1w staff in evsu

~

pcfcproblems or postiletad aceldents. Or ID prVOvd gJUWdnc

10

nt.Ragulatory Gulde. wre hiot subeftfts te 10"0

sauelosnd corn pence with irn Is not equkL Meihods and eolutlona dffrent rom *so s

out in weidss v be

=

"*e thP

prfdo r

a

"* *Xe&W

Me e

c.n aetr ka by to Corm desio Comnenwts n uggestou wo fo tr aov~ament meh

1wae idesare ncourasgdat of I m.

n wgukd. .Ube ,ebed. as Pfrpiat. 10 sci10date camnme and 10 ~sic now infomato or expe-rienoe.

This guide was orvised ae remit of subetantie coment isev OM 111 pubic end additional emil revlew.

B.

DISCUSSION

The ASME Boiler and Pressure Vessel Com mittee publishes a document entitled "Code Cases."

Generally, a Code Case explains the

'intent of rules in the ASME's Boiler and Pressure Vessel Code (the Code)' or provides for alternative requirements under special circumstances. Most Code Cases are evehtually Ssuperseded by Lrevisions to the Code and then are annulled by action of the ASME Council.

Code Case N-155-1 (1792-1),

referred to in this guide, is limited to Section III, Division 1, of the Code and is oriented toward design and fabrication of RTR piping. The Code Case does not prescribe a lower temperature limit, prima rily because the American Society for Testing and Materials (ASTM)

specifications do not contain a lower temperature" limit, but RTR

piping systems would normally be qualified for the intended service temperature condition.

It is planned that after Revision 2 of, this guide is issued, the acceptability of future minor revisions to Code Case N-155 (1792) will be noted in Regulatory Guide 1.84, "Design and Fabrication Code Case Acceptability--ASME

Section III Division I1." Major revisions to the Code Case will, however, result in a revision

-to this guide -(1.72). Filament-wound struc tures have mechanical properties superior to fiberglass-filled laminates, and they are con sidered more desirable when intended for safety-related pressure components.

The Code Case obtains an allowable design stress from the hydrostatic design basis (HDB)

strength as derived from either Procedure A

Copies Jay be obtained from the American Society of Mechan ticl Inghieers. United Ingieerling Canter, 345 Seat 47th Street.

New Terk. New Yorkt 10017.

Connffao awloid be se nt fto Ssem"

of Me CommisIonS

U.S. Nucea noguitor Commission Washingon D.C.

  • W

Attntion: Ockstlng anO

Ma e

gildas ua ied in 1ft Ioowg ten bod tlona:

1. ftwr Reactors S. PoducM

2. Iosearch wed Tat Rescto

7. Trsrporatn

3. -uek and Maltis Fact Wes

.c Heath

4. gnvoniwntdl and SRing S. Antitrust ind Financial Review S.

tairla end Pi P

cton

10. Gen*eal.

Request for singe coples of lasued Suides lutch nay be uspaoduedl for f

placement en en automat dalbutlon Ist fo g

o f at u.gd In specfick dvimsn etmiod be wadle hInwm an7le UMSNuclarReulaimy Comission. Wash n. D.C.

0 . Aato Okectr. DivIon of Techicsl Iformation and Document Contol.

(cyclic) or Procedure B (static) of Specifica tion ASTM D-2992, "Standard Method for Ob taining Hydrostatic Design Basis for Reinforced Thermosetting Resin Pipe and Fittings Proce dures." 2 These procedures are intended to be used for general applications for Class 3 piping. For safety-related systems such as spray pond piping, a design factor of 6 is desired. Under some conditions, the qualifica tion procedures may not result in. a design factor of 6, and it is therefore necessary to perform an additional short-time cyclic and burst test to ensure that the desired design factor is obtained.

Failure is defined in ASTM D-2992 as either leaking, weeping, or bursting. Whichever of these occurs first defines failure.

General guidance for loading combinations relative to design limits for Class 3 piping may be found in Regulatory Guide 1.48, "Design Limits and Loading Combinations for Seismic Category I Fluid System Components."

How ever, specific equations and limits from Code Case N-155 are not addressed in Regulatory Guide 1.48.

Normal commercial practice provides a

weather-resistant coating to the exterior of RTR piping that will be exposed to weather conditions.

Experience has shown that this practice provides adequate protection for the service considered in this guide. Distribution of resin is generally such that more resin Is applied to the exterior of the pipe than to the interior, and part of the outer resin may have special properties to protect the underlying material from deleterious effects from sources such as ultraviolet radiation and weathe

r. RTR

piping has been used to distribute cooling water to nozzles in spray ponds. It Is desirable to provide weather protection to such piping.

However, the omission of an exterior protective coating would be acceptable for piping installed in covered but accessible trenches, provided the inservice inspection frequency is increased to require visual inspection for leaks of all such piping at least once every year.

Limited information is available on the effects of radiation on laminates (fiberglass and resin materials bonded together). However, short time exposure tests have been made, and they showed no appreciable change in the tensile strength of the pipe test piece. For cooling water application,. there appears little opportu nity for radiation exposure, and the piping should be acceptable without additional testing.

This guide does not address the acceptability of RTR piping for other system

s. If RTR

piping is considered for systems such as liquid radwaste systems where it may be exposed to long-term radiation, the laminates should be a Copies may be obtained from the Amerien Society for Testing and Materal$, 1915 Racm Street, Philadelphia, Pennsylvania 19103.

tested and qualified" for the intended environ ment. Use of RTR piping for systems other than spray ponds would be considered on a case-by-case basis only.

Metal pressure vessels and closed systems

"are provided with pressure relief valves or devices for protection against overpressure.

Where RTR piping systems are used for open ended systems such as the cooling water distri bution for spray ponds, the relief valve provi sions may be omitted. However, it is desirable to protect the integrity of the piping by other means such as selection of spray nozzles to prevent their clogging or selection of pump delivery characteristics to prevent the piping pressure from exceeding the design pressure for the piping.

Industry experience with fiberglass reinforced resin pressure vestels-and piping extends over

20

to

23 years of service I

experience during which the performance of fiberglass-reinforced resin piping has been satisfactory.

Industry claims that the life expectancy for properly installed piping is at least 40 years, the' normal design life for presently planned- nuclear- power plants. Since RTR piping applications will be limited to temperatures less than 650 C (149 0 F). except for occasional transients to 1000C (212 0F),

there is little need for applying insulation to such piping. Hence it should be left bare to make the piping readily, accessible for inspec tion.

Since the NRC' staff is allowing only 105 cycles for qualification testing of the piping, special precautions should be taken to ensure that the design assumptions are not exceeded.

The preoperational testing program should include tests of the installed piping to ensure absence of vibration due to weather conditions or water flow that may fatigue the piping beyond values assumed in the design of the system.

Inservice inspection requirements should be similar to those in ASME Code,Section XII for Class 3 components. 3 The inspection for Code Class 3 components involves a visual inspection of the piping for evidence of unanticipated leakage and structural distress.

Since the support of RTR piping may be sensitive, each inservice inspection of such piping should include all its supports.

C.

REGULATORY POSITION

Safety-related spray pond piping components made from fiberglass-reinforced thermosetting

3 Components classified as NRC Quality Group At B,. ard C

should conform to the requirements of the ARMi Boiler and Pressure Vessel Code for Class 3 components (NBC Regulatory Guide 1.25, "Qu*lity Group Classificatio and Standards for Water-, Steam-, and Radoactive-Wuts-Containing Components ot Nuclear Power Plants-).

1.72-2

resin should comply with ASME Code Case N-155-l (1792-1) supplemented by the follow ing:

1. The design temperature for spray pond piping should be 1000 C (212 0F).

2. The allowable design stress should be the value obtained from the minimum HDB (hydro static design basis) in Table 3611-1 of Code Case N-155-1 (Procedure A or B) or the value determined as one-sixth of the stress obtained from a short-time burst test for the pipe being qualified, whichever is lower. The short-time burst strength should be determined by bursting the pipe (ASTM D-1599-74 using free end mounting) after it has been exposed to 105 pressure cycles from atmospheric to design pressure.

3. The value of "K" in equation 9 of para graph 3652.2 should be limited to 1.2 unless it can be demonstrated that with the use of a large value of K the functional capability of the system will not be impaired during upset and emergency conditions.

4. The following items should be identified:

a. The physical location of the system in relation to other safety-related systems, b. The design and service loads, and c. The value of "B" to be used in equa tion 1 of paragraph 3641.1, together with justification for its selection.

5. Pressure-relief devices may be omitted for piping systems that are open-ended and for which the system pressure is limited by other means (such as nonclogging spray nozzles and self-limiting pump characteristics) to design pressure.

6. RTR piping should be uninsulated or uncovered and installed under conditions that make it readily accessible for inspection.

7. Preoperational and inservice inspections should be as follows:

a. During the preoperational testing peri od, tests should be made to verify that the piping is free of vibration induced by weather conditions or water flow that could fatigue the piping prematurely.

b. Fiberglass-reinforced piping components should be inspected in accordance with ASME

Code,Section XI,

for Code Class 3 compo nents .3 In addition, all pipe supports should be inspected.

c. Inspection frequency for piping should be increased to once annually if an exterior weather-resistant coating is not provided.

D.

IMPLEMENTATION

The purpose of this section is to provide information to license applicants and licensees regarding the NRC staff's plans for using this regulatory guide.

This guide reflects current NRC staff prac tice. Therefore, except in those cases in which the applicant proposes an acceptable alter native method for complying with ,specified por tions of the Commission's regulations, the method described herein is being and will con tinue to be used in the evaluation of submittals in connection with operating license or con struction permit applications until this guide is revised as a result of suggestions from the public or additional staff review.

1.72-3