L-PI-05-054, Unit 2 Steam Generator Inspection Results - 15-Day Report

From kanterella
Jump to navigation Jump to search
Unit 2 Steam Generator Inspection Results - 15-Day Report
ML051650318
Person / Time
Site: Prairie Island 
Issue date: 06/08/2005
From: Solymossy J
Nuclear Management Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
FOIA/PA-2010-0209, L-PI-05-054
Download: ML051650318 (50)


Text

9..'

-1 I-NMC Committed to NudearExcel Prairie Island Nuclear Generating Plant Operated by Nuclear Management Company, LLC JUN 0 8 2009 U S Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 L-PI-05-054 T.S. 5.6.7 Prairie Island Nuclear Generating Plant Unit 2 Docket 50-306 License No. DPR-60 2005 Unit 2 Steam Generator Inspection Results Day Report In accordance with Technical Specification 5.6.7.1, the number of tubes plugged or sleeved in each steam generator is provided in Table 1.

Table I - Prairie Island Unit 2 Refueling Outage 23 Plugs and Sleeves EOC 22 2005 Re pairs BOC 23 Type of Repair 21 SG 22 SG 21 SG 22SG 21 SG 22 SG Tubes Plugged 230 250 1

12 8

242 258 Tubes Sleeved 0

0

'0 0

0 0

EOC = End of Cycle BOC = Beginning of Cycle SG = Steam Generator In accordance with Technical Specification 5.6.7.4, the identification of F* and EF* tubes and the location and extent of degradation are included in Enclosure 1 (21 and 22 Steam Generator F* and EF* Tube Report) to this letter. There are 2306 tubes classified as F* tubes and 21 tubes classified as EF* tubes.

Summary of Commitments This letter contains no new commitments and no revisions to existing commitments.

6 h M. Solymossy Vice President, Pr ie Is nd Nuclear Generating Plant Nuclear Management Company, LLC 1717 Wakonade Drive East

  • Welch, Minnesota 55089-9642 Telephone: 651.388.1121

Document Control Desk Page 2 Enclosure cc:

Administrator, Region 1i, USNRC Project Manager, Prairie Island, USNRC Resident Inspector, Prairie Island, USNRC

ENCLOSURE 1 21 AND 22 STEAM GENERATOR EF* AND F* TUBE REPORT CODES Location (Landmark)

TRH = Top of OEM Hard Roll Hot Leg 1 BH = Bottom of Additional Hard Roll 1 2BH = Bottom of Additional Hard Roll 2 EBH = Bottom of Additional Elevated Hard Roll Types of F and EF Stars EF* = EF* Tube with Elevated Additional Roll Expansion F*O = F* Tube without Additional Roll Expansion F*1 = F* Tube with One Additional Roll Expansion F*2 = F* Tube with Second Higher Additional Roll Expansion Indication Code IRR = Inadvertent Re-Roll - No Defect - Tracked for Configuration Management MAD = Multiple Axial Indication - No Longer Detectable MAI = Multiple Axial Indication MAN = Multiple Axial Indication - No Change MCI = Multiple Circumferential Indication SAD = Single Axial Indication - No Longer Detectable SAI = Single Axial Indication SAN = Single Axial Indication - No Change SCD = Single Circumferential Indication - No Longer Detectable SCN = Single Circumferential Indication - No Change SVD = Single Volumetric Indication - No Longer Detectable SVI = Single Volumetric Indication 21 STEAM GENERATOR F*0 TUBES, BOC23, 2005 No. SIG Le Row Col Indication Location Elev from Elev to tatus 1

21 H

2 1

SAI TRH

-2.41

-2.28 F*O 2

21 H

1 2

SAN TRH

-2.29

-2.02 F*O 3

21 H

2 2

SAN TRH

-2.38

-2.19 F*O 4

21 H

1 4

SAN TRH

-2.63

-2.39 F*O 5

21 H

1 5

SAN TRH

-2.67

-2.54 F*O 6

21 H

2 5

SAN TRH

-2.71

-2.52 F*O 7

21 H

1 7

SAN TRH

-2.58

-2.49 F*O 8

21 H

2 7

MAN TRH

-2.80

-2.35 F*O 9

21 H

4 7

SAN TRH

-1.92

-1.89 F*O 10 21 H

7 8

SAI TRH

-2.47

-2.40 F*O 11 21 H

24 8

SAN TRH

-2.18

-2.14 F*O 12 21 H

12 9

SAN TRH

-2.06

-1.93 F*O 13 21 H

20 9

MAN TRH

-2.75

-2.63 F*O 14 21 H

25 9

SAN TRH

-2.12

-2.09 F*O 15 21 H

2 10 SAN TRH

-2.59

-2.32 F*O 16 21 H

14 10 SAN TRH

-2.93

-2.80 F*O Page 1 of 48

I ;!

21 STEAM GENERATOR F*0 TUBES, BOC23,. 2005 No. SIG Lp Row Col Indication Location E-ev from Elev to tatus 17 21 H

15 10 SAN TRH

-2.68

-2.61 F*O 18 21 H

16 10 SAN TRH

-2.83

-2.77 F*O 19 21 H

25 10 SAN TRH

-2.23

-2.20 F*O 20 21 H

26 10 SAN TRH

-2.19

-2.16 F*O 21 21 H

27 10 MAN TRH

-2.59

-2.63 F*O 22 21 H

28 10 MAN TRH

-2.37

-2.31 F*O 23 21 H

7 11 SAN TRH

-1.63

-1.42 F*O 24 21 H

19 11 SAN TRH

-2.58

-2.45 F*O 25 21 H

27 11 MAN TRH

-2.46

-2.32 F*O 26 21 H

29 11 MAN TRH

-2.43

-2.34 F*O 27 21 H

15 12 SAN TRH

-2.80

-2.65 F*O 28 21 H

26 12 SAN TRH

-2.29

-2.25 F*O0 29 21 H

27 12 MAN TRH

-2.24

-2.23 F*O 30 21 H

28 12 MAN TRH

-2.29

-2.19 F*O 31 21 H

1 13 MAN TRH

-2.60

-2.48 F*O 32 21 H

6 13 SAN TRH

-2.37

-2.26 F*O 33 21 H

7 13 MAN TRH

-2.28

-2.15 F*O 34 21 H

23 13 SAN TRH

-2.51

-2.41 F*O 35 21 H

25 13 SAN TRH

-2.51

-2.40 F*O 36 21 H 6 14 MAN TRH

-2.61

-2.24 F*O 37 21 H

6 15 SAN TRH

-2.46

-2.30 F*O 38 21 H

7 15 SAN TRH

-2.48

-2.04 F*O 39 21 H

20 15 SAN TRH

-2.53

-2.45 F*O 40 21 H

28 16 MAN TRH

-2.57

-2.47 F*O 41 21 H

2 16 SAN TRH

-2.56

-2.30 F*O 42 21 H

6 16 SAN TRH

-2.45

-2.32 F*O 43 21 H

15 16 SAN TRH

-2.46

-2.29 F*O 44 21 H

16 16 SAN TRH

-2.32

-2.22 F*O 45 21 H

28 16 MAN TRH

-2.23

-2.18 F*O 46 21 H

5 17 MAN TRH

-2.53

-2.44 F*O 47 21 H

7 18 SAN TRH

-2.57

-2.47 F*O 48 21 H

26 19 MAN TRH

-2.61

-2.18 F*O 49 21 H

8 20 SAN TRH

-2.51

-2.40 F*O 50 21 H

25 20 MAN TRH

-2.52

-2.39 F*O 51 21 H

31 20 SAN TRH

-2.59

-2.49 F*O 52 21 H

33 1 20 MAN TRH

-2.61

-2.46 F*O 53 21 H

29 21 SAN TRH

-2.57

-2.46 F*O 54 21 H

32 21 MAN TRH

-2.57

-2.50 F*O 55 21 H

6 22 MAN TRH

-2.49

-2.29 F*O 56 21 H

7 22 SAN TRH

-2.47

-2.27 F*O 57 21 H

2 23 SAl TRH

-2.61

-2.49 F*O 58 21 H

7 23 SAN TRH

-2.49

-2.26 F*O 59 21 H

33 24 SAN TRH

-2.53

-2.34 FF*

60 21 H

1 25 MAN TRH

-2.47

-2.40 F*O 61 21 H

33 25 SAN TRH

-2.50

-2.36 F*O 62 21 H

1 27 SAN TRH

-2.56

-2.49 F*

0 63 21 H

33 30 SAN TRH

-2.55

-2.41 F*O 64 21 H

17 32 SAN TRH

-2.64

-2.53 F*O 65 21 H

1 34 SAN TRH _

-2.61

-2.47 F*0 66 21 H

1 35 SAN TRH

-2.73

-2.60 F*O Page 2 of 48

-I 1

21STEAM GENERATOR F*0 TUBES, BO C23: 2005 No. SIG Leg Row Col Indication Location Elev from Elev to Status 67 21 H

1 40 SAN TRH

-2.71

-2.64 F*C 68 21 H

25 41 SAN TRH

-2.72

-2.32 F*O 69 21 H

26 41 SAI TRH

-2.58

-2.46 F*

O 70 21 H

21 47 MAN TRH

-2.46

-2.40 F*O 71 21 H

1 58 SAN TRH

-2.44

-2.30 F*O 72 21 H

27 60 MAN TRH

-2.54

-2.39 F*O 73 21 H

28 60 SAN TRH

-2.43

-2.27 F*O 74 21 H

33 60 MAN TRH

-2.42

-2.32 F*O 75 21 H

26 61 MAN TRH

-2.70

-2.59 F*O 76 21 H

23 62 MAN TRH

-2.51

-2.35 F*O 77 21 H

28 62 SAN TRH

-2.47

-2.34 F*O 78 21 H

32 62 SAN TRH

-2.50

-2.36 F*O 79 21 H

33 62 SAN TRH

-2.53

-2.32 F*O 80 21 H

26 63 SAN TRH

-2.44

-2.37 F*O 81 21 H

29 63 SAN TRH

-2.78

-2.63 F*O 82 21 H

18 64 MAI TRH

-2.49

-2.38 F*O 83 21 H

23 64 SAN TRH

-2.56

-2.43 F*O 84 21 H

25 64 SAN TRH

-2.64

-2.50 F*O 85 21 H

26 64 MAN TRH

-2.55

-2.42 F*O 86 21 H

32 64 MAN TRH

-2.45

-2.28 F*O 87 21 H

33 64 SAN TRH

-2.42

-2.31 F*O 88 21 H

3 65 SAN TRH

-2.77

-2.74 F*O 89 21 H

23 65 SAN TRH

-2.64

-2.50 F*O 90 21 H

24 65 SAN TRH

-2.42

-2.31 F*O 91 21 H

26 65 MAN TRH

-2.47

-2.30 F*O 92 21 H

30 65 SAN TRH

-2.43

-2.27 F*O 93 21 H

1 66 MAN TRH

-2.61

-2.21 F*O 94 21 H

2 66 SAN TRH

-2.23

-1.96 F*O 95 21 H

23 66 SAN TRH

-2.53

-2.42 F*O 96 21 H

27 66 SAN TRH

-2.43

-2.27 F*O 97 21 H

32 66 SAN TRH

-2.34

-2.27 F*O 98 21 H

17 67 SAN TRH

-1.65

-1.52 F*O 99 21 H

33 67 MAI TRH

-2.52

-2.40 F*0 100 21 H

1 68 SAN TRH

-2.41

-2.31 F*O 101 21 H

6 68 SAN TRH

-2.55

-2.43 F*O 102 21 H

8 68 SAN TRH

-2.66

-2.56 F*O 103 21 H

27 68 SAN TRH

-2.58

-2.40 F*O 104 21 H

2 69 SAN TRH

-2.57

-2.49 F*O 105 21 H

24 69 MAN TRH

-2.48

-2.35 F*O 106 21 H

32 69 SAN TRH

-2.53

-2.37 F*O 107 21 H

8 70 SAN TRH

-2.62

-2.51 F*O 108 21 H

23 70 MAN TRH

-2.62

-2.42 F*O 109 21 H

24 70 SAN TRH

-2.51

-2.37 F*O 110 21 H

27 70 SAN TRH

-2.42

-2.29 F*O 111 21 H

1 71 SAI TRH

-2.50

-2.42 F*O 112 21 H

23 71 SAN TRH

-2.45

-2.37 F*0 113 21 H

33 71 SAI TRH

-2.52

-2.39 F*O 114 21 H

27 72 SAN TRH

-2.41

-2.30 F*O 115 21 H

31 72 MAN TRH

-2.51

-2.29 F*O 116 21 H

1 73 MAN TRH

-2.48

-2.35 F*O Page 3 of 48

21 STEAM GENERATOR F*0 TUBES, BOC23, 2005 No. SIG Lpj Row Col Indication Location EIev from EIev to Status 117 21 H

30 74 SAN TRH

-2.41

-2.33 F*O 118 21 H

32 74 SAN TRH

-2.37

-2.30 F*O 119 21 H

1 75 SAN TRH

-2.52

-2.35 F*O 120 21 H

16 75 MAN TRH

-2.44

-2.36 F*O 121 21 H

23 75 SAN TRH

-2.53

-2.43 F*O 122 21 H

27 75 SAN TRH

-2.42

-2.31 F*O 123 21 H

31 75 MAN TRH

-2.53

-2.40 F*O 124 21 H

32 75 MAI TRH

-2.56

-2.40 F*O 125 21 H

1 76 SAN TRH

-2.58

-2.41 F*O 126 21 H

6 76 SAN TRH

-2.67

-2.51 F*O 127 21 H

14 76 MAI TRH

-2.37

-2.26 F*O 128 21 H

16 76 SAN TRH

-2.58

-2.21 F*O 129 21 H

21 76 SAN TRH

-2.59

-2.51 F*O 130 21 H

26 76 MAN TRH

-2.65

-2.53 F*O 131 21 H

27 76 MAN TRH

-2.60

-2.33 F*O 132 21 H

29 76 SAN TRH

-2.51

-2.37 F*O 133 21 H

33 76 MAI TRH

-2.51

-2.35 F*O 134 21 H

1 77 SAN TRH

-2.71

-2.28 F*O 135 21 H

8 77 SAN TRH

-2.64

-2.47 F*O 136 21 H

27 77 MAN TRH

-2.43

-2.33 F*O 137 21 H

1 78 MAN TRH

-2.57

-2.47 F*O 138 21 H

16 78 SAN TRH

-2.32

-2.27 F*O 139 21 H

17 78 SAN TRH

-2.81

-2.73 F*O 140 21 H

22 78 MAI TRH

-2.66

-2.57 F*O 141 21 H

23 78 SAN TRH

-2.48

-2.38 F*O 142 21 H

27 78 SAN TRH

-2.43

-2.36 F*O 143 21 H

29 78 SAN TRH

-2.29

-2.22 F*O 144 21 H

32 78 MAN TRH

-2.51

-2.39 F*O 145 21 H

14 79 SAN TRH

-2.52

-2.39 F*O 146 21 H

20 79 SAN TRH

-2.53

-2.37 F*O 147 21 H

22 79 MAI TRH

-2.45

-2.36 F*O 148 21 H

26 79 MAN TRH

-2.47

-2.34 F*0 149 21 H

24 80 SAI TRH

-2.43

-2.33 F*0 150 21 H

25 80 MAN TRH

-2.55

-2.40 F*0 151 21 H

31 80 SAN TRH

-2.57

-2.45 F*O 152 21 H

5 81 SAN TRH

-2.52

-2.37 F*O 153 21 H

25 81 SAN TRH

-2.50

-2.39 F*O 154 21 H

16 82 SAN TRH

-2.18

-2.09 F*O 155 21 H

22 82 SAN TRH

-2.32

-2.25 F*O 156 21 H

23 82 MAN TRH

-2.18

-2.13 F*O 157 21 H

25 82 SAI TRH

-2.22

-2.15 F*O 158 21 H

1 83 SAN TRH

-2.59

-2.44 F*O 159 21 H

6 93 SAN TRH

-2.58

-2.47 F*O 21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG lLp Row Cot Indication Location Elev from Elev tolStatus 1

21 H

4 2

MAD l 1BH l

-1.06 l

l F*1 2

21 H

3 3

SAD I1BH1-1

-1.53 F*1 3

21 H

14 3

MAD l11BH l

-1.63 l

l F*1 4

21 H

3 4

SAD I1BH3 l

-1.01 l

l F*1 Page 4 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. S/G Le Row Col Indication Location Elev from Elev to Status 5

21 H

6 4

SAD 1BH

-1.16 F*1 6

21 H

7 4

SAD 1BH

-1.00 F*1 7

21 H

3 5

'SAD 1BH

-1.58 F*1 8

21 H

7 5

MAD 1BH

-1.16 F*1 9

21 H

1 6

SAD 1BH

-1.00 F*1 10 21 H

3 6

SAD 1BH

-1.61 F*1 11 21 H

7 7

SAD IBH

-1.74 F*1 12 21 H

13 7

MAD 1BH

-1.00 F*1 13 21 H

17 7

MAD 1BH

-1.16 F*1 14 21 H

1 8

MAD 1BH

-1.31 F*1 15 21 H

2 8

SAD 1BH

-1.60 F*1 16 21 H

5 8

SAD 1BH

-1.05 F*1 17 21 H

10 8

MAD 1BH

-0.90 F*1 18 21 H

13 8,

MAD 1BH

-1.35 F*l 19 21 H

3 9

SAD 1BH

-1.60 F*l 20 21 H

4 9

MAD IBH

-1.48 F*l 21 21 H

5 9

SAD 1BH

-1.37 F*l 22 21 H

7 9

MAD 1BH

-1.22 F*l 23 21 H

11 9

MAD 1BH

-1.34 F*l 24 21 H

13 9

SAD 1BH

-1.27 F*l 25 21 H

18 9

MAD 1BH

-1.49 F*1 26 21 H

21 9

MAD 1BH

-1.04 F*l 27 21 H

1 10 MAD 1BH

-1.39 F*l 28 21 H

4 10 SAD 1BH

-1.39 F*l 29 21 H

5 10 SAD 1BH

-1.10 F*1 30 21 H

11 10 SAD 1BH

-1.03 F*1 31 21 H

12 10 SAD 1BH

-1.25 F*l 32 21 H

19 10 SAD 1BH

-1.05 F*l 33 21 H

20 10 SAD 1BH

-1.33 F*l 34 21 H

1 11 SAD 1BH

-1.48 F*l 35 21 H

2 11 SAD 1BH

-0.90 F*l 36 21 H

3 11 SAD 1BH

-1.61 F*l 37 21 H

5 11 MAN 1BH

-1.37

-1.30 F*1 38 21 H

6 11, SAD 1BH 1

-1.40 F*l 39 21 H

10 11 SAD 1BH

-1.14 F*l 40 21 H

13 11 SAD 1BH

-0.78 F*l 41 21 H

14 11 MAD 1BH

-1.12 F*l 42 21 H

15 11 MAD 1BH 1

-1.30 F*l 43 21 H

23 11 MAD 1BH

-1.50 F*l 44 21 H

24 11 MAI 1BH

-0.33

-0.08 F*l 45 21 H

1 12 SAD 1BH

-1.32 F*l 46 21 H

2 12 SAD 1BH

-1.47 F*l 47 21 H

4 12 SAD 1BH

-1.06 F*1 48 21 H

-5 12 SAD 11BH

-1.09 F*l 49 21 H

6 12 IRR 1BH

-1.43 F*l 50 21 H

7 12 SAD 1BH

-1.07 F*l 51 21 H

9 12 SAD 1BH

-1.33 F*l 52 21 H

11 12 SAD 1BH

-1.06 F*1 53 21 H

14 12 MAN 1BH

-1.33

-0.96 F*

54 21 H

22 12 SAD 1BH

-1.40 Fl Page 5 of 48

21_STEAM GENERATOR F*1TUBES, BOC23,2005 No. S/G Leg Row Col Indication Location Elev from Elev tolStatus 55 21 H

23 12 MAD 1BH

-1.43 F*1 56 21 H

2 13 MAN 11BH

-1.45

-0.94 F*1 57 21 H*

4 13 SAN 1BH

-1.26

-1.16 F*1 58 21 H

5 13 SAD 1BH

-1.48 F*1 59 21 H

8 13 MAD 1BH

-1.12 F*1 60 21 H

11 13 MAD IBH

-1.33 F*1 61 21 H

13 13 SAD 1BH

-1.40 F*1 62 21 H

14 13 SAD 1BH

-1.33 F*1 63 21 H

15 13 MAD 1BH

-1.19 F*1 64 21 H

21 13 SAD 1BH

-1.24 F*1 65 21 H

2 14 SAN 1BH

-1.09

-1.03.

F*1 66 21 H

4 14 MAD 1BH _-1.22 F*1 67 21 H

5 14 SAD 1BH

-2.14 F*1 68 21 H

7 14 SAN 1BH 1

-3.90

-3.81 F*1 69 21 H

9 14 MAD 1BH

-1.35 F*1 70 21 H

13 14 SAD 1BH

-1.17 F*1 71 21 H

15 14 MAD 1BH

-1.21 F*1 72 21 H

22 14 SAD 11BH

-1.17 F*1 73 21 H

23 14 SAD 1BH

-1.30 F*1 74 21 H

1 15 MAN 1BH 1

-1.33

-1.04 F*1 75 21 H

2 15 SAD 1BH

-1.38 F*1 76 21 H

4 15 MAD 1BH

-1.02 F*1 77 21 H

5 15 SAD 1BH

-1.17 F*1 78 21 H

8 15 SAD 1BH

-1.21 F*1 79 21 H

10 15 SAD 1BH

-1.37 F*1 80 21 H

11 15 SAD 1BH

-0.89 F*1 81 21 H

13 15 MAN 1BH

-1.38

-0.91 F*1 82 21 H

14 15 SAD 1BH

-1.26 F*1 83 21 H

15 15 SAD 1BH

-0.90 F*1 84 21 H

16 15 MAN 1BH

-1.24

-1.11 F*1 85 21 H

18 15 MAN 1BH

-1.25

-1.09 F*1 86 21 H

19 15 MAD 1BH

-1.21 F*1 87 21 H

22 15 SAD 1BH1-

-1.22 F*1 88 21 H

23 15 SAD 1BH

-1.18 F*l 89 21 H

26 15 SAD 1BH

-0.85 F*l 90 21 H

27 15 SAD 1BH

-1.31 F*1 91 21 H

1 16 SAD 1BH

-1.34 F*l 92 21 H

3 16 SAD 1BH

-1.16 F*l 93 21 H

4 16 MAN 1BH

-1.32

-1.01 F*l 94 21 H

5 16 SAD 1BH

-1.16 Fl 95 21 H

7 16 SAD 1BH

-0.80 F*l 96 21 H

8 16 MAD 1BH1

-1.20 F*l 97 21 H

10 16 SAD 1BH

-0.88 F*l 98 21 H

12 16 MAD 1BH

-1.23 F*l 99 21 H

13 16 MAD 1BH

-1.16 F*1 100 21 H

14 16 MAD 1BH3-

-1.35

=

F*1 101 21 H

17 16 SAD 1BH

-1.28 F*l 102 21 H

18 16 SAD 1BH

-1.24 F*l 103 21 H

24 16 MAD 1BH

-1.39 F*l 104 21 H

26 16 MAD 1BH

-1.40 F*l Page 6 of 48

21 STEAM GENERATOR F*1_TUBES, BOC23, 2005 No. SIG Leg Row Cot Indication Location Elev from Elev tolStatus 105 21 H

29 16 MAN -

BH

-1.17

-1.09 F*1 106 i

21 H

1 17 MAN 1BH

-1.33

-0.96 F*1 107 21 H

2 17 SAD 1BH

-1.40 F*1 108 21 H

6 17 SAD 1BH

-0.92 F*1 109 21 H

7 17 SAD 1BH

-1.03 F*1 110 21 H

10 17 SAD 1BH

-1.37.___

F*1 111 21 H

11 17 SAD 1BH

-1.32 F*1 112 21 H

13 17 SAD 1BH

-1.31 F*1 113 21 H

16 17 MAD 1BH

-1.00 IF*

114 21 H

19 17 SAD 1BH

-1.32 F*l 115 21 H

22 17 SAD 1BH

-1.35 F*l 116 21 H

25 17 SAN 1BH

-1.11

-0.86 F*1 117 21 H

1 18 MAD 1BH

-1.21 F*1 118 21 H

2 18 SAD 1BH

-0.89 F*1 119 21 H

3 18 SAN 1BH

-1.26

-1.18 F*1 120 21 H

5 18 MAN 1BH

-1.36

-0.90 F*l 121 21 H

10 18 MAD 1BH

-1.25 F*l 122 21 H

11 18 SAD 1BH

-1.40 F*l 123 21 H

13 18 SAD 1BH

-1.30 F*l 124 21 H

16 18 SAD 1BH

-1.44 F*1 125 21 H

18 18 MAD 1BH

-0.82 F*1 126 21 H

20 18 SAD 1BH

-0.85 F*1 127 21 H

22 18 SAD 1BH

-1.15 F*l 128 21 H

25 18 SAD 1BH

-2.11 F*l 129 21 H

29 18 SAD 1BH

-1.04 F*1 130 21 H

31 18 SAD 1BH

-1.22 F*l 131 21 H

1 19 MAN 1BH

-1.39

-0.98 F*l 132 21 H

2 19 SAD 1BH-

-1.39 F*l 133 21 H

4 19 SAD 1BH

-1.20 F*l 134 21 H

7 19 MAD 1BH

-1.04 F*1 135 21 H

8 19 SAD 1BH

-1.32 F*l 136 21 H

11 19 MAD 1BH 1

-1.37 F*1 137 21 H

12 19 MAD 1BH

-1.20 F*l 138 21 H

14 19 SAD 1BH

-0.85 F*1 139 21 H

15 19 SAD 1BH

-1.12 F*1 140 21 H

16 19 SAD 1BH

-1.20 F*1 141 21 H

17 19 MAD 1BH

-0.86 F*l 142 21 H

20 19 SAD 1BH

-1.21 F*1 143 21 H

22 19 MAD 1BH

-0.93 F*1 144 21 H

23 19 SAD 1BH

-1.06 F*1 145 21 H

24 19 SAD 1BH

-0.90 F*l 146 21 H

27 19 MAD 1BH

-1.10 F*1 147 21 H

30 19 SAD 1BH

-1.37 F*l 148 21 H

31 19 MAD 1BH

-1.30 F*1 149 21 H

32 19 SAD 1BH

-1.42 F*1 150 21 H

33 19 SAD 1BH

-1.38 F*1 151 21 H

4 20 SAD 1BH

-0.95 F*l 152 21 H

6 20 SAD 1BH

-0.90 F*1 153 21 H

7 20 MAN 1BH

-1.24

-1.06 F*1 154 21 H

9 20 SAD 1BH

-1.16 F*l Page 7 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 l

No. SIG Le Row Col indication Location Elev from Elev to Status 155 21 H

11 20 SAD IBH

-1.06 F*1 156 21 H

13 20 MAN 1BH

-1.27

-1.09 F*1 157 21 H

16 20 SAD IBH

-1.20 F*l 158 21 H

17 20 MAN IBH

-1.21

-1.13 F*l 159 21 H

'18 20 SAD IBH

-1.29 F*l 160 21 H

19 20 SAD 1BH

-1.40 F*l 161 21 H

20 20 SAD 1BH

-1.23 F*1 162 21 H

23 20 MAD 1BH

-1.42 F*1 163 21 H

29 20 MAN 1BH

-1.16

-1.01 F*l 164 21 H

30 20 SAD IBH

-1.40 F*l 165 21 H

32 20 SAN 1BH

-1.15

-1.08 F*l 166 21 H

35 20 SAD 1BH

-1.27 F*l 167 21 H

36 20 MAD 1BH

-1.37 F*l 168 21 H

37 20 MAD IBH

-1.35 F*1 169 21 H

6 21 SAN 1BH

-1.24

-1.20 F*1 170 21 H

8 21 SAD 1BH

-1.15 F*1 171 21 H

11 21 SAD 1BH

-1.21 F*l 172 21 H

12 21 MAD 1BH

-1.27 F*l 173 21 H

14 21 MAN 1BH

-0.56

-0.13 F*l 174 21 H

16 21 MAN 1BH

-1.21

-1.04 F*l 175 21 H

17 21 MAN 1BH

-1.28

-1.15 F*l 176 21 H

19 21 SAD 1BH

-1.03 F*1 177 21 H

20 21 MAD 1BH

-0.88 F*1 178 21 H

23 21 MAD 1BH

-1.41 F*l 179 21 H

24 21 MAN 1BH

-1.16

-0.85 F*l 180 21 H

26 21 SAD 1BH

-1.25 F*l 181 21 H

27 21 SAD 1BH

-1.47 F*1 182 21 H

28 21 SAD 1BH

-0.85 F*l 183 21 H

30 21 SAD 1BH

-1.40 F*l 184 21 H

31 21 SAD 1BH

-1.27 F*l 185 21 H

33 21 SAD 1BH

-1.26 F*l 186 21 H

36 21 SAD 1BH

-1.25 F*1 187 21 H

1 22 MAN 1BH

-1.34

-0.96 F*l 188 21 H

2 22 MAN 1BH

-1.27

-1.14 F*l 189 21 H

4 22 MAN IBH

-1.19

-1.10 F*l 190 21 H

5 22 SAD IBH

-0.84 F*l 191 21 H

8 22 MAN 1BH

-1.22

-0.89 F*l 192 21 H

9 22 SAD IBH

-1.16 F*l 193 21 H

10 22 SAD IBH

-0.90 F*1 194 21 H

13 22 MAD 1BH

-1.20 F*l 195 21 H

14 22 MAN 1BH

-1.16

-1.08 F*l 196 21 H

17 22 MAN 1BH

-1.15

-1.06 F*l 197 21 H

18 22 SAD 1BH

-1.16 F*l 198 21 H

19 22 MAD IBH

-1.20 F*l 199 21 H

20 22 SAD 1BH

-0.88 F*l 200 21 H

21 22 MAD 1BH

-1.31 F*l 201 21 H

22 22 SAD IBH

-0.85 F*l 202 21 H

24 22 MAD IBH

-0.85 F*1 203 21 H

26 22 MAD IBH

-0.87 F*l 204 21 H

28 22 SAD IBH

-1.28 F*l Page 8 of 48

21 STEAM GENERATOR FP TUBES, BOC23, 2005 No. SIG Leg Row Col ndication Location EIev from Elev to Status 205 21 H

32 221 SAD IBH

-1.39 F*l 206 21 H

37 22 MAD IBH

-1.49 F*l 207 21 H

1 23 MAD IBH

-1.00 F*l 208 21 H

3 23 MAN IBH

-1.31

-0.82 F*1 209 21 H

5 23 MAD IBH

-1.40 F*l 210 21 H

.6 23 MAN IBH

-1.19

-1.08 F*l 211 21 H

.8 23 MAD IBH

-1.30 F*l 212 21 H

9 23 MAN IBH

-0.45

-0.17 F*l 213 21 H

10 23 SAD IBH

-0.87 F*l 214 21 H

12 23 MAD IBH

-1.21 F*l 215 21 H

14 23 MAN IBH

-1.20

-1.02 F*l 216 21 H

15 23 MAN IBH

-1.16

-1.06 F*l 217 21 H

17 23 MAD IBH

-1.30 F*l 218 21 H

18 23 MAN IBH

-1.01

-0.89 F*l 219 21 H

19 23 MAN IBH

-1.18

-1.05 F*1 220 21 H

21 23 MAD IBH

-0.98 F*1 221 21 H

24 23 MAD IBH

-0.83 F*1 222 21 H

25 23 MAD IBH

-0.78 F*l 223 21 H

26 23 MAD IBH

-0.97 F*l 224 21 H

27 23 SAD IBH

-1.17 F*l 225 21 H

30 23 MAD IBH

-0.97 IF*

226 21 H

31 23 SAD IBH

-1.23 F*l 227 21 H

34 23 SAD IBH

-1.17 F*l 228 21 H

35 23 MAD IBH

-1.03 F*l 229 21 H

37 23 SAD IBH

-1.38 F*l 230 21 H

38 23 MAD IBH

-1.29 F*l 231 21 H

39 23 MAD IBH

-1.38 F*l 232 21 H

2 24 SAD IBH

-1.35 F*1 233 21 H

4 24 MAD IBH

-1.23 F*l 234 21 H

7 24 SAD 1BH

-1.32 F*l 235 21 H

8 24 SAD 1BH

-1.26 F*l 236 21 H

9 24 SAN 1BH

-1.13

-1.04 F*l 237 21 H

11 24 MAD 1BH

-1.16 F*l 238 21 H

12 24

-MAN 1BH

-1.21

-1.04 F*l 239 21 H

13 24 SAD 1BH

-1.01 F*

240 21 H

15 24 SAD 1BH

-0.89 F*1 241 21 H

16 24 MAD IBH

-1.20 F*l 242 21 H

19 24 MAD 1BH

-0.82 F*l 243 21 H

20 24 MAD IBH

-1.34 F*l 244 21 H

23 24 SAD IBH

-0.94 F*l 245 21 H

25 24 SAD 1BH

-1.25 F*1 246 21 H

28 24 SAD IBH

-0.93 F*l 247 21 H

29 24 SAD IBH

-1.14 F*l 248 21 H

30 24 MAD IBH

-1.31 F*l 249 21 H

31 24 SAD IBH

-0.98 F*l 250 21 H

35 24 SAD IBH

-0.83 F*1 251 21 H

37 24 SAD IBH

-1.32 F*l 252 21 H

5 25 SAD 1BH

-1.17 F*l 253 21 H

6 25 MADI 1BH

-1.20 F*l 254 21 H

7 25 SAI-I1BH

-0.39

-0.24 F*l Page 9 of 48

21 STEAM GENERATOR Fl TUBES. BOC23, 2005 No. SIG _ Row Col Indication Location Elev from ilev to Status 255 21 H

8 25 SAD IBH

-1.49 F*l 256 21 H

9 25 SAD IBH

-0.82 F*1 257 21 H

10 25 SAD IBH

-1.29 F*l 258 21 H

16 25 SAN 1BH

-1.22

-0.86 F*l 259 21 H

17 25 SAD 1BH

-1.21 F*l 260 21 H

20 25 MAD IBH

-1.26 F*l 261 21 H

24 25 SAD IBH

-1.00 F*1 262 21 H

25 25 MAD IBH

-1.25 F*1 263 21 H

28 25 SAD 1BH

-1.06 F*l 264 21 H

30 25 MAD IBH

-1.39 F*1 265 21 H

38 25 MAD IBH

-0.89 F*l 266 21 H

1 26 SAD 1BH

-0.95 F*l 267 21 H

5 26 SAD 1BH

-1.27 F*1 268 21 H

7 26 MAD IBH

-1.32 F*l 269 21 H

8 26 SAD IBH

-1.25 F*l 270 21 H

10 26 MAD IBH

-0.91 F*1 271 21 H

13 26 MAD IBH

-1.27 F*l 272 21 H

14 26 SAD IBH

-1.02 F*l 273 21 H

15 26 MAD 1BH

-0.85 F*l 274 21 H

16 26 SAD 1BH

-1.26 F*l 275 21 H

17 26 SAN IBH

-1.00

-0.93 F*l 276 21 H

19 26 MAD IBH

-1.27 F*1 277 21 H

21 26 SAD 1BH

-1.02 F*1 278 21 H

22 26 SAD IBH

-1.22 F*l 279 21 H

25 26 SAD 1BH

-1.13 F*l 280 21 H

28 26 SAD 1BH

-0.93 F*l 281 21 H

34 26 SAD 1BH

-1.10 F*l 282 21 H

2 27 SAD 1BH

-1.20 F*l 283 21 H

3 27 SAD IBH

-1.46 F*l 284 21 H

4 27 MAN 1BH

-0.79

-0.14 F*1 285 21 H

5 27 SAN IBH

-1.64

-1.51 F*l 286 21 H

6 27 SAD IBH

-0.87 F*1 287 21 H

8 27 SAN 1BH

-1.15

-1.04 F*1 288 21 H

9 27 SAD 1BH

-1.23 F*1 289 21 H

13 27 SAD IBH

-1.28 F*l 290 21 H

16 27 SAD IBH

-1.21 F*l 291 21 H

17 27 MAN 1BH

-1.35

-1.15 F*l 292 21 H

18 27 SAD IBH

-1.33 F*l 293 21 H

24 27 SAD IBH

-0.95 F*1 294 21 H

25 27 SAD 1BH

-0.99 F*l 295 21 H

26 27 MAD 1BH

-1.27 F*l 296 21 H

27 27 MAD IBH

-1.30 F*l 297 21 H

31 27 MAD IBH

-0.79 F*l 298 21 H

32 27 SAN IBH

-1.16

-1.04 F*l 299 21 H

35 27 SAD 1BH

-1.06 F*l 300 21 H

36 27 MAD IBH

-1.18 F*l 301 21 H

37 27 MAD IBH

-0.90 F*1 302 21 H

1 28 MAN 1BH

-1.32

-0.88 F*l 303 21 H

3 28 MAN 1BH

-1.28

-1.17 F*l 304 21 H

5 28 MAN IBH

-1.28

-1.10 F*l Page 10 of 48

21_STEAM GENERATOR F*l TUBES, BOC23; 2005 No. S/G Leg Row Col Indication Location Elev from Elev to Status 305 21 H

6 28 SAD IBH

-1.30 F*l 306 21 H

7 28 MAD 1BH

-1.17 F*l 307 21 H

8 28 SAD IBH

-1.20 F*l 308 21 H

10 28 SAD 1BH

-1.30 F*l 309 21 H

11 28 SAD 1BH

-0.77 F*l 310 21 H

15 28 SAN 1BH

-1.19

-1.13 F*1 311 21 H

16 28 MAN 1BH

-1.28

-1.11 F*l 312 21 H

17 28 MAD 1BH

-1.17 F*l 313 21 H

19 28 MAN 1BH

-1.29

-0.96 F*l 314 21 H

20 28 SAD 1BH

-1.25 F*l 315 21 H

21 28 MAN 1BH

-1.36

-0.97 F*l 316 21 H

28 28 SAD iBH

-1.18 F*1 317 21 H

30 28 SAD 1BH

-1.15 F*l 318 21 H

31 28 MAD 1BH

-1.19 F*l 319 21 H

32 28 SAD 1BH

-0.96 F*l 320 21 H

33 28 SAD 1BH

-1.03 F*l 321 21 H

39 28 SAD IBH

-1.32 F*l 322 21 H

2 29 MAD 1BH

-1.04 F*1 323 21 H

3 29 SAD 1BH

-0.98 F*l 324 21 H

5 29 SAD 1BH

-0.89 F*1 325 21 H

7 29 MAN 1BH

-1.15

-1.05 F*l 326 21 H

8 29 MAD 1BH

-1.27 F*l 327 21 H

9 29 SAD 1BH

-0.90 F*l 328 21 H

10 29 MAD 1BH

-1.31 F*l 329 21 H

16 29 MAN 1BH

-1.03

-0.82 F*l 330 21 H

18 29 MAN 1BH

-1.35

-1.07 F*l 331 21 H

19 29 MAD 1BH

-1.30 F*l 332 21 H

22 29 MAD 1BH

-1.09 F*l 333 21 H

23 29 MAD 1BH

-1.26 F*1 334 21 H

25 29 SAD 1BH

-1.26 F*l 335 21 H

26 29 SAD IBH

-1.22 F*l 336 21 H

27 29 MAD 1BH 1

-1.27 F*l 337 21 H

28 29 MAD 1BH

-1.16 F*l 338 21 H

31 29 MAD 1BH

-1.29 F*l 339 21 H

35 29 SAD 1BH

-0.86 F*l 340 21 H

1 30 MAD 1BH

-1.42 F*l 341 21 H

3 30 MAD 1BH

-1.26 F*l 342 21 H

4 30 MAN 1BH

-0.47

-0.32 F*l 343 21 H

5 30 SAD 1BH

-0.94 F*l 344 21 H

6 30 MAN IBH

-1.35

-0.99 F*l 345 21 H

8 30 SAN 1BH

-1.26

-1.19 F*l 346 21 H

10 30 SAD 1BH

-1.12 F*1 347 21 H

22 30 MAD 1BH

-1.20 F*l 348 21 H

26 30 SAD 1BH

-0.79 F*1 349 21 H

29 30 MAD 1BH

-0.88 F*1 350 21 H

31 30 MAD 1BH

-1.38 F*l 351 21 H

36 30 MAD IBH

-1.00 F*l 352 21 H

38 30 SAD 1BH

-1.13 F*l 353 21 H

1 31 SAD 1BH

-1.21 F*l 354 21 H 12 31 MAD 1BH

-1.00 F*l Page 11 of 48

21 STEAM GENERATOR F*l TUBES, BOC23, 2005 No. SIG IL2 Row Col Indication Location EIev from Elev to Status 355 21 H

3 31 MAN 1BH

-1.09

-1.04 F*l 356 21 H

4 31 MAN 1BH

-1.38

-0.80 F*l 357 21 H

5 31 SAD 1BH

-1.08 F*1 358 21 H

6 31 SAN IBH

-1.06

-0.74 F*l 359 21 H

7 31 MAD 1BH

-1.41 F*l 360 21 H

8 31 SAD 1BH

-1.09 F*l 361 21 H

10 31 SAD 1BH

-1.26 F*l 362 21 H

22 31 SAD 1BH

-1.27 F*l 363 21 H

26 31 SAD 1BH

-0.84 F*l 364 21 H

27 31 SAD-1BH

-1.29 F*l 365 21 H

32 31 SAD 1BH

-1.36 F*i 366 21 H

35 31 SAD 1BH

-0.90 F*l 367 21 H

37 31 MAD 1BH

-1.23 F*l 368 21 H

3 32 MAD 1BH-1

-1.50 F*l 369 21 H

5 32 SAD IBH

-1.45 F*l 370 21 H

6 32 MAN 1BH

-1.35

-0.99 F*l 371 21 H

7 32 MAD IBH

-1.04 F*l 372 21 H

8 32 SAD 1BH

-0.97 F*1 373 21 H

24 32 MAD 1BH

-1.29 F*l 374 21 H

25 32 SAD 1BH

-1.26 F*l 375 21 H

26 32 SAD 1BH

-1.18 F*l 376 21 H

27 32 SAD 1BH

-1.27 F*l 377 21 H

30 32 SAN 1BH

-1.29

-1.15 F*l 378 21 H

32 32 MAN 1BH

-1.20

-1.13 F*l 379 21 H

33 32 SAD IBH

-1.26 F*l 380 21 H

36 32 MAD 1BH

-0.90 I F*1 381 21 H

4 33 SAD 1BH 1

-1.30 F*1 382 21 H

7 33 MAN 1BH

-1.15

-1.06 F*1 383 21 H

8 33 MAN IBH

-1.17

-1.07 F*l 384 21 H

11 33 SAD IBH

-1.24 F*1 385 21 H

21 33 MAN 1BH

-1.22

-1.10 F*l 386 21 H

23 33 SAD 1BH

-0.88 F*l 387 21 H

24 33 SAD 1BH

-1.31 F*l 388 21 H

27 33 MAN 1BH

-1.35

-1.19 F*1 389 21 H

33 33 MAD IBH

-1.26 F*l 390 21 H

37 33 MAD 1BH

-1.38 F*l 391 21 H

2 34 SAD 1BH

-1.24 F*l 392 21 H

4 34 SAD IBH

-1.14 F*l 393 21 H

5 34 MAD 1BH

-1.00 F*1 394 21 H

7 34 SAD IBH

-1.42 F*l 395 21 H

8 34 MAN 1BH

-1.18

-1.03 F*l 396 21 H

10 34 MAN 1BH

-1.24

-0.90 F*1 397 21 H

27 34 SAD 1BH

-0.87 F*l 398 21 H

28 34 SAD 1BH

-0.88 F*l 399 21 H

29 34 MAD 1BH

-1.22 F*l 400 21 H

33 34 SAD 1BH

-1.26 F*l 401 21 H

34 34 MAN 1BH

-1.27

-1.15 F*l 402 21 H

36 34 SAD IBH -

-0.98 F*1 403 21 H

37 34 MAD 1BH 1

-1.38 F*l 404 21 H

41 34 MAD 1BH

-1.22 F*l Page 12 of 48

21 STEAM GENERATOR F*1CTUBES, BOC23, 2005 No. S/G L Row Col Indication Location Elev from Elev to Status 405 21 H

2 351 SAD

. 1BH

-1.27 F*1 406 21 H

4 35 MAD 1BH

-0.95 F*1 407 21 H

5 35 MAD 1BH

-1.18 F*1 408 21 H

8 35 MAN 1BH

-1.17

-1.08 F*1 409 21 H

11 35 SAD 1BH

-1.28 F*1 410 21 H

12 35 SAD 1BH

-1.29 F*l 411 21 H

-13 35 MAN 1BH

-1.13

-0.98 F*l 412 21 H

21 35 MAD 1BH

-1.21 F*l 413 21 H

24 35 SAD 1BH

-1.25 F*l 414 21 H

25 35 SAD 1BH

-1.00 F*l 415 21 H

27 35 MAD 1BH

-1.20 F*l 416 21 H

29 35 SAD 1BH

-1.29 F*l 417 21 H

30 35 SAD 1BH

-1.31 F*l 418 21 H

31 35 SAD 1BH

-1.36 F*l 419 21 H

37 35 SAD 1BH

-1.45 F*l 420 21 H

2 36 SAD 1BH

-1.00 F*1F 421 21 H

3 36 SAD 1BH

-1.30 F*l 422 21 H

4 36 MAD 1BH

-1.27 F*l 423 21 H

6 36 MAN 1BH

-1.15

-1.04 F*l 424 21 H

9 36 SAD IBH

-1.42 F*l 425 21 H

10 36 SAD 1BH

-1.35 Fl 426 21 H

12 36 SAD IBH

-1.55 F*l 427 21 H

20 36 MAN 1BH

-1.15

-1.03 F*l 428 21 H

22 36 SAN IBH

-1.18

-1.05 F*l 429 21 H

23 36 MAD 1BH

-1.30 F*l 430 21 H

25 36 SAD IBH

-1.40 F*l 431 21 H

27 36 SAD 1BH

-1.26 F*l 432 21 H

28 36 SAD IBH

-1.00 F*l 433 21 H

29 36 SAD 1BH

-1.31 F*l 434 21 H

35 36 MAD 1BH

-0.86 F*l 435 21 H

36 36 SAD 1BH

-0.90 F*l 436 21 H

37 36 SAD 1BH

-1.00 F*1 437 21 H

38 36 MAD 1BH

-1.22 F*1 438 21 H

4 37 SAD 1BH

-1.33 F*l 439 21 H

6 37 MAN 1BH

-1.14

-1.07 F*1 440 21 H

8 37 MAN 1BH _

-0.91

-0.85 F*1 441 21 H

9 37 SAD 1BH

-0.90 F*l 442 21 H

10 37 SAD 1BH

-0.90 F*l 443 21 H

13 37 MAN 1BH

-1.13

-1.02 F*1 444 21 H

21 37 SAN 1BH

-1.16

-1.04 F*l 445 21 H

22 37 SAD 1BH

-0.80 F*1 446 21 H

25 37 SAD 1BH

-1.20 F*1 447 21 H

27 37 MAD 1BH

-1.25 F*l 448 21 H

28 37 MAD 1BH

-0.84 F*l 449 21 H

31 37 SAD 1BH

-0.98 F*1 450 21 H

32 37 SAD 1BH

-1.20 F*1 451 21 H

33 37 SAD 1BH

-0.88 F*l 452 21 H

34 37 SAD 1BH

-1.24 F*l 453 21 H

36 37 MAD 1BH

-1.27 F*l 454 21 H

1 38 MAD 1BH

-1.25 F*l Page 13 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23,2005 No. SI eg Row Col lindication Location Elev from Elev to Status 455 21 H

2 38 SAD IBH

-1.02 F*1 456 21 H

3 38 MAN IBH

-1.16

-0.97 F*1 457 21 H

5 38 SAD IBH

-1.35 F*1 458 21 H

8 38 MAD IBH

-0.93 F*1 459 21 H

9 38 MAN IBH

-1.22

-1.01 F*1 460 21 H

12 38 SAD IBH

-1.50 F*l 461 21 H

13 38 SAN 1BH

-1.31

-1.07 F*1 462 21 H

23 38 MAD 1BH

-0.91 F*1 463 21 H

24 38 SAD 1BH

-1.18 F*1 464 21 H

26 38 SAD 1BH

-1.03 WF*

465 21 H

27 38 MAD 1BH

-0.99 F*W 466 21 H

30 38 MAD IBH

-1.11 F*1 467 21 H

31 38 SAD IBH

-1.25 F*I 468 21 H

32 38 SAD 1BH

-1.40 F*1 469 21 H

35 38 MAD IBH

-1.26 F*1 470 21 H

37 38 MAD IBH

-1.22 F*1 471 21 H

2 39 SAD 1BH

-1.36 F*1 472 21 H

4 39 MAN 1BH

-1.32

-0.94 F*W 473 21 H

7 39 SAD 1BH

-1.35 F*1 474 21 H

9 39 SAD IBH

-1.24 F*1 475 21 H

12 39 SAN 1BH

-1.11

-1.00 F*1 476 21 H

15 39 SAD 1BH

-0.91 F*1 477 21 H

19 39 SAD 1BH

-1.29 F*1 478 21 H

20 39 SAN 1BH

-1.26

-1.12 F*1 479 21 H

22 39 SAD 1BH

-1.28 F*1 480 21 H

24 39 SAD 1BH

-1.13 F*W 481 21 H

25 39 MAN 1BH

-1.17

-1.09 F*1 482 21 H

26 39 SAD 1BH

-1.22 F*I 483 21 H

29 39 SAN 1BH

-1.02

-0.95 F*W 484 21 H

30 39 MAD 1BH

-1.17 F*1 485 21 H

32 39 MAD 1BH

-1.23 F*W 486 21 H

33 39 SAD IBH

-1.19 WF*

487 21 H

35 39 SAD IBH

-1.13 F*W 488 21 H

36 39 SAD IBH

-1.43 F*W 489 21 H

2 40 SAD IBH

-1.36 F*I 490 21 H

3 40 MAD IBH

-1.26 F*1 491 21 H

6 40 MAD IBH

-1.30 F*W 492 21 H

9 40 SAD 1BH

-1.27 F*W 493 21 H

13 40 MAD IBH

-1.56 F*W 494 21 H

20 40 SAD IBH

-1.00 F*1 495 21 H

21 40 MAD IBH

-1.26 F*W 496 21 H

24 40 MAD IBH

-1.00 F*W 497 21 H

26 40 MAD IBH

-1.28 F*W 498 21 H

29 40 SAD IBH

-1.30 F*W 499 21 H

30 40 SAD IBH

-0.80 F*W 500 21 H

31 40 MAN IBH

-1.20

-1.09 F*1 501 21 H

32 40 SAI 1BH

-1.09

-0.90 F*1 502 21 H

33 40 SAD IBH

-1.20 F*1 503 21 H

37 40 MAD IBH

-1.14 F*W 504 21 H

1 41 SAD 1BH

-1.30 F*W Page 14 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG Lpj Row Col Indication Location Eiev from Elev to Status 505 21 H

2 41 SAD 1BH

-0.93 F*l 506 21 H

3 41 SAD 1BH

-1.31 F*l 507 21 H

4 41 MAN 1BH

-1.34

-0.90 F*l 508 21 H

5 41 MAN 1BH_

-1.10

-1.00 F*1 509 21 H

7 41 MAN 1BH

-1.09

-0.96 F*l 510 21 H

8 41 MAD 1BH

-1.27 F*l 511 21 H

11 41 SAD 1BH

-1.37 F*l 512 21 H

12 41 MAN 1BH

-1.17

-1.06 F*1 513 21 H

14 41 MAN 1BH

-0.84

-0.16 F*l 514 21 H

23 41 SAD 1BH

-0.98 F*l 515 21 H

28 41 SAD 1BH

-1.29 F*l 516 21 H

31 41 SAD 1BH

-1.00 F*l 517 21 H

32 41 SAD 1BH

-0.95 F*l 518 21 H

34 41 SAD 1BH

-1.02 F*l 519 21 H

1 42 SAD 1BH

-1.36 F*l 520 21 H

3 42 MAD 1BH

-1.22 F*l 521 21 H

4 42 SAD 1BH

-1.30 F*l 522 21 H

5 42 MAD 1BH

-0.92 F*l 523 21 H

8 42 MAD 1BH

-1.23 F*l 524 21 H

10 42 SAD 1BH

-1.28 F*l 525 21 H

11 42 SAD 1BH

-1.05 F*l 526 21 H

12 42 MAD 1BH

-1.17 F*l 527 21 H

15 42 MAN 1BH

-1.12

-1.02 F*l 528 21 H

16 42 SAD 1BH

-1.31 F*l 529 21 H

17 42 SAD 1BH

-0.80 F*l 530 21 H

20 42 SAD 1BH

-1.30 F*l 531 21 H

21 42 SAN 1BH

-0.44

-0.25 F*1 532 21 H

24 42 SAD 1BH

-1.25 F*l 533 21 H

25 42 SAD 1BH

-0.85 F*l 534 21 H

28 42 SAD 1BH

-1.05 F*l 535 21 H

36 42 MAD 1BH

-1.37 F*l 536 21 H

5 43 SAN 1BH

-1.25

-1.17 F*1 537 21 H

7 43 MAN 1BH

-1.21

-1.11 F*1 538 21 H

12 43 SAN 1BH

-0.93

-0.88 F*l 539 21 H

21 43 SAD 1BH_

-1.23 F*l 540 21 H

23 43 MAN 1BH

-1.24

-1.06 F*l 541 21 H

24 43 MAN 1BH

-1.50

-0.82 F*l 542 21 H

30 43 SAD 1BH

-0.80 F*l 543 21 H

32 43 SAD 1BH

-1.10 F*1 544 21 H

35 43 SAD 1BH

-1.18 F*l 545 21 H

36 43 MAD 1BH

-1.00 F*1 546 21 H

42 43 SAD 1BH_

-0.99 F*1 547 21 H

1 44 MAD 1BH

-1.32 F*l 548 21 H

3 44 SAD 1BH

-1.30 F*l 549 21 H

4 44 MAD 1BH

-1.25 F*l 550 21 H

6 44 SAD 1BH

-1.30 F*l 551 21 H

8 44 SAD 1BH

-0.90 F*l 552 21 H

12 44 MAD 1BH

-0.95 F*1 553 21 H

13 44 SAD I1BH

-0.93 F*l 554 21 H

21 44 SAD I1BH

-1.30 F*l Page 15 of 48

21 STEAM GENERATOR F*1 TUBES. BOC23, 2005 No. SIG Lea Row Col indication Location Eiev from Elev to Status 555 21 H

22 44 SAD 1BH

-0.90 F*l 556 21 H

25 44 MAD 1BH

-0.99 F*l 557 21 H

29 44 MAD IBH

-0.97 F*l 558 21 H

31 44 MAD 1BH

-1.02 F*l 559 21 H

32 44 MAD 1BH_

-1.00 F*l 560 21 H

1 45 SAD 1BH

-1.36 F*l 561 21 H

3 45 MAN 1BH

-1.37

-0.96 F*l 562 21 H

6 45 SAD 1BH

-1.18 F*1 563 21 H

9 45 MAN 1BH

-1.01

-0.84 F*l 564 21 H

10 45 MAD 1BH

-0.89 F*l 565 21 H

13 45 MAN 1BH

-1.34

-0.75 F*l 566 21 H

14 45 SAN 1BH

-0.84

-0.81 F*1 567 21 H

16 45 SAD 1BH

-1.30 F*l 568 21 H

18 45 MAD 1BH

-1.23 F*l 569 21 H

21 45 MAD 1BH

-1.22 F*1 570 21 H

23 45 SAD 1BH

-1.33 F*1 571 21 H

28 45 MAN IBH

-1.07

-0.96 F*1 572 21 H

32 45 MAD IBH

-1.26 F*l 573 21 H

34 45 SAD IBH

-1.07 F*l 574 21 H

4 46 MAN 1BH

-1.26

-1.15 F*l 575 21 H

5 46 SAD 1BH

-1.35 F*l 576 21 H

6 46 MAD 1BH

-1.55 F*l 577 21 H

7 46 SAD 1BH

-1.43 F*l 578 21 H

8 46 MAN 1BH

-1.27

-1.15 F*l 579 21 H

10 46 MAD 1BH

-1.49 F*l 580 21 H

14 46 MAN 1BH

-1.09

-0.86 F*l 581 21 H

15 46 SAD 1BH

-0.93 F*l 582 21 H

16 46 MAD 1BH

-1.36 F*1 583 21 H

17 46 SAD 1BH

-1.25 F*1 584 21 H

18 46 SAD 1BH

-1.24 F*l 585 21 H

19 46 SAD 1BH

-1.18 F*1 586 21 H

21 46 SAD 1BH _

-1.25 F*l 587 21 H

22 46 MAN 1BH

-0.34

-0.04 F*l 588 21 H

24 46 MAN 1BH

-0.82

-0.07 F*l 589 21 H

26 46 MAD 1BH _

-0.98 F*l 590 21 H

27 46 SAD 1BH

-0.85 F*l 591 21 H

28 46 MAD 1BH

-1.28 F*l 592 21 H

34 46 MAD 1BH

-1.27 F*l 593 21 H

1 47 SAD 1BH

-1.00 F*l 594 21 H

3 47 MAD 1BH _

-1.41 F*l 595 21 H

4 47 MAN 1BH

-1.46

-1.10 F*l 596 21 H

8 47 SAN 1BH

-1.15

-1.05 F*l 597 21 H

9 47 SAD 1BH

-0.75 F*l 598 21 H

11 47 MAD 1BH

-1.18 F*1 599 21 H

12 47 SAN 1BH

-0.89

-0.75 F*l 600 21 H

17 47 SAD 1BH

-0.99 F*l 601 21 H

19 47 MAD 1BH

-1.28 F*1 602 21 H

22 47 MAD 1BH

-1.27 F*l 603 21 H

23 47 MAD 1BH

-1.19 F*l 604 21 H

24 47 MAD I1BH

-1.32 F*1 Page 16 of 48

21 STEAM GENERATOR F*l TUBES. BOC23, 2005 No. SIG Leg Row Col Indication Location Elev from Elev to Status 605 21 H

26 47 SAD 1BH

-1.25 F*l 606 21 H

27 47 SAD 1BH

-1.47 F*l 607 21 H

29 47 MAD 1BH

-0.99 F*1 608 21 H

31 47 SAD 1BH

-1.31 F*l 609 21 H

34 47 SAD IBH

-1.20 F*l 610 21 H

35 47 SAD 1BH

-1.04 F*l 611 21 H

36 47 MAD IBH

-1.10 F*l 612 21 H

37 47 SAD IBH

-1.60 F*1 613 21 H

1 48 SAD 1BH

-1.29 F*l 614 21 H

3 48 SAD 1BH

-1.34 F*l 615 21 H

5 48 SAD 1BH

-1.36 F*l 616 21 H

6 48 SAN 1BH

-1.08

-0.98 F*1 617 21 H

9 48 SAD 1BH

-1.36 F*1 618 21 H

11 48 MAD 1BH

-1.41 F*1 619 21 H

12 48 MAD 1BH

-1.31 F*1 620 21 H

16 48 SAD 1BH

-0.89 F*l 621 21 H

18 48 MAN 1BH

-0.47

-0.25 F*l 622 21 H

20 48 MAD 1BH

-1.24 F*l 623 21 H

22 48 MAD 1BH

-1.15 F*l 624 21 H

23 48 MAD 1BH

-1.31 F*l 625 21 H

25 48 SAN 1BH

-0.98

-0.87 F*l 626 21 H

30 48 MAD 1BH

-1.16 F*l 627 21 H

1 49 MAD 1BH

-0.91 F*l 628 21 H

3 49 SAD 1BH

-1.36 F*l 629 21 H

4 49 MAD 1BH

-1.39 F*l 630 21 H

7 49 MAD 1BH

-1.39 F*l 631 21 H

11 49 MAD 1BH

-1.36 F*l 632 21 H

12 49 MAN 1BH

-0.36

-0.17 F*l 633 21 H

13 49 MAN 1BH

-1.17

-1.09 F*l 634 21 H

23 49 SAD 1BH

-0.88 F*1 635 21 H

24 49 SAD 1BH

-0.87 F*l 636 21 H

28 49 SAD 1BH

-1.33 F*1 637 21 H

29 49 MAD IBH

-1.26 l F*1 638 21 H

31 49 SAD 1BH

-1.26 F*l 639 21 H

36 49 SAD 1BH

-1.26 F*l 640 21 H

2 50 MAN IBH

-1.42

-0.82 F*l 641 21 H

3 50 SAD IBH

-0.90 F*l 642 21 H

-4 50 MAN 1BH

-1.38

-0.97 F*l 643 21 H

5 50 MAN 1BH

-1.31

-0.96 F*l 644 21 H

6 50 SAD 1BH

-1.41 F*l 645 21 H

.7 50 MAN 1BH

-1.04

-0.68 F*l 646 21 H

8 50 MAD 1BH

-0.93 F*1 647 21 H

9 50 MAD 1BH

-1.02 F*1 648 21 H

10 50 MAN 1BH

-1.17

-0.98 F*l 649 21 H

12 50 MAN 1BH

-0.58

-0.28 F*l 650 21 H

18 50 MAD 1BH

-1.21 F*l 651 21 H

19 50 MAD IBH

-0.90 F*l 652 21 H

20 50 SAD 1BH

-1.25 F*1 653 21 H

21 50 SAD 1BH

-1.30 F*1 654 21 H

22 50 SAD 1BH

-1.27 F*1 Page 17 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. S/G Leg Row Col Indication Location Elev from Elev to Status 655 21 H

24 50 MAN IBH

-0.76

-0.18 F*1 656 21 H

25 50 SAD IBH

-1.26 IF*

657 21 H

28 50 SAD 1BH

-1.27 F*l 658 21 H

30 50 MAD IBH

-1.10 F*1 659 21 H

37 50 SAD IBH

-0.90 F*l 660 21 H

1 51

-SAN IBH

-1.27

-1.09 F*1 661 21 H

2 51 SAD 1BH

-1.37 F*l 662 21 H

3 51 SAD 1BH

-1.07 F*l 663 21 H

4 51 MAN 1BH

-1.05

-0.98 F*l 664 21 H

5 51 MAN IBH

-1.12

-0.89 F*l 665 21 H

6 51 MAD IBH

-1.27 FP 666 21 H

8 51 MAN 1BH

-1.33

-0.90 F*l 667 21 H

11 51 SAD IBH

-1.75 F*l 668 21 H

12 51 MAD 1BH

-1.30 F*l 669 21 H

13 51 SAD IBH

-1.41 F*l 670 21 H

14 51 SAN 1BH

-0.43

-0.26 F*1 671 21 H

15 51 SAD IBH

-1.28 F*l 672 21 H

16 51 MAD 1BH

-1.28 F*1 673 21 H

18 51 MAD 1BH

-1.30 F*1 674 21 H

19 51 SAD IBH

-1.21 F*l 675 21 H

21 51 SAD IBH

-1.16 FP 676 21 H

23 51 MAD IBH

-0.88 F*l 677 21 H

26 51 SAD IBH

-1.34 F*l 678 21 H

29 51 MAD 1BH

-1.30 F*l 679 21 H

32 51 MAD IBH

-1.23 F*1 680 21 H

34 51 MAD IBH

-0.84 FP 681 21 H

35 51 SAD IBH

-0.86 F*l 682 21 H

37 51 MAD IBH

-1.31 F*l 683 21 H

38 51 SAD IBH

-1.32 F*l 684 21 H

1 52 SAN 1BH

-1.14

-1.02 Fl 685 21 H

2 52 MAN IBH

-1.38

-0.92 F*l 686 21 H

3 52 MAN 1BH

-1.20

-1.06 F*1 687 21 H

5 52 MAD IBH

-1.38 F*1 688 21 H

7 52 SAD IBH

-1.31 F*l 689 21 H

9 52 SAD 1BH

-1.34 F*1 690 21 H

10 52 SAD 1BH

-1.36 FP 691 21 H

13 52 SAD IBH

-1.65 F*l 692 21 H

15 52 MAD 1BH

-1.31 F*1 693 21 H

16 52 SAD 1BH

-0.88 F*1 694 21 H

17 52 SAD IBH

-0.99 F*l 695 21 H

18 52 SAD IBH

-0.90 FP 696 21 H

19 52 MAD IBH

-1.33 F*l 697 21 H

20 52 MAD 1BH

-0.89 F*1 698 21 H

22 52 SAD IBH

-1.27 F*l 699 21 H

25 52 SAD IBH

-1.36 F*l 700 21 H

30 52 MAD 1BH

-1.34 F*l 701 21 H

33 52 SAD 1BH

-1.25 F*1 702 21 H

36 52 SAD IBH

-1.05 F*1 703 21 H

37 52 SAD 1BH

-1.06 F*l 704 21 H

1 53 MAD I1BH

-1.43 F*l Page 18 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG Leg Row Col Indication Location Elev from Elev to Status 705 21 H

2 53 SAD 1BH

-0.93 F*l 706 21 H

3 53 MAD 1BH

-1.40 F*l 707 21 H

4 53 MAN 1BH

-1.13

-0.90 F*l 708 21 H

6 53 MAD 1BH

-1.04 F*l 709 21 H

7 53 MAN IBH

-0.80

-0.33 F*l 710 21 H

10 53 SAN IBH

-1.10

-0.90 F*1 711 21 H

11 53 SAD 1BH

-1.42 F*l 712 21 H

12 53 SAD IBH

-1.23 F*l 713 21 H

13 53 MAD IBH

-1.33 F*l 714 21 H

14 53 MAD 1BH

-1.50 F*1 715 21 H

16 53 SAD 1BH

-1.00 F*1 716 21 H

18 53 SAD 1BH

-1.10 F*1 717 21 H

20 53 SAD 1BH

-1.30 F*l 718 21 H

21 53 SAD IBH

-0.95 F*l 719 21 H

22 53 SAD 1BH

-0.85 F*l 720 21 H

25 53 MAD IBH

-1.05 F*l 721 21 H

27 53 MAD 1BH

-0.88 F*l 722 21 H

35 53 SAD IBH

-0.84 F*l 723 21 H

1 54 SAN IBH

-1.21

-1.11 F*l 724 21 H

2 54 SAD IBH

-1.48 Fl 725 21 H

3 54 MAD IBH

-1.06 F*l 726 21 H

5 54 SAD IBH

-1.09 F*l 727 21 H

7 54 MAN 1BH

-1.20

-1.11 F*l 728 21 H

10 54 SAD 1BH

-0.92 F*l 729 21 H

13 54 MAD IBH

-1.38 F*l 730 21 H

14 54 SAD IBH

-1.37 F*l 731 21 H

15 54 MAD IBH

-0.94 F*1 732 21 H

17 54 MAD IBH

-1.16 F*l 733 21 H

18 54 SAD IBH

-1.21 F*l 734 21 H

19 54 MAN IBH

-1.25

-1.15 F*l 735 21 H

20 54 SAD IBH

-1.32 Fl 736 21 H

27 54 SAD 1BH

-1.31 F*l 737 21 H

29 54 MAD IBH

-1.32 F*l 738 21 H

34 54 SAD 1BH

-1.29 F*l 739 21 H

3 55 SAD 1BH

-1.06 F*l 740 21 H

7 55 SAD IBH

-1.58 F*1 741 21 H

9 55 MAD IBH

-0.94 F*l 742 21 H

12 55 SAD IBH

-1.40 F*l 743 21 H

15 55 MAD IBH

-1.33 F*1 744 21 H

17 55 SAD 1BH

-1.23 F*1 745 21 H

18 55 MAD 1BH

-0.85 F*l 746 21 H

20 55 MAD 1BH

-1.00 F*l 747 21 H

22 55 SAD 1BH

-1.23 F*l 748 21 H

23 55 MAD 1BH

-1.19 F*l 749 21 H

24 55 MAD 1BH

-1.01 F*l 750 21 H

25 55 SAD 1BH

-1.17 F*l 751 21 H

27 55 SAD 1BH

-1.26 F*l 752 21 H

29 55 SAD 1BH

-1.30 F*1 753 21 H

31 55 SAD 1BH

-0.85 F*l 754 21 H

33 55 SAD IBH

-0.90 F*l Page 19 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG Lek Row Col Indication Location Elev from Elev to Status 755 21 H

1 56 MAD 1BH

-1.00 F*1 756 21 H

2 56 MAN 1BH

-0.48

-0.22 F*1 757 21 H

3 56 MAD 1BH

-0.99 F*1 758 21 H

4 56 MAD 1BH

-1.54 F*1 759 21 H

6 56 MAN 1BH

-1.20

-1.08 F*1 760 21 H

9 56 MAD 1BH

-1.27 F*1 761 21 H

10 56 MAN 1BH

-1.28

-1.04 F*1 762 21 H

13 56 SAD -

1BH

-0.85 F*1 763 21 H

14 56 SAD 1BH

-1.46 F*1 764 21 H

18 56 SAD 1BH

-1.35 F*1 765 21 H

19 56 SAD IBH

-0.99 F*1 766 21 H

20 56 SAD 1BH

-1.28 F*1 767 21 H

22 56 SAD 1BH

-1.35 F*1 768 21 H

27 56 SAD 1BH

-0.88 F*1 769 21 H

29 56 SAD 1BH

-1.31 F*1 770 21 H

34 56 MAD 1BH

-0.85 F*1 771 21 H

43 56 SAD IBH

-1.05 F*1 772 21 H

2 57 MAD 1BH

-1.43 F*1 773 21 H

3 57 MAD 1BH 1

-1.29 F*1 774 21 H

4 57 SAD 1BH

-1.28 F*1 775 21 H

5 57 SAD 1BH

-1.50 F*1 776 21 H

6 57 MAN 1BH 1

-1.28

-1.02 F*1 777 21 H

7 57 MAD 1BH

-1.36 F*1 778 21 H

8 57 MAN 1BH

-0.72

-0.07 F*1 779 21 H

12 57 MAD 1BH

-1.38 F*1 780 21 H

14 57 SAD 1BH

-1.30 F*1 781 21 H

15 57 MAD 1BH

-1.37 F*1 782 21 H

17 57 SAD 1BH

-1.30 F*1 783 21 H

18 57 MAD 1BH

-1.30 F*1 784 21 H

19 57 SAD 1BH

-1.28 F*1 785 21 H

21 57 MAD 1BH

-0.87 F*1 786 21 lH 25 57 SAD 1BH

-1.31 F*1 787 21 H

27 57 SAD IBH

-1.11 F*1 788 21 H

2 58 SAD 1BH1-

-1.39 F*1 789 21 H

3 58 SAD 1BH

-1.00 F*1 790 21 H

4 58 MAD 1BH

-1.41 F*1 791 21 H

11 58 SAD IBH

-1.20 F*1 792 21 H

14 58 MAN 1BH

-1.15

-1.08 F*1 793 21 H

16 58 MAN 1BH

-1.28

-0.91 F*1 794 21 H

17 58 SAD 1BH

-1.28 F*1 795 21 H

18 58 SAD 1BH

-1.32 F*1 796 21 H

21 58 MAN 1BH

-1.20

-1.05 F*1 797 21 H

23 58 SAD 1BH

-1.32 F*1 798 21 H

31 58 MAD IBH

-1.40 F*1 799 21 H

2 59 SAD 1BH

-1.00 F*1 800 21 H

3 59 SAD 1BH

-1.29 F*1 801 21 H

6 59 MAD 1BH

-1.38 F*1 802 21 H

8 59 MAN 1BH

-1.43

-1.02 F*l 803 21 H

9 59 MAD 1BH

-1.39 F*l 804 21 H

10 59 MAN IBH

-1.22

-1.05 F*1 Page 20 of 48

21 STEAM GENERATOR F*l TUBES, BOC23.12005 No. S/G lLeg Row Col Indication Location Elev from Elev to Status 805 21 H

12 59 MAD 71BH1

-1.44 l

I F*l 806 21 H

13 59 MAN 1BH

-1.21

-0.96 F*l 807 21 H

14 59 MAN IBH

-1.39

-1.25 F*l 808 21 H

17 59 SAD 1BH

-1.32 F*l 809 21 H

19 59 MAD 1BH

-1.26 F*l 810 21 H

21 59 SAD 1BH

-1.28 F*l 811 21 H

26 59 SAD 1BH

-1.23 F*l 812 21 H

28 59 SAD 1BH

-1.20 F*1 813 21 H

29 59 SAD 1BH

-1.05 F*l 814 21 H

31 59 MAD 1BH

-1.34 F*l 815 21 H

33 59 SAD 1BH

-1.39 F*l 816 21 H

3 60 MAN 1BH

-1.24

-1.12 F*l 817 21 H

7 60 SAN IBH

-1.19

-0.93 F*l 818 21 H

9 60 MAD 1BH

-1.23 F*l 819 21 H

14 60 MAN 1BH

-1.21

-0.97 F*1 820 21 H

16 60 MAN IBH

-1.02

-0.93 F*l 821 21 H

17 60 MAD 1BH

-1.34 F*l 822 21 H

18 60 SAD 1BH

-1.29 F*1 823 21 H

19 60 SAD 1BH

-1.30 F*l 824 21 H

23 60 MAD 1BH

-1.29 F*1 825 21 H

24 60 SAD 1BH

-0.93 F*l 826 21 H

25 60 MAD 1BH

-0.98 F*l 827 21 H

29 60 MAD 1BH

-1.27 F*1 828 21 H

36 60 SAD 1BH

-1.30 F*l 829 21 H

37 60 SAD 1BH

-1.26 F*l 830 21 H

-3 61 MAN 1BH

-1.32

-1.20 F*1 831 21 H

4 61 SAD 1BH

-1.26 F*1 832 21 H

5 61 MAN 1BH

-1.29

-1.14 F*1 833 21 H

6 61 MAD IBH

-1.95 F*l 834 21 H

8 61 SAD 1BH

-0.99 F*l 835 21 H

10 61 MAN 1BH

-1.13

-1.01 F*l 836 21 H

13 61 MAN 1BH 1

-0.67

-0.19 F*l 837 21 H

14 61 MAD 1BH

-1.00 F*l 838 21 H

17 61 MAN 1BH

-1.21

-1.08 F*l 839 21 H

18 61 SAD 1BH

-1.00 F*l 840 21 H

19 61 SAD 1BH

-1.32 F*l 841 21 H

23 61 SAD 1BH

-1.35 F*l 842 21 H

24 61 SAD 1BH

-1.32 F*1 843 21 H

27 61 MAD 1BH

-1.08 F*l 844 21 H

31 61 SAD 1BH

-3.50 F*l 845 21 H

33 61 MAD 1BH

-1.42 Fl 846 21 H

34 61 MAD 1BH

-1.30 F*l 847 21 H

37 61 SAD IBH

-1.33 F*1 848 21 H

1 62 SAD 1BH

-1.41 F*l 849 21 H

2 62 MAN 1BH I -1.21

-1.13 F*l 850 21 H

3 62 SAD 1BH

-1.36

__IF*1 851 21 H

5 62 MAN IBH

-1.19

-0.98 F*l 852 21 H

6 62 SAD 1BH

-1.47 F*l 853 21 H

8 62 MAN 1BH

-1.24

-1.17 F*l 854 21 H

12 62 SAN 1BH

-1.17

-1.11 F*

Page 21 of 48

21 STEAM GENERATOR Fl TUBES, BOC23, 2005 No. SIG Leg Row Col Indication Location Elev from Elev to Status 855 21 H

13 62 MAD 1BH

-1.34 F*l 856 21 H

14 62 MAN 1BH

-1.20

-0.93 F*l 857 21 H

15 62 MAD 1BH

-1.00 F*1 858 21 H

17 62 MAD 1BH

-1.42 F*l 859 21 H

21 62 SAD 1BH

-1.10 F*l 860 21 H

27 62 MAD 1BH

-0.83 F*l 861 21 H

35 62 MAD 1BH

-1.35 F*l 862 21 H

36 62 SAD 1BH

-1.35 F*1 863 21 H

37 62 SAD 1BH

-0.90 F*l 864 21 H

38 62 SAD 1BH

-1.32 F*l 865 21 H

7 63 SAD 1BH

-1.40 F*1 866 21 H

9 63 SAD 1BH

-1.34 F*l 867 21 H

11 63 SAD 1BH

-1.39 F*1 868 21 H

12 63 SAD 1BH

-1.00 F*l 869 21 H

15 63 SAD 1BH

-1.21 F*l 870 21 H

16 63 SAD 1BH

-1.33 F*l 871 21 H

18 63 SAD 1BH

-0.89 F*1 872 21 H

19 63 MAN 1BH

-0.70

-0.17 F*1 873 21 H

21 63 SAD 1BH

-1.01 F*l 874 21 H

23 63 SAD l1BH

-1.03 F*l 875 21 H

25 63 MAD 1BH

-1.30 F*l 876 21 H

27 63 SAD 1BH

-1.07 F*l 877 21 H

28 63 MAD 1BH

-1.30 F*l 878 21 H

34 63 MAN 1BH

-0.65

-0.20 F*l 879 21 H

36 63 SAD IBH

-0.89 F*l 880 21 H

37 63 MAD 1BH

-1.38 F*l 881 21 H

1 64 SAD 1BH

-1.35 F*l 882 21 H

3 64 SAN 1BH

-1.36

-1.28 F*l 883 21 H

4 64 MAN 1BH

-1.31

-1.22 F*l 884 21 H

5 64 MAN 1BH

-1.72

-1.12 F*l 885 21 H

6 64 MAN

_1BH

-1.20

-1.09 F*1 886 21 H

7 64 MAN lBH

-1.27

-1.11 F*1 887 21 H

10 64 MAD 1BH

-1.28 F*1 888 21 H

11 64 MAD 1BH

-1.59 F*1 889 21 H

12 64 MAN 1BH

-1.03

-0.95 F*l 890 21 H

14 64 MAN 1BH

-1.12

-1.01 F*l 891 21 H

15 64 SAD 1BH

-1.25 F*l 892 21 H

19 64 MAD 1BH

-1.38 F*l 893 21 H

22 64 SAD 1BH

-1.35 F*l 894 21 H

29 64 SAD 1BH

-0.80 F*l 895 21 H

34 64 MAD 1BH

-1.22 F*1 896 21 H

35 64 SAD 1BH

-1.28 F*l 897 21 H

37 64 SAD 1BH

-1.34 F*l 898 21 H

1 65 MAD 1BH

-1.251 F*l 899 21 H

2 65 SAD 1BH

-1.42 F*l 900 21 H

4 65 SAN 1BH

-0.36

-0.23 F*l 901 21 H

8 65 SAN 1BH

-1.24

-1.13 F*l 902 21 H

10 65 MAD 1BH

-1.24 F*l 903 21 H

13 65 MAN 1BH

-0.82

-0.28 F*l 904 21 H

14 65 SAD I1BH

-1.19 F*l Page 22 of 48

21 STEAM GENERATOR F*l TUBES, BOC23, 2005 l

No. SIG Leg Row Col Indication Location Elev from Elev to Status 905 21 H

15 65 SAD 1BH

-1.02 F*l 906 21 H

17 65 MAD IBH

-1.33 F*l 907 21 H

18 65 SAD 1BH

-1.36 F*l 908 21 H

20 65 SAD 1BH

-1.00 F*1 909 21 H

25 65 SAD 1BH

-0.79 F*l 910 21 H

40 65 MAD 1BH

-1.32 F*l 911 21 H

3 66 MAD 1BH

-1.30 F*l 912 21 H

5 66 MAN 1BH

-1.28

-1.16 F*l 913 21 H

6 66 SAD 1BH

-1.22 F*1 914 21 H

7 66 SAD IBH

-1.27 F*1 915 21 H

8 66 MAD IBH

-1.02 F*l 916 21 H

12 66 MAD IBH

-1.33 F*l 917 21 H

14 66 SAD IBH

-1.29 F*l 918 21 H

15 66 MAD IBH

-1.41 F*l 919 21 H

16 66 SAN 1BH

-1.93

-1.93 F*l 920 21 H

18 66 SAD IBH

-1.36 F*l 921 21 H

19 66 SAD IBH

-0.82 F*l 922 21 H

21 66 SAD 1BH

-1.24 F*l 923 21 H

22 66 SAD IBH

-1.23 F*l 924 21 H

24 66 MAD 1BH

-1.18 F*l 925 21 H

25 66 SAD 1BH

-1.26 F*l 926 21 H

35 66 SAD 1BH

-1.35 F*l 927 21 H

1 67 MAD 1BH

-1.31 F*l 928 21 H

2 67 SAD 1BH

-1.42 F*l 929 21 H

3 67 MAD 1BH

-1.36 F*l 930 21 H

4 67 SAD IBH

-1.17 F*l 931 21 H

5 67 MAD IBH

-1.35 F*l 932 21 H

6 67 SAD IBH

-1.33 F*l 933 21 H

8 67 SAD IBH

-0.86 F*l 934 21 H

11 67 SAD IBH

-1.34 F*l 935 21 H

12 67 MAD IBH

-1.36 F*l 936 21 H

16 67 SAN 1BH

-3.87

-3.65 F*l 937 21 H

18 67 SAD 1BH

-1.00 F*l 938 21 H

19 67 SAD 1BH

-0.79 F*l 939 21 H

20 67 SAD 1BH

-0.92 F*l 940 21 H

21 67 MAD IBH

-1.30 F*l 941 21 H

24 67 MAN 1BH

-1.25

-1.09 F*1 942 21 H

25 67 SAN IBH

-3.90

-3.69 F*l 943 21 H

26 67 SAD IBH

-1.21 F*l 944 21 H

30 67 MAD IBH

-1.25 F*l 945 21 H

34 67 MAD IBH

-1.41 F*l 946 21 H

2 68 MAD IBH

-0.93 F*1 947 21 H

7 68 MAN IBH

-1.41

-1.12 F*1 948 21 H

12 68 MAN IBH

-0.73

-0.26 F*l 949 21 H

13 68 MAD IBH

-1.39 F*l 950 21 H

14 68 MAD 1BH

-1.35 F*l 951 21 H

15 68 MAD IBH

-1.44 F*l 952 21 H

17 68 MAD 1BH

-1.25 F*l 953 21 H

19 68 SAD 1BH

-0.85 F*l 954 21 H

20 68 SAD 1BH

-0.85 F1l Page 23 of 48

21 STEAM GENERATOR Fl TUBES. BOC23.,2005 No. SIG L-Row Col Indication Location Elev from Elev to Status 955 21 H

37 68 MAD IBH

-1.05 F*1 956 21 H

1 69 SAD 1BH

-1.30 F*1 957 21 H

4 69 MAD IBH

-1.42 F*1 958 21 H

5 69 SAD 1BH

-1.35 F*l 959 21 H

6 69 SAD IBH

-1.34 F*l 960 21 H

8 69 SAD 1BH

-1.40 F*l 961 21 H

11 69 SAN IBH

-1.14

-1.05 F*l 962 21 H

12 69 MAD IBH

-1.33 F*1 963 21 H

13 69 SAD 1BH

-1.34 F*1 964 21 H

14 69 SAD IBH

-1.34 F*l 965 21 H

15 69 MAD 1BH

-1.47 F*l 966 21 H

16 69 SAD 1BH

-1.35 F*l 967 21 H

17 69 SAD IBH

-1.30 F*l 968 21 H

20 69 MAD 1BH

-1.41 F*l 969 21 H

23 69 SAD 1BH

-1.00 F*l 970 21 H

25 69 SAD 1BH

-1.42 F*l 971 21 H

26 69 SAD 1BH

-1.41 F*l 972 21 H

33 69 SAD IBH

-1.48 F*l 973 21 H

35 69 SAD 1BH

-1.32 F*l 974 21 H

2 70 SAD IBH

-1.23 F*1 975 21 H

4 70 SAD 1BH

-1.42 F*l 976 21 H

5 70 MAN 1BH

-1.21

-1.09 F*l 977 21 H

6 70 SAD 1BH

-1.41 F*1 978 21 H

7 70 SAD 1BH

-0.86 F*1 979 21 H

9 70 MAD 1BH

-1.20 F*l 980 21 H

11 70 MAD 1BH

-0.87 F*1 981 21 H

13 70 MAD 1BH

-1.40 F*l 982 21 H

16 70 MAD 1BH

-1.40 F*1 983 21 H

17 70 MAN 1BH

-0.58

-0.19 F*l 984 21 H

22 70 SAD IBH

-1.05 F*l 985 21 H

25 70 SAD 1BH

-1.49 F*l 986 21 H

30 70 SAN IBH

-1.04

-0.87 F*l 987 21 H

38 70 MAD 1BH

-1.07 F*l 988 21 H

2 71 MAD 1BH

-0.92 F*1 989 21 H

4 71 MAD IBH

-0.96 F*l 990 21 H

5 71 MAD IBH

-1.41 F*l 991 21 H

6 71 MAD 1BH

-1.36 F*l 992 21 H

7 71 MAD 1BH

-1.55 F*l 993 21 H

8 71 MAD 1BH

-1.36 F*l 994 21 H

9 71 SAD 1BH

-1.46 F*l 995 21 H

12 71 SAD 1BH

-1.28 F*l 996 21 H

16 71 SAD 1BH

-0.87 F*l 997 21 H

17 71 MAD 1BH

-1.34 F*1 998 21 H

20 71 SAD 1BH

-1.07 F*l 999 21 H

21 71 MAD 1BH

-1.42 F*l 1000 21 H

22 71 MAD IBH

-0.86 F*l 1001 21 H

29 71 SAD 1BH

-1.02 F*l 1002 21 H

30 71 SAD 1BH

-1.30 F*l 1003 21 H

31 71 SAD IBH

-1.37 F*1 1004 21 H

34 71 MAN 1BH

-0.74

-0.14 F*1 Page 24 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG Leg Row Col Indication Location Elev from Elev to Status 1005 21 H

2 72 MAD 1BH

-1.37 F*1 1006 21 H

3 72 SAD 1BH

-1.00 F*1 1007 21 H

4 72 SAD 1BH

-1.00 F*1 1008 21 H

5 72 SAD 1BH

-1.41 F*1 1009 21 H

6 72 SAD 1BH

-1.30 F*1 1010 21 H

8 72 MAN 1BH

-1.08

-0.98 F*1 1011 21 H

11 72 MAN IBH

-1.23

-1.14 F*1 1012 21 H

12 72 SAD 1BH

-1.46 F*1 1013 21 H

15 72 SAD 1BH

-1.29 F*1 1014 21 H

16 72 SAD 1BH

-1.42 F*1 1015 21 H

17 72 SAD 1BH

-1.39 F*1 1016 21 H

18 72 MAD 1BH

-1.48 F*1 1017 21 H

23 72 SAD 1BH

-1.24 F*1 1018 21 H

35 72 MAD 1BH

-1.01 F*1 1019 21 H

36 72 MAD 1BH

-1.46 F*1 1020 21 H

38 72 SAD IBH

-1.31 F*1 1021 21 H

2 73 SAD 1BH

-0.95 F*1 1022 21 H

3 73 MAN 1BH

-1.25

-1.12 F*1 1023 21 H

5 73 MAN 1BH

-1.16

-1.06 F*1 1024 21 H

12 73 MAD 1BH

-0.89 F*1 1025 21 H

15 73 SAD 1BH

-0.99 F*1 1026 21 H

16 73 MAD 1BH

-0.86 F*1 1027 21 H

17 73 MAD 1BH

-0.88 F*1 1028 21 H

18 73 MAD 1BH

-1.45 F*1 1029 21 H 23 73 SAD 1BH

-0.82 F*l 1030 21 H

25 73 SAD 1BH

-1.09 F*l 1031 21 H

1 74 SAD 1BH

-1.41 F*l 1032 21 H

2 74 SAD 1BH

-1.35 F*l 1033 21 H

3 74 SAN 1BH

-1.45

-0.98 F*l 1034 21 H

4 74 MAD 1BH

-1.43 F*1 1035 21 H

6 74 SAD 1BH

-1.32 F*1 1036 21 H

7 74 MAD 1BH

-1.34 F*l 1037 21 H

11 74 MAN 1BH

-1.31

-1.04 F*1 1038 21 H

13 74 SAD 1BH

-1.38 F*l 1039 21 H

15 74 SAD IBH

-1.37 F*l 1040 21 H

19 74 SAD 1BH

-1.41 F*l 1041 21 H 25 74 SAD 1BH

-0.85 F*l 1042 21 H

28 74 SAD 1BH

-0.94 F*l 1043 21 H

29 74 SAD 1BH

-1.49 F*l 1044 21 H

34 74 SAD 1BH

-1.01 F*1 1045 21 H

37 74 SAD 1BH

-1.26 F*l 1046 21 H

4 75 SAD 1BH

-1.34 F*l 1047 21 H

5 75 MAN 1BH

-1.36

-1.26 F*l 1048 21 H

8 75 MAD 1BH

-0.90 F*l 1049 21 H

11 75 SAD 1BH

-1.36 F*l 1050 21 H

17 75 MAD 1BH

-1.40 F*l 1051 21 H

21 75 SAD 1BH

-1.47 F*l 1052 21 H 22 75 SAD 1BH

-1.46 F*l 1053 21 H 35 75 MAD 1BH

-1.04 F*l 1054 21 H

2 76 SAD 1BH

-1.38 F*l Page 25 of 48

21 STEAM GENERATOR F*l TUBES, BOC23,' 2005 No. S/G Leg Row Col Indication Location Elev from Elev to Status 1055 21 H

3 76 SAD IBH

-1.37 F*l 1056 21 H

5 76 SAD IBH

-1.31 F*l 1057 21 H

7 76 MAD 1BH

-1.41 F*l 1058 21 H

9 76 MAD 1BH

-1.39 F*l 1059 21 H

10 76 MAD 1BH

-1.30 F*l 1060 21 H

11 76 SAD IBH

-1.38 F*l 1061 21 H

18 76 SAD IBH

-0.87 F*1 1062 21 H

24 76 SAD 1BH

-1.33 F*l 1063 21 H

28 76 SAD IBH

-1.31 F*l 1064 21 H

3 77 MAD 1BH

-0.93 F*l 1065 21 H

4 77 SAD 1BH

-1.33 F*1 1066 21 H

5 77 SAD 1BH

-1.77 F*l 1067 21 H

6 77 MAD 1BH

-1.40 F*l 1068 21 H

7 77 SAN 1BH

-1.20

-1.07 F*1 1069 21 H

10 77 MAD 1BH

-1.33 F*l 1070 21 H

11 77 SAD 1BH

-1.44 F*1 1071 21 H

16 77 SAD 1BH

-0.87 F*l 1072 21 H

17 77 SAN 1BH

-0.71

-0.32 F*l 1073 21 H

20 77 SAD 1BH

-1.41 F*l 1074 21 H

22 77 SAD 1BH

-1.16 F*l 1075 21 H

3 78 MAD 1BH

-1.53 F*l 1076 21 H

4 78 MAD 1BH

-1.08 F*1 1077 21 H

5 78 MAD IBH

-1.44 F*l 1078 21 H

7 78 MAN 1BH

-1.39

-1.25 F*l 1079 21 H

9 78 MAD 1BH

-1.39 F*l 1080 21 H

11 78 MAN 1BH

-1.23

-1.13 F*l 1081 21 H

2 79 MAD IBH

-1.45 F*l 1082 21 H

4 79 SAD 1BH

-1.37 F*l 1083 21 H

5 79 MAD IBH

-1.37 F*l 1084 21 H

6 79 MAD 1BH

-1.00 F*l 1085 21 H

7 79 MAN 1BH

-1.27

-1.18 F*l 1086 21 H

8 79 SAD 1BH

-0.93 F*l 1087 21 H

10 79 SAD 1BH

-1.39 F*l 1088 21 H

11 79 SAD 1BH

-1.47 F*l 1089 21 H

12 79 SAD 1BH

-1.42 F*l 1090 21 H

17 79 MAN 1BH

-0.67

-0.10 F*l 1091 21 H

19 79 MAD IBH

-1.52 F*l 1092 21 H

21 79 SAD IBH

-1.29 F*1F 1093 21 H

1 80 MAD 1BH

-1.00 F*1 1094 21 H

3 80 SAD 1BH

-1.31 Fl 1095 21 H

5 80 SAD 1BH

-1.56 F*l 1096 21 H

8 80 SAD 1BH

-1.31 F*l 1097 21 H

9 80 SAD 1BH

-1.38 F*l 1098 21 H

11 80 MAD IBH

-1.37 F*1 1099 21 H

12 80 SAD 1BH

-1.26 F*l 1100 21 H

28 80 SAN 1BH

-1.25

-1.11 F*l 1101 21 H

1 81 MAD 1BH

-0.90 F*l 1102 21 H

8 81 SAD 1BH

-1.20 F*1 1103 21 H

11 81 SAD 1BH

-1.45 F*l 1104 21 H

19 81 SAD IBH

-1.32 F*l Page 26 of 48

21 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG Leg RowlCollIndication Location Elev from Elev tolstatus 1105 21 H

21 81 SAD 71BH I -1.30 l F*l 1106 21 H

27 81 SAD I1BH1 I -1.02 1

l F*l 1107 21 H

1 82 SAD 71BH1

-1.40 1

l F*l 1108 21 H

7 82 SAD 1BH l -1.52 1

I F*1 1109 21 H

9 82 MAD IBH

-0.88 F*l 1110 21 H

11 82 SAD 1BH

-1.36 F*1 1111 21 H

12 82 SAD 1BH

-1.44 F*1 1112 21 H

26 82 SAD IBH

-1.37 F*1 1113 21 H

2 83 SAD 1BH

-0.94 F*l 1114 21 H

4 83 SAD 1BH

-1.30 F*l 1115 21 H

9 83 MAD 1BH

-1.52 F*l 1116 21 H

10 83 SAD 1BH

-0.95 F*l 1117 21 H

11 83 SAD 1BH

-1.00 F*l 1118 21 H

4 84 SAD 1BH

-1.37 F*l 1119 21 H

5 84 MAD

1BH

-1.00 F*l 1120 21 H

9 84 SAD 1BH

-1.42 F*l 1121 21 H

10 84 MAD IBH

-1.02 F*l 1122 21 H

11 84 MAD IBH

-1.45 F*l 1123 21 H

12 84 SAI 1BH

-0.42

-0.35 F*l 1124 21 H

7 85 SAD 1BH

-1.49 F*l 1125 21 H

9 85 MAD IBH

-1.35 F*l 1126 21 H

11 85 SAD 1BH

-1.26 F*l 1127 21 H

13 85 MAD 1BH

-1.39 F*l 1128 21 H

18 86 SAN IBH

-1.26

-1.16 F*l 1129 21 H

3 87 SAD 1BH

-1.31 F*l 1130 21 H

9 89 SAD 1BH

-1.23 F*1 1131 21 H

10 89 MAD 1BH

-1.25 F*1 21 STEAM GENERATOR F*2 TUBES, BOC23, 2005 No. SIG Leg Row Col Indication Location Elev from Elev to Status 1 21 H

12 11 SAN 2BH

-1.44

-1.18 F*2 2

21 H

6 14 SAN 2BH

-0.89

-0.82 F*2 3

21 H

11 14 SAN 2BH

-0.84

-0.71 F*2 4

21 H

4 17 SAD 2BH

-3.11 F*2 5

21 H

14 17 SAN 2BH

-1.14

-1.08 F*2 6

21 H

18 17 SAN 2BH

-0.88

-0.72 F*2 7

21 H

4 18 SAN 2BH

-0.78

-0.56 F*2 8

21 H

19 18 MAN 2BH

-0.89

-0.75 F*2 9

21 H

27 18 SAN 2BH

-1.01

-0.90 F*2 10 21 H

33 18 SAN 2BH

-2.05

-1.98 F*2 11 21 H

6 19 SAN 2BH

-0.81

-0.72 F*2 12 21 H

9 19 SAN 2BH

-0.81

-0.67 F*2 13 21 H

19 19 MAN 2BH

-0.90

-0.62 F*2 14 21 H

25 19 SAN 2BH

-0.87

-0.77 F*2 15 21 H

27 20 MAN 2BH

-0.84

-0.70 F*2 16 21 H

34 20 MAN 2BH

-0.85

-0.65 F*2 17 21 H

2 21 SAN 2BH

-1.00

-0.81 F*2 18 21 H

9 21 SAN 2BH

-1.04

-0.62 F*2 19 21 H

16 22 SAN 2BH

-0.98

-0.58 F*2 20 21 H

16 23 SAN 2BH

-0.84

-0.76 F*2 Page 27 of 48

21 STEAM GENERATOR F*2 TUBES. BOC23. 2005 No. S/G Leg Row Col Indication Location Elev from Elev to Status 21 21 H

23 23 SAN 2BH

-0.79

-0.67 F*2 22 21 H

3 24 SAN 2BH

-0.89

-0.76 F*2 23 21 H

5 24 SAN 2BH

-0.70

-0.61 F*2 24 21 H

6 24 SAN 2BH

-0.86

-0.77 F*2 25 21 H

14 25 MAN 2BH

-0.86

-0.68 F*2 26 21 H

23 25 SAN 2BH

-0.70

-0.58 F*2 27 21 H

4 26 SAN 2BH

-1.09

-0.71 F*2 28 21 H

18 26 SAN 2BH

-0.91

-0.74 F*2 29 21 H

12 27 SAN 2BH

-0.76

-0.64 F*2 30 21 H

28 27 SAN 2BH

-1.05

-0.52 F*2 31 21 H

9 28 MAN 2BH

-2.13

-1.92 F*2 32 21 _H 18 28 SAN 2BH

-0.82

-0.71 F*2 33 21 H

23 28 MAN 2BH

-0.78

-0.66 F*2 34 21 H

38 28 SAN 2BH

-0.90

-0.72 F*2 35 21 H

4 29 MAN 2BH

-1.02

-0.54 F*2 36 21 H

13 29 SAN 2BH

-3.19

-3.12 F*2 37 21 H

9 30 SAN 2BH

-0.73

-0.27 F*2 38 21 H

18 30 SAN 2BH

-1.01

-0.86 F*2 39 21 H

21 30 SAN 2BH3-

-0.75

-0.62 F*2 40 21 H

1 32 SAN 2BH

-0.86

-0.58 F*2 41 21 H

3 33 MAN 2BH

-0.90

-0.79 F*2 42 21 H

22 33 SAN 2BH

-0.84

-0.63 F*2 43 21 H

3 34 SAN 2BH

-0.84

-0.76 F*2 44 21 H

5 36 MAN 2BH

-2.65

-1.92 F*2 45 21 H

7 36 SAN 2BH

-0.87

-0.72 F*2 46 21 H

8 36 SAN 2BH

-0.86

-0.77 F*2 47 21 H

14 36 MAD 2BH

-3.00 F*2 48 21 H

4 38 SAN 2BH

-0.85

-0.80 F*2 49 21 H

21 39 SAN 2BH

-0.91

-0.77 F*2 50 21 H

10 40 SAN 2BH

-0.75

-0.63 F*2 51 21 H

12 40 SAN 2BH

-0.75

-0.60 F*2 52 21 H

14 40 SAN 2BH

-2.79

-1.27 F*2 53 21 H

33 41 SAN 2BH

-0.74

-0.69 F*2 54 21 H

2 42 SAN 2BH

-0.91

-0.85 F*2 55 21 H

9 42 MAN 2BH

-0.80

-0.70 F*2 56 21 H

8 43 SAN 2BH

-0.81

-0.69 F*2 57 21 H

9 43 SAN 2BH

-0.81

-0.71 F*2 58 21 H

9 44 SAN 2BH

-0.80

-0.59 F*2 59 21 H

10 44 SAD 2BH

-2.90 F*2 60 21 H

19 44 SAN 2BH

-1.86

-1.71 F*2 61 21 H

24 44 SAN 2BH

-0.91

-0.81 F*2 62 21 H

30 45 SAN 2BH3-

-1.05

-0.99 F*2 63 21 H

3 46 SAN 2BH

-0.74

-0.67 F*2 64 21 H

9 46 SAN 2BH

-1.99

-1.26 F*2 65 21 H

12 46 MAN 2BH

-2.60

-1.82 F*2 66 21 H

20 46 SAD 2BH

-1.50 F*2 67 21 H

6 47 SAN 2BH

-2.85

-2.03 F*2 68 21 H

13 47 SAN 2BH

-0.86

-0.74 F*2 69 21 H

14 47 SAN 2BH

-2.67

-1.48 F*2 70 21 H

18 47 MAD 2BH

-3.12 F*2 Page 28 of 48

21 STEAM GENERATOR F*2 TUBES, BOC23, 2005 No. SIG L Row Col Indication Location Elev from Elev to Status 71 21 H

4 48 SAN 2BH

-0.70

-0.60 F*2 72 21 H

10 48 MAN 2BH1 l -2.96

-2.88 F*2 73 21 H

14 49 SAN 2BH

-0.77

-0.62 F*2 74 21 H

15 49 MAD 2BH

-3.35 F*2 75 21 H

14 50 SAN 2BH

-2.17

-1.61 F*2 76 21 H

17 50 SAD 2BH

-3.58 F*2 77 21 H

4 52 SAN 2BH

-0.78

-0.72 F*2 78 21 H

11 52 SAN 2BH

-0.85

-0.76 F*2 79 21 H

12 52 SAD 2BH

-1.81 F*2 80 21 H

35 52 SAN 2BH

-0.88

-0.81 F*2 81 21 H

21 54 SAN 2BH

-0.81

-0.78 F*2 82 21 H

2 55 SAD 2BH

-3.01 F*2 83 21 H

10 55 SAN 2BH

-0.82

-0.67 F*2 84 21 H

11 55 MAN 2BH

-0.59

-0.54 F*2 85 21 H

7 56 SAN 2BH

-0.58

-0.47 F*2 86 21 H

11 56 SAN 2BH

-0.72

-0.65 F*2 87 21 H

1 57 SAN 2BH

-0.87

-0.76 F*2 88 21 H

13 57 MAN 2BH

-0.88

-0.81 F*2 89 21 H

23 57 SAN 2BH

-0.76

-0.63 F*2 90 21 H

5 58 SAN 2BH

-0.82

-0.72 F*2 91 21 H

1 59 SAN 2BH

-0.91

-0.63 F*2 92 21 H

11 59 MAN 2BH

-0.87

-0.74 F*2 93 21 H

2 60 MAN 2BH

-0.73

-0.38 F*2 94 21 H

4 60 SAN 2BH

-0.71

-0.48 F*2 95 21 H

5 60 MAN 2BH

-0.86

-0.65 F*2 96 21 H

6 60 SAD 2BH

-1.11 F*2 97 21 H

2 61 SAN 2BH

-1.01

-0.53 F*2 98 21 H

9 61 SAN 2BH

-0.89

-0.74 F*2 99 21 H

4 62 SAN 2BH

-0.85

-0.48 F*2 100 21 H

10 62 SAN 2BH

-0.85

-0.79 F*2 101 21 H

25 62 MAN 2BH

-0.62

-0.09 F*2 102 21 H

3 63 SAN 2BH

-0.86

-0.53 F*2 103 21 H

5 63 SAN 2BH

-0.89

-0.78 F*2 104 21 H

8 63 MAN 2BH

-1.10

-0.81 F*2 105 21 H

14 63 MAN 2BH

-0.78

-0.63 F*2 106 21 H

8 64 SAN 2BH

-0.62

-0.52 F*2 107 21 H

17 64 SAN 2BH

-0.87

-0.78 F*2 108 21 H

5 65 SAN 2BH

-0.75

-0.63 F*2 109 21 H

12 65 MAN 2BH

-1.01

-0.85 F*2 110 21 H

16 65 MAN 2BH

-0.97

-0.75 F*2 111 21 H

10 66 SAN 2BH

-0.83

-0.53 F*2 112 21 H

17 66 SAN 2BH

-0.65

-0.53 F*2 113 21 H

14 67 SAD 2BH

-3.02 F*2 114 21 H

4 68 SAN 2BH

-0.86

-0.73 F*2 115 21 H

5 68 SAN 2BH

-0.90

-0.76 F*2 116 21 H

3 71 SAN 2BH

-0.85

-0.73 F*2 117 21 H

10 71 SAN 2BH

-0.89

-0.79 F*2 118 21 H

11 71 SAN 2BH

-0.77

-0.65 F*2 119 21 H

10 73 SAN 2BH

-0.79

-0.71 F*2 120 21 H

11 73 SAN 2BH

-0.88

-0.78 F*2 Page 29 of 48

21 STEAM GENERATOR F*2 TUBES, BOC23, 2005 No. SIG LegRow Col IndicationjLocationjElev fromlElev tolStatus 121 21 Hj 5 74 SAN I 2BH

-0.95

-0.811 F*2 122 21 H 1 9 74 SAN 2BH

-0.96

-0.87 1 F*2 21 STEAM GENERATOR EF* TUBES, BOC23,2005 No. SIG l-eg Row Col Indication Location Elev from Elev to Status 1

21 H

4 11 MAN EBH

-10.97

-10.43 EF*

2 21 H

3 17 SAD EBH

-13.35 EF*

3 21 H

9 18 SAN EBH

-0.34

-0.23 EF*

4 21 H

3 22 SAN EBH

-9.57

-9.43 EF*

5 21 H

19 25 SAN EBH

-9.59

-9.43 EF*

6 21 H

30 27 MAN EBH

-9.42

-9.18 EF*

7 21 H

13 30 SAD EBH

-13.71 EF*

8 21 H

13 32 SAD EBH

-13.67 EF*

9 21 H

19 32 SAN EBH

-12.40

-11.94 EF*

10 21 H

23 34 SAN EBH

-9.41

-9.35 EF*

11 21 H

23 39 SAN EBH

-11.41

-8.80 EF*

12 21 H

10 43 SAN EBH

-13.17

-11.20 EF*

13 21 H

1 46 MAN EBH

-12.87

-11.53 EF*

14 21 H

28 48 SAN' EBH

-13.31

-9.91 EF*

15 21 H

8 49 SAN EBH

-9.14

-9.04 EF*

16 21 H

25 49 MAN EBH

-13.21

-10.35 EF*

17 21 H

28 55 SAN EBH

-13.44

-10.27 EF*

18 21 H

11 57 SAN EBH

-9.06

-9.03 EF*

19 21 H

27 59 SAN EBH

-13.47

-10.45 EF*

20 21 H

7 61 SAN EBH

-9.64

-9.49 EF*

21 21 H

7 67 MAN EBH

-9.63

-9.01 EF*

22 STEAM GENERATOR F*0 TUBES, BOC23,2005 -

No. SIG LeRow Coll Indication Location Elev from Elev to Status 1

22 H

4 1

SAN TRH

-2.22

-2.02 F*0 2

22 H

1 2

SAN TRH

-1.99

-1.83 F*0 3

22 H

1 7

SAN TRH

-2.33

-2.07 F*0 4

22 H

3 10 SAN TRH

-2.30

-2.10 F*0 5 22l H 1

16l MCI TRH

-2.60

-2.37 F*0 6 22 H

35 20 SAN TRH

-2.29

-2.11 F*0 7

22 H

35 23 SAN TRH

-2.44

-2.29 F*0 8

22 H

37 25 SAN TRH

-2.45

-2.38 F*0 9

22 H

8 27 SAD TRH

-2.57 l F*0 10,22, H 1

281 SAN TRH

-2.43

-2.30 F*0 11 22 H

2 28 SAI TRH

-2.03

-1.94 F*0 12 22 H

2 29 SAN TRH

-2.47

-2.33 F*0 13 22 H

3 29 SAN TRH

-2.59

-2.48 F*0 14 22 H

2 30 SAN TRH

-2.51

-2.48 F*0 15 22 H

1 33 MAN TRH

-2.67

-2.36 F*0 16 22 H

1 34 SAN TRH

-2.67

-2.26 F*0 17 22 H

42 35 SAN TRH

-2.60

-2.50 F*O 18 22 H

1 37 MAN TRH

-2.77

-2.55 F*0 19 22 H

2 45 SAN TRH

-2.29

-2.15 F*0 20 22 H

1 46 SAN TRH

-2.74

-2.51 F*0 21l22 H

42 46 SAIl TRH

-2.22

-1.85 F*0 Page 30 of 48

22 STEAM GENERATOR F*0 TUBES, BOC23, 2005 No. SIG-LegIRow Col Indication Location Elev from Elev to Status 22 22 H

7 48 SAN TRH

-2.59

-2.48 F*O 23 22 H

9 48 SAN TRH

-2.36

-2.14 F*O 24 22 H

10 48 SAN TRH

-2.35

-2.28 F*O 25 22 H

5 49 SAN TRH

-2.49

-2.39 F*O 26 22 H

6 49 SAI TRH

-2.46

-2.37 F*O 27 22 H

7 49 SAN TRH

-2.44

-2.26 F*O 28 22 H

8 49 SAN TRH

-2.41

-2.33 F*O 29 22 H

3 50 SAN TRH

-2.63

-2.55 F*O 30 22 H

4 50 SAN TRH

-2.67

-2.56 F*O 31 22 H

6 50 SAN TRH

-2.60

-2.52 F*O 32 22 H

7 50 SAN TRH

-2.58

-2.44 F*O 33 22 H

10 50 SAN TRH

-2.57

-2.49 F*O 34 22 H

37 50 SAN TRH

-2.56

-2.48 F*O 35 22 H

4 51 MAN TRH

-2.48

-2.23 F*O 36 22 H

7 51 SAN TRH

-2.80

-2.64 F*O 37 22 H

1 52 MAN TRH

-2.64

-2.33 F*O 38 22 H

1 53 MAN TRH

-2.67

-2.41 F*O 39 22 H

6 53 SAN TRH

-2.47

-2.28 F*O 40 22 H

34 53 MAN TRH

-2.34

-2.19 F*O 41 22 H

5 54 MAN TRH

-2.34

-2.22 F*O 42 22 H

7 55 SAN TRH

-2.91

-2.82 F*O 43 22 H

34 55 MAN TRH

-2.25

-2.06 F*O 44 22 H

1 56 MAN TRH

-2.60

-2.47 F*O 45 22 H

2 56 SAN TRH

-2.72

-2.63 F*0 46 22 H

34 56 MAN TRH

-2.31

-2.09 F*O 47 22 H

24 57 SVI TRH

-2.29

-2.03 F*O 48 22 H

37 57 MAN TRH

-2.32

-2.10 F*O 49 22 H

6 58 SAI TRH

-2.92

-2.83 F*O 50 22 H

9 58 SAN TRH

-2.43

-2.31 F*O 51 22 H

34 58 MAN TRH

-2.61

-2.27 F*O 52 22 H

7 59 SAN TRH

-2.43

-2.37 F*O 53 22 H

26 59 MAN TRH

-2.30

-2.16 F*O 54 22 H

34 60 MAN TRH

-2.29

-2.13 F*O 55 22 H

11 61 SAN TRH

-2.41

-2.33 F*O 56 22 H

1 62 MAN TRH

-2.70

-2.44 F*O 57 22 H

8 63 SAN TRH

-2.95

-2.64 F*O 58 22 H

17 63 MAN TRH

-2.56

-2.42 F*O 59 22 H

18 63 MAI TRH

-2.48

-2.40 F*O 60 22 H

34 63 MAN TRH

-2.33

-2.10 F*O 61 22 H

5 64 SAN TRH

-2.47

-2.36 F*O 62 22 H

6 64 SAI TRH

-2.47

-2.40 F*O 63 22 H

8 64 SAN TRH

-2.39

-2.33 F*O 64 22 H

7 65 MAN TRH

-2.80

-2.64 F*0 65 22 H

8 66 MAN TRH

-2.41

-2.32 F*O 66 22 H

18 66 SAN TRH

-1.47

-1.42 F*0 67 22 H

8 67 SAN TRH

-2.41

-2.37 F*O 68 22 H

8 68 SAN TRH

-2.42

-2.35 F*0 69 22 H

34 68 MAN TRH

-2.61

-2.19 F*O 70 22 H

1 69 MAN TRH

-2.65

-2.38 F*0 71 22 H

10 69 SAI TRH

-2.74

-2.64 F*O Page 31 of 48

22 STEAM GENERATOR F*0 TUBES, BOC23, 2005 No. SIG Leg Row Col Indication Location Elev from EIev to Status 72 22 H 1 70 MAN TRH

-2.57

-2.29 F*O 73 22 H

8 70 SAI TRH

-2.51

-2.44 F*O 74 22 H 9

70 SAI TRH

-2.45

-2.38 F*O 75 22 H 37 70 MAN TRH

-2.51

-2.20 F*O 76 22 H 6

71 SAN TRH

-2.45

-2.35 F*0 77 22 H

7 71 SAN TRH

-2.40

-2.30 F*O 78 22 H

9 71 SAI TRH

-2.62

-2.53 F*0 79 22 H

I1 71 SAN TRH

-2.54

-2.39 F*0 80 22 H

24 71 MAN TRH

-2.36

-2.16 F*0 81 22 H

1 72 MAN TRH

-2.57

-2.47 F*O 82 22 H 5

72 SAN TRH

-2.53

-2.46 F*O 83 22 H

6 72 SAI TRH

-2.53

-2.50 F*O 84 22 H

7 72 SAI TRH

-2.47

-2.43 F*0 85 22 H

34 72 SAN TRH

-2.61

-2.54 F*O 86 22 H 37 72 SAN TRH

-2.18

-1.95 F*O 87 22 H 1 74 MAN TRH

-2.54

-2.40 F*O 88 22 H

4 74 MAN TRH

-2.41

-2.37 F*O 89 22 H

5 74 SAN TRH

-2.44

-2.33 F*O 90 22 H

6 74 MAN TRH

-2.47

-2.36 F*O 91 22 H

6 75 SAN TRH

-2.54

-2.46 F*O 92 22 H

1 76 MAN TRH

-2.71

-2.47 F*O 93 22 H

1 77 MAN TRH

-2.48

-2.38 F*O 94 22 H

4 77 SAN TRH

-2.44

-2.33 F*O 95 22 H

6 77 MAN TRH

-2.43

-2.30 F*O 96 22 H 1 78 MAN TRH

-2.64

-2.33 F*0 97 22 H

2 78 SAI TRH

-2.30

-2.24 F*O 98 22 H

4 78 SAN TRH

-2.57

-2.44 F*O 99 22 H

5 78 SAI TRH

-2.41

-2.29 F*O 100 22 H

1 79 MAN TRH

-2.51

-2.41 F*O 101 22 H

3 79 MAN TRH

-2.45

-2.31 F*0 102 22 H

1 80 MAN TRH

-2.60

-2.27 F*O 103 22 H

4 80 SAN TRH

-2.37

-2.26 F*O 104 22 H

5 80 SAN TRH

-2.38

-2.22 F*0 105 22 H

4 81 SAN TRH

-2.41

-2.32 F*0 106 22 H

1 82 MAN TRH

-2.65

-2.35 F*0 107 22 H

5 82 SAN TRH

-2.42

-2.25 F*O 108 22 H

1 83 MAN TRH

-2.47

-2.29 F*O 109 22 H

5 84 SAI TRH

-2.38

-2.30 F*O 110 22 H

6 85 SAN TRH

-2.42

-2.31 F*0 111 22 H

7 85 SAN TRH

-2.49

-2.39 F*O 112 22 H

6 86 SAN TRH

-2.43

-2.33 F*O 113 22 H

1 87 SAN TRH

-2.62

-2.45 F*O 114 22 H

4 88 SAN TRH

-2.45

-2.37 F*O 115 22 H

9 88 SAI TRH

-2.46

-2.40 F*O 116 22 H

13 88 SAN TRH

-1.96

-1.91 F*0 117 22 H

15 88 MAI TRH

-2.62

-2.52 F*O 118 22 H

6 91 SAN TRH

-2.56

-2.49 F*O 119 22 H

6 94 MAN TRH

-2.64

-2.44 F*O 120 22 H

7 94 SAI TRH

-2.51

-2.47 F*O Page 32 of 48

22 STEAM GENERATOR F*1 TUBES, BOC23,2005 No. S/G Leg Row Col Indication Location Elev from Elev to Status 1

22 H

15 7

SAD 1BH

-1.05 F*1 2

22 H

4 8

SAD 1BH

-1.40 F*1 3

22 H

1 10 SAN 1BH

-2.15

-1.96 F*1 4

22 H

21 11 SAD 1BH

-1.42 F*1 5

22 H

15 13 SAD 1BH

-1.11 F*1 6

22 H

24 13 SAD IBH

-1.46 F*1 7

22 H

4 14 SANJ:

1BH

-2.22

-2.10 F*1 8

22 H

17 14 MAD 1BH

-1.32 F*1 9

22 H

18 14 SAN 1BH

-1.38

-1.34 F*l 10 22 H

2 15 SAN 1BH

-2.33

-2.23 F*l 11 22 H

4 15 SAD.

1BH

-1.25 F*l 12 22 H

9 15 SAD IBH

-1.16 F*l 13 22 H

14 15 SAD 1BH

-1.06 F*l 14 22 H

24 15 MAN' 1BH

-1.54

-1.14 F*l 15 22 H

25 15 SAD 1BH

-1.49 F*l 16 22 H

13 16 MAN 1BH

-1.10

-0.46 F*l 17 22 H

18 16 SAD 1BH

-1.34 F*l 18 22 H

25 16 SAD 1BH

-1.07 F*1 19 22 H

27 16 SAD 1BH

-1.17 F*l 20 22 H

1 17 MAN 1BH

-2.40

-2.24 F*l 21 22 H

4 17 MAD 1BH

-1.30 F*l 22 22 H

14 17 SAD 1BH

-1.32 F*l 23 22 H

25 17 SAD 1BH

-1.40 F*l 24 22 H

1 18 MAN 1BH

-2.16

-2.05 F*1 25 22 H

2 18 MAN 1BH

-2.10

-2.00 F*l 26 22 H

3 18 SAD 1BH

-0.91 F*l 27 22 H

4 18 MAD 1BH

-1.19 F*1 28 22 H

9 18 SAD 1BH

-1.45 F*1 29 22 H

14 18 MAD 1BH

-1.37 F*1 30 22 H

15 18 SAD 1BH

-0.94 F*l 31 22 H

4 19 SAN 1BH

-2.30

-2.08 F*l 32 22 H

13 19 SAD 1BH

-0.96 F*l 33 22 H

15 19 MAD 1BH

-1.08 F*1 34 22 H

25 19 SAD 1BH

-0.92 F*l 35 22 H

1 20 MAN 1BH

-2.21

-2.03 F*

36 22 H

3 20 SAN 1BH

-2.18

-2.11 F*1 37 22 H

9 20 MAD 1BH

-0.98 F*l 38 22 H

12 20 MAN 1BH

-0.80

-0.17 F*l 39 22 H

14 20 SAD 1BH

-0.91 F*l 40 22 H

20 20 MAD 1BH

-1.40 F*l 41 22 H

24 20 MAN 1BH

-0.93

-0.14 F*l 42 22 H

29 20 SAD 1BH

-1.47 F*l 43 22 H

37 20 SAD 1BH

-1.14 F*l 44 22 H

1 21 MAN 1BH

-2.38

-2.21 F*l 45 22 H

4 21 MAN 1BH

-2.45

-2.36 F*l 46 22 H

10 21 SAD.

1BH

-1.34 F*1 47 22 H

31 21 SAD 1BH

-1.40 F*l 48 22 H

1 22 MAD IBH

-0.99 F*l 49 22 H

7 22 SAD IBH

-1.27 F*1 50 22 H

14 22 MAD IBH

-0.96 F*l Page 33 of 48

22 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG -

Row Col Indication Location Elev from Elev to Status 51 22 H 18 22 SAN IBH

-1.55

-1.48 F*1 52 22 H 23 22 SAD IBH

-1.31 F*l 53 22 H 25 22 MAD 1BH

-1.30 F*l 54 22 H 28 22 SAD IBH

-1.47 F*l 55 22 H

33 22 SAD 1BH

-1.28 F*1F 56 22 H

1 23 MAD IBH

-0.96 F*l 57 22 H

22 23 SAN IBH

-1.55

-1.34 F*l 58 22 H

26 23 SAD 1BH

-1.53 F*1 59 22 H

32 23 SAD 1BH

-1.24 F*l 60 22 H

1 24 SAD 1BH

-1.36 F*l 61 22 H

7 24 SAD IBH

-0.98 F*1 62 22 H

15 24 MAD 1BH

-0.90 F*l 63 22 H

21 24 MAN IBH

-0.70

-0.01 FP 64 22 H

27 24 MAD IBH

-1.57 F*l 65 22 H

28 24 SAN IBH

-1.35

-1.24 F*l 66 22 H

34 24 SAD 1BH

-1.02 F*l 67 22 H

35 24 SAD 1BH

-1.32 F*l 68 22 H

37 24 SAD 1BH

-1.04 F*l 69 22 H

7 25 SAD IBH

-1.31 F*l 70 22 H

14 25 SAD IBH

-1.33 F*l 71 22 H

16 25 SAD 1BH

-1.27 IF*

72 22 H

19 25 SAD 1BH

-1.24 F*1 73 22 H

20 25 SAD 1BH

-0.96 F*l 74 22 H

21 25 SAD IBH

-1.51 F*l 75 22 H

23 25 MAN IBH

-1.52

-1.35 F*l 76 22 H

26 25 SAN IBH

-1.17

-1.04 F*1 77 22 H

28 25 MAN 1BH

-0.77

-0.21 F*l 78 22 H

31 25 SAD IBH

-1.00 F*l 79 22 H

32 25 SAD 1BH

-1.40 F*l 80 22 H

33 25 SAD 1BH

-1.00 F*l 81 22 H

35 25 SAD 1BH

-1.56 F*1F 82 22 H

1 26 SAN IBH

-0.53

-0.30 F*l 83 22 H

7 26 MAD 1BH

-0.98 F*1 84 22 H

18 26 SAD IBH

-1.27 F*l 85 22 H

19 26 MAD.

IBH

-1.67 F*1 86 22 H

21 26 SAD IBH

-1.36 F*l 87 22 H

22 26 SAD IBH

-1.56 IF*

88 22 H

25 26 SAD IBH

-1.31 F*1 89 22 H

27 26 SAD 1BH

-1.50 F*l 90 22 H

28 26 SAD IBH

-0.96 F*1F 91 22 H

32 26 SAD IBH

-1.30 F*1 92 22 H

33 26 SAD IBH

-1.33 F*l 93 22 H

1 27 SAD IBH

-0.99 l F*l 94 22 H

7 27 SAD 1BH

-0.96 F*l 95 22 H

13 27 MAD IBH

-1.29 F*l 96 22 H

14 27 SAD IBH

-0.95 F*l 97 22 H

15 27 SAD IBH

-1.59 F*1F 98 22 H

20 27 SAD IBH

-1.52 F*l 99 22 H

24 27 SAD 1BH

-1.35 F*l 100 22 H

25 27 SAD IBH

-1.22 F*l Page 34 of 48

22 STEAM GENERATOR F*l TUBES, BOC23, 2005 No. SIG _ Row Col Indication Location Elev from Elev to Status 101 22 H

28 27 MAD IBH

-1.24 F*1 102 22 H

31 27 MAD IBH

-1.29 F*1 103 22 H

3 28 SAD 1BH

-0.98 F*1 104 22 H

7 28 MAD IBH

-1.51 F*1 105 22 H

23 28 SAD IBH

-1.34 F*1 106 22 H

31 28 SAD 1BH

-1.34 FP 107 22 H

38 28 SAD 1BH

-2.18 F*1 108 22 H

1 29 MAD 1BH

-1.35 F*l 109 22 H

7 29 SAD IBH

-1.18 F*l 110 22 H

19 29 SAD IBH

-1.72 F*l 111 22 H

24 29 SAD 1BH

-1.57 F*1 112 22 H

26 29 MAD 1BH

-1.44 F*1 113 22 H

27 29 MAD IBH

-1.23 F*1 114 22 H

32 29 SAD 1BH

-1.52 F*1 115 22 H

33 29 SAD 1BH

-0.98 F*l 116 22 H

1 30 MAD IBH

-0.94 F*l 117 22 H

5 30 SAN 1BH

-0.39

-0.15 F*1 118 22 H

7 30 SAD 1BH

-1.05 F*1 119 22 H

9 30 SAD 1BH

-1.61 F*l 120 22 H

21 30 SAD 1BH

-1.29 F*l 121 22 H

32 30 MAD l IBH

-1.40 F*1 122 22 H

35 30 SAD IBH

-1.40 F*l 123 22 H

3 31 MAN IBH

-1.65

-1.16 F*1 124 22 H

4 31 SAN IBH

-1.69

-1.55 F*1 125 22 H

5 31 SAD IBH

-1.02 F*1 126 22 H

27 31 SAD IBH

-1.25 F*1 127 22 H

28 31 SAD 1BH

-1.47 F*1 128 22 H

29 31 SAD IBH

-1.25 F*l 129 22 H

32 31 SAD IBH

-1.40 F*1 130 22 H

33 31 SAD IBH

-1.32 F*l 131 22 H

35 31 SAD IBH

-1.53 F*l 132 22 H

39 31 SAD IBH

-1.15 F*1 133 22 H

1 32 MAD IBH

-1.34 F*1 134 22 H

6 32 SAD IBH

-1.00 F*1 135 22 H

9 32 MAD IBH

-1.18 F*l 136 22 H

20 32 MAN 1BH

-1.36

-1.21 F*l 137 22 H

21 32 SAD IBH

-1.36 F*1 138 22 H

22 32 SVD 1BH

-1.80 F*1 139 22 H

28 32 SAD IBH

-1.17 F*l 140 22 H

31 32 SAN 1BH

-1.48

-1.28 F*l 141 22 H

32 32 SAD 1BH

-1.44 F*l 142 22 H

33 32 MAD IBH

-1.46 F*l 143 22 H

18 33 SAD 1BH

-1.41 F*1 144 22 H

23 33 SAD 1BH

-1.53 F*1 145 22 H

25 33 SAD IBH

-0.90 F*l 146 22 H

32 33 MAD IBH

-1.49 F*l 147 22 H

33 33 SAD IBH

-1.00 F*l 148 22 H 7

34 SAD 1BH

-1.25 F*1 149 22 H 28 34 MAN 1BH

-1.53

-1.38 F*l 150 22 H

30 34 MAN 1BH

-1.61

-1.54 Fl*

Page 35 of 48

22 STEAM GENERATOR F1 TUBES, BOC23,2005 No. SIG Le Ro Col Indication Location Elev from Elev to Status 151 22 H

33 34 SAD 1BH

-0.97 F*1 152 22 H

3 35 SAD 1BH

-1.36 F*1 153 22 H

12 35 MAD 1BH

-1.21 F*1 154 22 H

13 35 MAN 1BH

-1.34

-1.12 F*1 155 22 H

22 35 SAD 1BH

-0.90 F*1 156 22 H

28 35 MAN IBH

-1.58

-1.34 F*1 157 22 H

29 35 SAD IBH

-1.27 F*1 158 22 H

30 35 SAD 1BH

-1.38 F*1 159 22 H

1 36 SAD 1BH

-1.30 F*1 160 22 H

7 36 SAD 1BH

-1.35 F*1 161 22 H

20 36 MAD 1BH

-1.47 F*1 162 22 H

23 36 MAN 1BH

-1.47

-1.24 F*1 163 22 H

27 36 SAD 1BH

-1.48 F*1 164 22 H

29 36 SAD-1BH

-1.22 F*1 165 22 H

32 36 SAN 1BH

-0.99

-0.81 F*1 166 22 H

33 36 SAD 1BH

-1.23 F*1 167 22 H

35 36 SAD 1BH

-1.51 F*1 168 22 H

2 37 SAD IBH

-1.25 F*1 169 22 H

20 37 SAD 1BH

-1.48 F*1 170 22 H

21 37 MAD 1BH

-1.23 F*1 171 22 H

23 37 SAD 1BH

-1.51 F*1 172 22 H

24 37 SAN IBH

-1.55

-1.45 F*1 173 22 H

30 37 SAD IBH

-1.29 F*1 174 22 H

37 37 SAD 1BH

-1.40 F*1 175 22 H

19 38 MAN 1BH

-1.34

-1.21 F*1 176 22 H

33 38 MAN

-1BH

-0.75

-0.17 F*1 177 22 H

42 38 SAD 11BH

-1.11 F*

178 22 H

1 39 MAN 1BH l -0.90

-0.18 F*1 179 22 H

3 39 SAD 1BH

-1.41 F*1 180 22 H

9 39 SAD 1BH

-1.50 F*1 181 22 H

20 39 SAD 1BH

-1.11 F*1 182 22 H

21 39 MAD 1BH

-1.07 F*

183 22 H

23 39 SAD 1BH

-1.50 F*1 184 22 H

33 39 SAD l1BH

-1.31 F*1 185 22 H

37 39 SAD 1BH

-1.33 F*1 186 22 H

1 40 MAD IBH

-1.34 F*1 187 22 H

3 40 SAD 1BH

-1.08 F*1 188 22 H

6 40 SAD 1BH

-1.07 F*1 189 22 H

12 40 SAD 1BH

-1.03 F*1 190 22 H

20 40 SAD 1BH

-1.41 F*1 191 22 H

21 40 SAD 1BH

-1.36 F*1 192 22 H

22 40 MAD 1BH

-0.95 F*1 193 22 H

23 40 SAD I1BH

-1.00 F*1 194 22 H

32 40 SAD 1BH

-1.52 F*1 195 22 H

33 40 SAD IBH

-1.00 F*1 196 22 H

1 41 MAD 1BH

-1.63 F*1 197 22 H

19 41 SAD 1BH

-1.54 F*1 198 22 H

21 41 SAD 1BH

-1.58 F*1 199 22 H

22 41 SAD 1BH

-1.47 F*1 200 22 H

23 41 MAD 1BH

-1.22 F*1 Page 36 of 48

22 STEAM GENERATOR F*1 TUBES, BOC23,2005 No. S/G Leg Row Col Indication Location Elev from Elev to Status 201 22 H

27 41 MAN 1BH

-1.53

-1.40 F*1 202 22 H

28 41 SAD 1BH

-0.92 F*1 203 22 H

29 41 SAD

-11BH

-1.28 F*1 204 22 H

30 41 SAD 1i31H

-0.99 F*1 205 22 H

33 41 MAD 1BH

-1.41 F*1 206 22 H

37 41 MAD 1BH

-1.45 F*1 207 22% H 1 42 SAD 1BH

-1.35 F*1 208 22 H

2 42 SAD 1BH

-1.32 F*1 209 22 H

10 42 SAD:

1BH

-1.10 F*1 210 22 H

13 42 SAD IBH

-1.28 F*1 211 22 H

21 42 MAD 1BH

-0.95 F*1 212 22 H

22 42 SAD IBH

-1.49 F*1 213 22 H

23 42 SAD 1BH

-1.07 F*1 214 22 H

24 42 SAD IBH

-1.71 F*1 215 22 H

28 42 SAN IBH

-0.74

-0.67 F*1 216 22 H

29 42 SAD 1BH

-1.50 F*l 217 22 H

32 42 SAN 1BH

-1.65

-1.51 F*1 218 22 H

33 42 MAN 1BH

-1.49

-1.35 F*l 219 22 H

35 42 SAI 1BH

-0.56

-0.36 F*1 220 22 H 1 43 SAD 1BH

-1.63 F*1 221 22 H

3 43 SAD 1BH

-1.22 F*l 222 22 H

12 43 MAD 1BH

-1.17 F*l 223 22 H

13 43 SAD IBH

-1.18 F*l 224 22 H 22 43 MAD IBH

-1.44 F*l 225 22 H 27 43 MAD 1BH

-1.06 F*l 226 22 H 30 43 SAD 1BH

-1.07 F*1 227 22 H

33 43 MAN 1BH

-1.49

-1.38 F*l 228 22 H

37 43 SAN 1BH

-0.45

-0.29 F*l 229 22 H

6 44 SAD 1BH

-1.07 F*1 230 22 H

13 44 MAN 1BH

-1.12

-0.97 F*1 231 22 H

14 44 SAD 1BH

-1.58 F*l 232 22 H

17 44 SAN 1BH

-1.40

-1.13 F*l 233 22 H

18 44 SAD 1BH

-0.93 F*l 234 22 H 22 44 MAD 1BH

-1.05 F*l 235 22 H 23 44 MAD 1BH

-1.52 F*l 236 22 H 27 44 SAD 1BH

-1.55 F*1 237 22 H

30 44 SAD 1BH

-1.50 F*l 238 22 H

33 44 SAD 1BH

-1.36 F*l 239 22 H

35 44 SAN 1BH

-1.42

-1.35 F*l 240 22 H

37 44 SAD IBH

-1.14 F*l 241 22 H

1 45 MAD 1BH

-0.75 F*1 242 22 H

6 45 SAD 1BH

-1.34 F*l 243 22 H

13 45 SAN 1BH

-1.24

-0.99 F*1 244 22 H

15 45 MAD 1BH

-1.52 F*l 245 22 H 19 45 MAD 1BH

-0.90 F*l 246 22 H 23 45 SAD 1BH

-1.00 F*l 247 22 H 28 45 MAD IBH

-1.57 F*l 248 22 H

29 45 SAD 1BH

-1.40 F*l 249 22 H

34 45 MAN 1BH

-1.40

-1.33 F*l 250 22 H 9

46 SAD 1BH

-1.03 F*1 Page 37 of 48

W:

t 22 STEAM GENERATOR P1 TUBES. BOC23. 2005 No. SIG Le Row Col Indication Location Elev from Elev to Status 251 22 H

10 46 SAD IBH

-1.18 F*1 252 22 H 12 46 SAD 1BH

-1.38 F*1 253 22 H

16 46 MAD IBH

-1.35 F*1 254 22 H 17 46 SAN 1BH

-1.02

-0.86 1F*

255 22 H 18 46 SAD IBH

-0.95 F*1 256 22 H 19 46 SAD IBH

-1.47 F*1 257 22 H

26 46 MAN IBH

-1.45

-1.16 F*1 258 22 H

28 46 SAN IBH

-1.38

-1.24 F*1 259 22 H

1 47 SAD 1BH

-1.19 F*1 260 22 H

6 47 SAD 1BH

-1.29 F*1 261 22 H

12 47 SAD IBH

-1.43 F*1 262 22 H

20 47 SAD IBH

-0.93 F*1 263 22 H

28 47 SAD IBH

-0.99 F*1 264 22 H

33 47 MAD IBH

-1.05 F*1 265 22 H

35 47 SAD IBH

-1.09 F*1 266 22 H

1 48 SAD 1BH

-1.07 F*1 267 22 H

2 48 MAN 1BH

-1.16

-1.02 F*1 268 22 H

3 48 MAD 1BH

-1.17 F*1 269 22 H

21 48 SAD IBH

-1.00 F*1 270 22 H

22 48 SAD IBH

-1.52 F*1 271 22 H

23 48 MAN IBH

-1.44

-1.22 F*1 272 22 H

28 48 MAN 1BH

-1.18

-0.85 F*1 273 22 H

29 48 SAD 1BH

-1.59 F*1 274 22 H

37 48 SAD IBH

-1.43 F*1 275 22 H

1 49 SAN IBH

-1.22

-1.03 F*1 276 22 H

4 49 SAD IBH

-1.28 F*1 277 22 H

9 49 SAD IBH

-1.32 F*1 278 22 H

10 49 SAD IBH

-1.35 F*1 279 22 H

11 49 MAD IBH

-1.36 F*1 280 22 H

12 49 SAN IBH

-0.32

-0.01 F*1 281 22 H

14 49 MAN 1BH

-1.22

-0.83 F*1 282 22 H

18 49 MAN 1BH

-1.35

-1.05 F*1 283 22 H

21 49 SAD 1BH

-0.86 F*1 284 22 H

23 49 MAN IBH

-1.53

-1.12 F*1 285 22 H

27 49 SAD IBH

-1.15 F*1 286 22 H

28 49 SAN IBH

-1.40

-1.32 F*1 287 22 H

32 49 MAN IBH

-1.64

-1.12 Ft1 288 22 H

40 49 SAD 1BH

-1.19 F*1 289 22 H

41 49 SAN 1BH

-1.29

-1.15 F*1 290 22 H

1 50 SAD IBH

-1.44 F*1 291 22 H

2 50 SAD IBH

-1.15 F*1 292 22 H

9 50 MAN 1BH

-1.10

-1.01 F*1 293 22 H

11 50 SAD IBH

-1.18 F*1 294 22 H

13 50 MAD IBH

-1.05 F*1 295 22 H

15 50 SAD IBH

-1.20 F*1 296 22 H

18 50 MAD 1BH

-0.94 F*1 297 22 H

22 50 SAD 1BH

-0.99 F*1 298 22 H

23 50 MAD 1BH

-0.97 F*1 299 22 H

24 50 MAN IBH

-1.52

-1.34 F*1 300 22 H

25 50 SAN IBH

-2.35

-2.28 F*1 Page 38 of 48

22 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG Leg Row Col Indication Location Elev from Elev to Status 301 22 H

27 50 MAD IBH

-1.51 F*1 302 22 H

28 50 SAN IBH

-1.46

-1.39 F*l 303 22 H

29 50 SAD IBH

-1.60 F*l 304 22 H

30 50 SAD IBH

-1.22 F*l 305 22 H 31 50 SAD 1BH

-1.00 F*l 306 22 H

32 50 MAN 1BH

-1.43

-1.29 F*1 307 22 H

33 50 SAN 1BH

-1.47

-1.30 F*l 308 22 H 34 50 SAD 1BH

-1.55 F*l 309 22 H

35 50 SAD 1BH

-1.56 F*l 310 22 H

1 51 SAD 1BH

-1.13 F*1 311 22 H 3

51 SAD 1BH

-1.35 F*1 312 22 H 10 51 SAD 1BH

-1.19 F*l 313 22 H

12 51 SAD 1BH

-1.17 F*l 314 22 H

13 51 MAD 1BH

-1.21 F*l 315 22 H

14 51 SAD IBH

-1.06 F*l 316 22 H

15 51 SAD 1BH

-1.09 F*l 317 22 H

16 51 SAD IBH

-1.22 F*1 318 22 H

18 51 MAD 11BH

-1.37 F*l 319 22 H

19 51 MAD IBH

-1.03 F*l 320 22 H

20 51 MAD IBH

-1.03 F*l 321 22 H

21 51 SAD IBH

-1.33 F*l 322 22 H

28 51 SAD IBH

-1.47 F*l 323 22 H

32 51 SAN IBH

-1.40

-1.26 F*l 324 22 H

37 51 SAD 1BH

-1.57 F*l 325 22 H

3 52 SAD 1 BH

-1.35 F*l 326 22 H

7 52 SAD 1BH

-1.03 F*l 327 22 H

9 52 SAD 1BH

-1.15 F*l 328 22 H

10 52 SAD 1BH

-1.07 F*l 329 22 H

12 52 SAN 1BH

-1.18

-1.09 F*l 330 22 H

14 52 MAD IBH

-1.02 F*l 331 22 H

20 52 SAD IBH

-1.28 F*1 332 22 H

28 52 SAN IBH

-1.37

-1.27 F*l 333 22 H

29 52 SAN 1BH

-1.46

-1.37 F*1 334 22 H

33 52 SAN IBH

-1.54

-1.22 F*l 335 22 H

7 53 SAD IBH

-1.02 F*l 336 22 H

13 53 MAN IBH

-1.37

-0.85 F*l 337 22 H

14 53 SAD IBH

-1.09 F*l 338 22 H

18 53 SAD IBH

-1.33 F*l 339 22 H

19 53 SAN 1BH

-1.12

-1.06 F*l 340 22 H

21 53 MAD IBH

-1.00 F*1 341 22 H

24 53 SAD IBH

-1.46 F*1 342 22 H

25 53 SAN IBH

-1.56

-1.35 F*l 343 22 H

29 53 MAD 1BH

-1.53 F*1 344 22 H 30 53 MAN IBH

-0.62

-0.06 F*

345 22 H

32 53 SAD IBH

-1.35 F*1 346 22 H

33 53 SAD 1BH

-1.34 F*1 347 22 H

37 53 MAD 1BH

-0.93 F*l 348 22 H 40 53 MAN 1BH

-0.84

-0.23 F*l 349 22 H 1 54 MAN 1BH

-1.17

-0.86 F*l 350 22 H

7 54 SAD IBH

-1.06 F*1 Page 39 of 48

22 STEAM GENERATOR F*l TUBES, BOC23,2005 No. S/G Leg Row Col Indication Location Elev from Elev to Status 351 22 H

9 54 MAD 1BH

-1.18 F*l 352 22 H

10 54 SAD 1BH

-1.24 F*l 353 22 H

13 54 SAD 1BH

-1.31 F*l 354 22 H

15 54 SAD 1BH

-1.07 F*l 355 22 H

16 54 MAN 1BH

-0.70

-0.15 F*1 356 22 H

18 54 MAD I-BH

-1.41 F*1 357 22 H

22 54 MAD.

1BH

-1.28 F*l 358 22 H

23 54 SAN 1BH

-1.50

-1.37 F*l 359 22 H

24 54 SAD 1BH

-1.46 F*l 360 22 H

25 54 SAD 1BH

-1.33 F*l 361 22 H

27 54 SAD 1BH

-1.45 F*l 362 22 H

34 54 SAD 1BH

-0.93 F*l 363 22 H

37 54 SAD 1BH

-1.41 F*1 364 22 H 1 55 SAN 1BH

-0.95

-0.62 F*l 365 22 H

9 55 SAD 1BH

-1.36 F*l 366 22 H

10 55 MAN 1BH

-1.25

-1.07 F*l 367 22 H

13 55 MAN

-1BH

-1.31

-0.65 F*l 368 22 H

14 55 SAD 1BH

-1.20 F*l 369 22 H

16 55 SAD 1BH

-1.09 F*1 370 22 H

17 55 SAN 1BH

-1.23

-1.09 F*l 371 22 H

19 55 MAD 1BH

-1.25 F*1 372 22 H

20 55 SAD 1BH

-1.23 F*l 373 22 H

21 55 MAD 1BH

-1.41 F*l 374 22 H

22 55 SAN 1BH

-1.43

-1.17 F*l 375 22 H

23 55 SAN 1BH

-1.35

-1.26 F1 376 22 H

24 55 SAD 1BH

-1.53 F*l 377 22 H 29 55 SAD 1BH

-1.39 F*l 378 22 H 32 55 SAD 1BH

-1.30 F*l 379 22 H 33 55 SAN 1BH

-1.45

-1.33 F*l 380 22 H 4

56 MAN IBH

-1.39

-0.99 F*l 381 22 H

6 56 SAD 1BH

-1.26 F*l 382 22 H

7 56 SAD 1BH

-1.36 F*l 383 22 H

9 56 SAD 1BH

-1.28 F*l 384 22 H

10 56 MAD 1BH

-1.20 F*l 385 22 H

11 56 MAD 1BH

-1.19 F*l 386 22 H

12 56 MAD 1BH

-1.24 F*1 387 22 H

13 56 SAD 1BH

-1.41 F*l 388 22 H 16 56 SAD -

1BH

-1.25 F*l 389 22 H

27 56 SAD 1BH

-1.60 F*l 390 22 H

28 56 SAD 1BH

-1.55 F*l 391 22 H

29 56 SAD 1BH

-1.50 F*l 392 22 H

32 56 SAD 1BH

-1.28 F*l 393 22 H

3 57 SAD 1BH

-1.28 F*l 394 22 H

5 57 SAD 1BH

-1.37 F*l 395 22 H

7 57 SAN 1BH

-1.15

-1.03 F*l 396 22 H

10 57 SAD 1BH

-1.24 F*1 397 22 H

13 57 MAD 1BH

-1.31 F*l 398 22 H

14 57 MAD 1BH

-1.04 F*l 399 22 H

15 57 SAD 1BH

-1.06 F*

400 22 H

16 57 SAD I1BH

-1.06 Fl Page 40 of 48

22 STEAM GENERATOR P1 TUBES. BOC23. 2005 No. SG L Row Col Indication Location Elev from Elev to Status 401 22 H

18 57 MAD 1BH

-0.92 F*1 402 22 H

20 57 SAD 1BH

-1.05 F*1 403 22 H

23 57 SAD IBH

-1.51 F*1 404 22 H

25 57 SAD 1BH

-1.44 F*1 405 22 H

27 57 SAD 1BH

-1.37 F*1 406 22 H

28 57 MAD IBH

-1.41 F*1 407 22 H

32 57 SAD 1BH

-1.28 F*1 408 22 H

34 57 SAD 1BH

-1.45 F*1 409 22 H

1 58 SAD 1BH

-1.30 F*1 410 22 H

3 58 SAD 1BH

-1.27 F*1 411 22 H

7 58 MAD 1BH

-1.21 F*1 412 22 H

12 58 SAD 1BH

-1.00 F*1 413 22 H

14 58 SAD 1BH

-1.31 F*1 414 22 H

16 58 SAD IBH

-1.20 F*1 415 22 H

18 58 MAD 1BH

-1.31 F*1 416 22 H

19 58 SAD 1BH

-0.98 F*1 417 22 H

20 58 SAD 1BH

-1.40 F*1 418 22 H

21 58 SAD 1BH

-1.01 F*1 419 22 H

23 58 SAN 1BH

-1.51

-1.15 F*1 420 22 H

24 58 SAD IBH

-1.51 F*1 421 22 H

37 58 SAN 11BH

-1.49

-1.28 F*1 422 22 H

4 59 SAD 1BH

-1.26 F*1 423 22 H

5 59 SAD 1BH

-1.42 F*1 424 22 H

9 59 SAD BH

-1.30 F*1 425 22 H

13 59 SAD 1BH

-1.01 F*1 426 22 H

15 59 MAD 1BH

-1.34 F*1 427 22 H 16 59 SAI 1BH

-0.45

-0.38 F*1 428 22 H

17 59 SAD 1BH

-1.04 F*1 429 22 H

18 59 SAD 1BH

-1.03 F*1 430 22 H

19 59 MAD 1BH

-1.01 F*1 431 22 H

20 59 SAD 1BH

-1.43 F*1 432 22 H

22 59 SAD 1BH

-1.43 F*1 433 22 H

23 59 SAN 1BH

-1.40

-1.25 F*1 434 22 H 24 59 SAD 1BH

-1.51 F*1 435 22 H 25 59 SAD 1BH

-1.40 F*1 436 22 H

27 59 SAD 1BH

-1.41 F*1 437 22 H

28 59 MAN 1BH

-1.45

-1.07 F*1 438 22 H

29 59 SAD 1BH

-1.51 F*1 439 22 H

30 59 MAN 1BH

-1.46

-1.35 F*1 440 22 H

34 59 SAD IBH

-1.39 F*1 441 22 H

37 59 SAD IBH

-1.01 F*1 442 22 H

5 60 SAD 1BH

-1.35 F*1 443 22 H 6

60 SAD

-11BH

-1.34 F*1 444 22 H 7

60 SAD 1BH

-1.35 F*1 445 22 H 13 60 MAI 1BH

-0.52

-0.21 F*1 446 22 H 15 60 SAD 1BH

-1.26 F*1 447 22 H 17 60 SAD 1BH

-0.99 F*1 448 22 H

18 60 SAD 1BH

-1.42 F*1 449 22 H

19 60 MAD 1BH

-1.41 F*1 450 22 H

23 60 SAD IBH

-1.48 F*1 Page 41 of 48

22 STEAM GENERATOR F*1 TUBES, BOC23, 2005 No. SIG Leg Row Col Indication Location Elev from Elev to Status 451 22 H 27 60 SAD 1BH

-1.26 F*1 452 22 H 32 60 SAN 1BH

-1.47

-1.30 F*1 453 22 H 37 60 SAD 1BH

-1.45 F*1 454 22 H 7

61 MAD 1BH

-1.26 F*1 455 22 H

12 61 SAD 1BH

-1.29 F*1 456 22 H

13 61 MAD 1BH

-1.53 F*1 457 22 H

14 61 MAD 1BH

-1.11 F*1 458 22 H

16 61 SAD 1BH

-1.10 F*1 459 22 H

18 61 MAD 1BH

-1.43 F*1 460 22 H

19 61 SAD 1BH

-1.02 F*1 461 22 H

20 61 SAD 1BH

-1.35 F*1 462 22 H 22 61 MAN 1BH

-1.37

-1.23 F*1 463 22 H 23 61 SAN 1BH

-1.43

-1.32 F*1 464 22 H

25 61 SAD 1BH

-1.50 F*1 465 22 H 26 61 SAD 1BH

-1.14 F*1 466 22 H 27 61 MAN 1BH

-0.54

-0.24 F*1 467 22 H 32 61 SAD 1BH

-1.47 F*1 468 22 H 5

62 MAD 1BH

-1.62 F*1 469 22 H 7

62 SAD 1BH

-1.23 F*1 470 22 H 10 62 SAD 1BH

-1.38 F*1 471 22 H 12 62 SAD 1BH

-1.42 F*1 472 22 H 16 62 MAI 1BH

-0.52

-0.37 F*1 473 22 H 18 62 SAD 1BH

-1.34 F*1 474 22 H 19 62 MAN.

1BH

-1.25

-0.88 F*l 475 22 H

23 62 MAD 1BH

-1.55 F*l 476 22 H

24 62 SAD 1BH

-1.36 F*1 477 22 H 25 62 SAN 1BH

-0.74

-0.32 F*l 478 22 H

29 62 SAD 13BH

-1.16 F*l 479 22 H

34 62 SAD 1BH

-1.46 F*1 480 22 H 37 62 SAN 1BH

-1.46

-1.38 F*l 481 22 H 42 62 MAN 1BH

-0.74

-0.25 F*l 482 22 H

1 63 SAD 1BH

-1.24 F*1 483 22 H

7 63 SAD 1BH

-1.19 F*1 484 22 H

11. 63 SAD 1BH

-1.30 F*1 485 22 H 12 63 SAD 1BH

-1.41 F*l 486 22 H

23 63 SAD 11BH

-1.16 F*1 487 22 H 24 63 SAD 1BH

-1.38 F*l 488 22 H

25 63 SAN 1BH

-1.61

-1.50 F*1 489 22 H 31 63 SAD 1BH

-1.08 F*l 490 22 H 33 63 SAD 1BH

-1.52 F*1 491 22 H 37 63 SAN 1BH

-1.34

-1.20 F*l 492 22 H 42 63 SAD 1BH

-1.15 F*l 493 22 H 1 64 SAD 1BH

-1.21 F*l 494 22 H 2

64 SAD 1BH

-1.26 F*l 495 22 H 4

64 SAD 1BH

-1.14 F*l 496 22 H

7 64 SAN 13BH

-1.66

-1.54 F*l 497 22 H 9

64 SAN 1BH

-1.23

-1.16 F*l 498 22 H

15 64 SAD 1BH

-1.06 F*l 499 22 H

18 64 SAD 1BH

-1.30 F*l 500 22 H

19 64 MAD 1BH

-1.26 F*l Page 42 of 48

22 STEAM GENERATOR F*1 TUBES. BOC23. 2005 No. SIG Leg Row Col Indication Location Elev from Eiev to Status 501 22 H

32 64 MAD 1BH

-1.50 F*1 502 22 H

34 64 MAN 1BH

-1.44

-1.36 F*l 503 22 H

37 64 SAD 1BH

-1.18 F*l 504 22 H

6 65 MAD 1BH

-1.27 F*l 505 22 H

8 65 SAD 1BH

-1.18 F*l 506 22 H

9 65 MAD IBH

-1.00 F*1 507 22 H

10 65 MAN 1BH

-1.22

-1.15 F*l 508 22 H

11 65 SAD 1BH

-1.33 F*l 509 22 H

12 65 MAN 1BH

-1.31

-1.22 F*l 510 22 H

17 65 SAD 1BH

-1.01 F*1 511 22 H

19 65 SAD 1BH

-1.29 F*1 512 22 H

24 65 MAN

-11BH

-1.39

-1.28 F*1 513 22 H

26 65 SAD IBH

-1.26 F*l 514 22 H

27 65 SAN IBH

-1.41

-1.28 F*l 515 22 H

33 65 SAD 1BH

-1.49 F*1 516 22 H

34 65 SAD IBH

-1.23 F*1 517 22 H

36 65 MAI 1BH

-0.51

-0.15 F*l 518 22 H

37 65 SAD 1BH

-1.28 F*l 519 22 H

9 66 SAD 1BH

-1.15 F*l 520 22 H

11 66 MAN 1BH

-1.27

-1.16 F*l 521 22 H

13 66 SAD IBH

-1.28 F*l 522 22 H

19 66 SAD 1BH

-1.00 F*l 523 22 H

20 66 MAD 1BH

-1.27 F*l 524 22 H 21 66 MAD 1BH

-1.03 F*1 525 22 H

22 66 SAD 1BH

-1.47 F*l 526 22 H

24 66 SAN 1BH

-1.50

-1.32 F*1 527 22 H

31 66 SAD 1BH

-1.50 F*l 528 22 H

37 66 SAD 1BH

-1.31 F*l 529 22 H

7 67 SAD 1BH

-1.31 F*l 530 22 H

9 67 MAN 1BH

-1.13

-1.03 F*l 531 22 H

12 67 SAD 1BH

-1.02 F*l 532 22 H

16 67 SAN 1BH

-1.16

-1.09 F*l 533 22 H

17 67 SAD 1BH

-1.39 F*l 534 22 H

18 67 SAD 1BH

-0.98 F*l 535 22 H

20 67 SAD 1BH

-1.27 F*l 536 22 H

24 67 MAN 1BH

-1.49

-1.23 F*l 537 22 H

27 67 MAN 1BH

-1.48

-1.25 F*l 538 22 H

30 67 SAN 1BH

-1.50

-1.43 F*l 539 22 H

31 67 SAD 1BH

-1.00 F*l 540 22 H

32 67 SAD IBH

-1.22 F*l 541 22 H

34 67 SAD IBH

-1.48 F*l 542 22 H

37 67 SAD l1BH

-1.45 F*l 543 22 H

9 68 SAI IBH

-0.40

-0.23 F*l 544 22 H

10 68 SAD IBH

-1.24 F*1 545 22 H

13 68 SAD 1BH

-1.17 F1 546 22 H

21 68 MAD 1BH

-1.33 F*l 547 22 H

24 68 MAN 1BH

-1.59

-1.48 F*l 548 22 H

27 68 SAN 1BH

-1.66

-1.34 F*l 549 22 H

31 68 SAD 1BH

-0.90 F*1 550 22 H

32 68 SAD 1BH

-1.32 F*1 Page 43 of 48

22 STEAM GENERATOR F* TUBES, BOC23,2005 No.lSIGlLeglRow Coll Indication Location Elev from Elev to Status 551 22 H

33 68 SAD IBH

-1.27 F*1 552 22 H

37 68 MAN 1BH

-1.51

-1.40 F*1 553 22 H

9 69 SAD 1BH

-1.34 F*1 554 22 H

14 69 SAD IBH

-0.99 F*1 555 22 H

15 69 MAD IBH

-0.94 F*1 556 22 H

16 69 MAD 1BH

-1.30 F*1 557 22 H

25 69 MAN IBH

-1.32

-1.21 F*1 558 22 H

27 69 SAD IBH

-1.51 F*1 559 22 H

31 69 SAD IBH

-1.46 F*1 560 22 H

32 69 SAD IBH

-1.15 F*1 561 22 H

37 69 SAD 1BH

-1.43 FP 562 22 H

4 70 SAD 1BH

-1.06 F*1 563 22 H

10 70 SAD 1BH

-1.10 F*1 564 22 H

11 70 SAD 1BH

-0.95 F*1 565 22 H

14 70 MAD 1BH

-1.00 F*1 566 22 H

16 70 SAD 1BH

-1.07 F*1 567 22 H

21 70 SAD 1BH

-1.47 F*1 568 22 H

22 70 SAD

.BH

-1.19 Fl 569 22 H

23 70 SAD 1BH

-1.14 F*1 570 22 H

24 70 SAD IBH

-1.57 F*1 571 22 H

27 70 SAN IBH

-1.52

-1.43 F*1 572 22 H

31 70 MAN IBH

-0.49

-0.31 F*1 573 22 H

12 71 MAD IBH

-1.11 F*1 574 22 H

13 71 MAD IBH

-0.98 F*1 575 22 H

14 71 SAD IBH

-1.36 F*1 576 22 H

17 71 MAD IBH

-1.35 F*1 577 22 H

18 71 SAD 1BH

-1.28 F*1 578 22 H

20 71 SAD IBH

-1.29 F*1 579 22 H

22 71 MAD IBH

-1.24 F*1 580 22 H

23 71 MAD 1BH

-1.42 F*1 581 22 H

27 71 SAD 1BH

-0.90 F*1 582 22 H

32 71 SAD 1BH

-1.17 F*1 583 22 H

37 71 SAD 1BH

-1.05 F*1 584 22 H

8 72 SAD 1BH

-1.28 F*1 585 22 H

9 72 MAD 1BH

-1.20 F*1 586 22 H

11 72 MAD IBH

-1.28 F*1 587 22 H

12 72 MAN 1BH

-1.24

-1.04 F*1 588 22 H

13 72 SAD 1BH

-1.37 F*1 589 22 H

15 72 SAD 1BH

-1.09 F*1 590 22 H

16 72 SAD 1BH

-1.40 F*1 591 22 H

17 72 SAD 1BH

-1.26 F*1 592 22 H 24 72 SAN 1BH

-0.51

-0.16 F*1 593 22 H

27 72 MAD 1BH

-1.32 F*1 594 22 H 31 72 SAD 1BH

-0.91 F*1 595 22 H 9

73 SAD IBH

-1.27 F*1 596 22 H

13 73 MAD BH

-1.30 F*1 597 22 H 14 73 MAD 1BH

-1.13 F*1 598 22 H 1 5 73 MAN 1BH

-1.16

-1.06 F*l 599 22 H

17 73 MAD IBH

-1.30 F*1 600 22 H

18 73 SAD IBH

-1.30 F*1 Page 44 of 48

I if 22 STEAM GENERATOR F-1 TUBES, BOC23, 2005 No. SIG L-Row Col Indication Location Elev from Elev to Status 601 22 H

19 73 SAD 1BH

-1.22 F*1 602 22 H

25 73 SAD 1BH

-1.49 F*1 603 22 H

31 73 SAD 1BH

-1.01 F*1 604 22 H

12 74 MAN 1BH

-0.59

-0.36 F*1 605 22 H

14 74 MAD 1BH

-1.34 F*1 606 22 H

17 74 MAN 1BH

-0.95

-0.22 F*1 607 22 H

18 74 SAN 1BH

-0.65

-0.34 F*1 608 22 H

24 74 SAD 1BH

-1.54 F*1 609 22 H

27 74 MAD 1BH

-1.14 F*1 610 22 H

4 751 SAD 1BH

-1.39 F*1 611 22 H

10 75 MAD 1BH

-1.24 F*1 612 22 H

12 75 MAD 1BH

-1.22 F*1 613 22 H

13 75 SAN 1BH

-1.27

-1.13 F*1 614 22 H

14 75 MAD 1BH

-1.33 F*1 615 22 H

15 75 MAD 1BH

-1.30 F*1 616 22 H

17 75 SAD 1BH

-1.07 F*l 617 22 H

19 75 SAD 1BH

-0.99 F*l 618 22 H

27 75 MAD 1BH

-0.90 F*l 619 22 H

8 76 SAD 1BH

-1.29 F*l 620 22 H

9 76 SAD 1BH

-1.18 F*l 621 22 H

13 76 SAD 1BH

-1.48 F*l 622 22 H

18 76 SAD 1BH

-1.42 F*l 623 22 H

20 76 SAD 1BH

-1.38 F*l 624 22 H

22 76 SAN 1BH

-0.82

-0.06 F*l 625 22 H

26 76 MAD 1BH

-1.50 F*l 626 22 H

8 77 SAD 1BH

-1.26 F*1 627 22 H

11 77 SAD 1BH

-1.39 F*l 628 22 H

12 77 MAD 1BH

-1.49 F*l 629 22 H

13 77 SAN 1BH

-1.18

-1.11 F*l 630 22 H

14 77 SAN 1BH

-0.45

-0.13 F*l 631 22 H

15 77 SAD 1BH

-1.33 F*l 632 22 H

16 77 MAD 1BH

-1.27 F*l 633 22 H

17 77 MAD 1BH

-1.10 F*1 634 22 H

18 77 MAD 1BH

-1.43 F*1 635 22 H

22 77 SAN 1BH

-1.30

-1.07 F*l 636 22 H

25 77 SAD 1BH

-0.94 F*l 637 22 H

11 78 SAD 1BH

-1.36 F*l 638 22 H

12 78 SAD 1BH

-0.95 F*l 639 22 H

17 78 SAD 1BH

-1.40 F*1 640 22 H

18 78 SAD 1BH

-1.38 F*l 641 22 H

22 78 SAD 1BH

-1.53 F*l 642 22 H

26 78 MAN 1BH

-1.20

-1.06 F*l 643 22 H 12 79 SAN 1BH

-0.68

-0.30 F*l 644 22 H 13 79 MAN 1BH

-1.21

-1.12 F*1 645 22 H

14 79 MAN 1BH

-1.13

-1.02 F*1 646 22 H

15 79 MAD 1BH

-1.29 F*1 647 22 H

17 79 MAD 1BH

-1.12 F*l 648 22 H

19 79 SAD 1BH

-1.20 F*l 649 22 H

22 79 SAD 1BH

-1.31 F*l 650 22 H

25 79 SAD 1BH

-1.36 F*l Page 45 of 48

r 22 STEAM GENERATOR F*1 TUBES. BOC23. 2005 No. SIG Row Coll Indication Location Elev from Elev to Status 651 22 H

26 79 SAD 1BH

-1.49 F*1 652 22 H

.9 80 MAN 1BH

-1.31

-1.21 F*1 653 22 H 10 80 MAD 1BH

-1.36 F*1 654 22 H

12 80 MAD 1BH

-1.36 F*1 655 22 H

13 80 MAN 1BH

-1.19

-1.05 F*1 656 22 H

15 80 SAD 1BH

-1.32 F*1 657 22 H 18 80 SAD 1BH

-1.02 F*1 658 22 H

22 80 MAD 13BH

-1.00 F*1 659 22 H

23 80 SAD 1BH

-1.40 F*1 660 22 H

9 81 MAD 1BH

-1.30 F*1 661 22 H

12 81 SAD 1BH

-0.88 F*1 662 22 H

13 81 SAD 1BH

-1.38 F*1 663 22 H

15 81 MAD 1BH

-0.94 F*1 664 22 H

17 81 SAD 1BH

-1.06 F*1 665 22 H

9 82 MAD 1BH

-1.04 F*1 666 22 H

12 82 SAD 1BH

-1.30 F*1 667 22 H 13 82 MAD 1BH 1

-1.00 F*1 668 22 H

17 82 MAD 1BH

-1.30 F*1 669 22 H

15 83 SAD 1BH

-0.90 F* 1 670 22 H 17 83 SAD 1BH

-0.86 F*1 671 22 H 22 83 SAD IBH

-1.44 F*1 672 22 H 10 84 SAD 1BH

-1.48 F*1 673 22 H

15 84 SAD 1BH

-1.48 F*1 674 22 H

18 84 MAD 1BH

-0.92 F*1 675 22 H

12 85 SAD 1BH

-1.45 F*1 676 22 H

13 85 SAD 1BH

-1.16 F*1 677 22 H

13 86 SAD 1BH

-1.32 F*1 678 22 H

16 86 SAD 1BH

-1.11 F*1 679 22 H

18 86 SCD

=BH

-1.02 F*1 I 680 22 H

15 87 SAD 1BH

-1.05 F*1 681 22 H

17 87 SAD 1BH

-1.42 F*1 22 STEAM GENERATOR F*2 TUBES, BOC23, 2005 No. S/G Leg Row Col Indication Location Elev from Elev to Status 1 22 H

25 14 MAN 2BH

-2.51

-1.87 F*2 2

22 H

18 20 MAN 2BH

-2.72

-1.85 F*2 3

22 H

18 21 SAD 2BH

-1.48 F*2 4 22 H

21 22 SAD 2BH

-3.51 F*2 5 22 H

32 22 MAN 2BH

-2.41

-1.73 F*2 6 22 H

16 23 MAN 2BH

-2.34

-1.79 F*2 7 22 H

25 24 MAN 2BH

-2.36

-1.75 F*2 8

22 H

24 26 MAN 2BH

-1.10

-1.00 F*2 9

22 H

9 28 SAN 2BH

-2.49

-1.97 F*2 10 22 H

17 28 SAD 2BH

-2.12 F*2 11 22 H

20 28 SAN 2BH

-0.70

-0.58 F*2 12 22 H

20 29 SAD 2BH

-3.16 F*2 13 22 H

29 29 MAN 2BH

-2.75

-1.85 F*2 14 22 H

27 30 SAN 2BH

-2.10

-1.86 F*2 15 22 H

15 31 SAD 2BH

-0.31 F*2 16 22 H

17 33 SAD 2BH

-3.08 F*2 Page 46 of 48

.. I -1, i, -..

.1..

I,.

`--..

1I.1 -j:

22 STEAM GENERATOR P2 TUBES. BOC23. 2005 No. S/G LeglRow Col Indication Location Elev from Elev tolStatus 17 22 H

22 34 MAN 2BH

-0.57

-0.52 F*2 18 22 H

14 35 SAN 2BH

-3.21i

-2.99 F*2 19 22 H

19 35 SAD 2BH

-3.18 F*2 20 22 H

37 35 SAD 2BH

-0.88 F*2 21 22 H

19 36 SADT 2BH

-3.32 F*2 22 22 H

12 37 SAD 2BH

-3.28 F*2 23 22 i-H 33 37 MAN 2BH

-2.38

-1.81 F*2 24 22 H 37 38 SAN 2BH

-0.86

-0.75 F*2 25 22 H

18 39 SAD 2BH

-3.16 F*2 26 22 H

19 39 SAD 2BH

-3.21 F*2 27 22 H

14 40 SAN 2BH

-1.10

-0.89 F*2 28 22 H

18 40 MAD 2BH

-3.00 F*2 29 22 H 5 41 MAN 2BH

-2.42

-1.80 F*2 3 0 22 H

13 41 MAD 2BH

-3.52 F*2 31 22 H

12 42 SAN 2BH

-0.75

-0.64 F*2 32 22 H 15 43 SAN 2BH

-2.09

-1.90 F*2 33 22 H

23 43 MAD 2BH

-3.02 F*2 34 22 H

1 44 MAD 2BH

-3.24 F*2 35 22 H

16 44 SAD 2BH

-3.40 F*2 36 22 H

17 45 MAN 2BH

-3.60

-3.07 F*2 37 22 H

37 45 SAD 2BH

-3.48 F*2 38 22 H

39 45 SAD 2BH

-3.15 F*2 39 22 H

14 46 SAN 2BH

-1.97

-1.82 F*2 40 22 H

15 46 MAD 2BH

-3.28 F*2 41 22 H

22 46 SAD 2BH

-2.98 F*2 42 22 H

23 46 SAD 2BH

-3.38 F*2 43 22 H

18 47 MAD 2BH

-3.37 F*2 44 22 H

21 47 SAD 2BH

-3.20 F*2 45 22 H

18 48 SAD 2BH

-2.96 F*2 46 22 H

27 48 SAD 2BH

-3.08 F*2 47 22 H

3 49 SAN 2BH

-0.81

-0.74 F*2 48 22 H

13 49 SAN 2BH

-0.84

-0.74 F*2 49 22 H

26 50 MAD 2BH

-3.14 F*2 50 22 H

8 51 SAD 2BH

-3.12 F*2 51 22 H

9 51 MAN 2BH

-2.11

-2.00 F*2 52 22 H

11 51 SAD 2BH

-3.16 F*2 53 22 H

18 52 SAD 2BH

-3.10 F*2 54 22 H

24 52 MAN 2BH

-3.50

-3.12 F*2 55 22 H

10 53 MAD 2BH

-3.29 F*2 56 22 H

12 53 SAN 2BH

-3.02

-2.95 F*2 57 22 H

16 53 SAD 2BH

-3.48 F*2 58 22 H

17 53 MAN 2BH

-1.84

-1.69 F*2 59 22 H

20 53 MAD 2BH

-3.16 F*2 60 22 H

12 54 MAD 2BH

-3.04 F*2 61 22 H

28 54 MAN 2BH

-2.56

-1.73 F*2 62 22 H

37 55 MAN 2BH

-2.38

-2.04 F*2 63 22 H

15 56 SAN 2BH

-0.47

-0.43 F*2 64 22 H

20 56 SAD 2BH

-3.21 F*2 65 22 H

37 56 SAD 2BH

-3.00 F*2 66 22 H

21 57 MAN 2BH

-0.89

-0.64 F*2 Page 47 of 48

0 I

t

'. ~

.I, 9.

  • t-ff t *-r 22 STEAM GENERATOR F*2 TUBES, BOC23, 2005 No. SIG L-Row Col Indication Location Elev from Elev to Status 67 22 H

2 58 SAD 2BH

-3.23 F*2 68 22 H

11 58 SAD 2BH

-3.08 F*2 69 22 H

13 58 SAN 2BH

-0.61

-0.45 F*2 70 22 H

9 60 SAN 2BH

-1.61

-1.43 F*2 71 22 H

20 60 SAD 2BH

-3.25 F*2 72 22 H 13 62 MAN 2BH

-2.22

-1.58 F*2 73 22 H

15 65 SAN 2BH

-0.76

-0.52 F*2 74 22 H

16 65 MAD 2BH

-3.04 F*2 75 22 H

12 66 SAN 2BH

-0.94

-0.82 F*2 76 22 H

24 69 SAN 2BH

-0.93

-0.81 F*2 77 22 H

32 70 MAN 2BH

-2.54

-1.90 F*2 78 22 H

26 71 MAN 2BH

-2.56

-2.11 F*2 79 22 H

12 73 SAN 2BH

-0.74

-0.64 F*2 80 22 H

16 73 MAN 2BH

-2.50

-1.83 F*2 81 22 H

15 74 SAN 2BH

-0.92

-0.80 F*2 82 22 H

19 74 SAN 2BH

-1.86

-1.75 F*2 83 22 H

22 75 MAN 2BH

-2.60

-1.90 F*2 84 22 H

11 76 SAN 2BH

-0.89

-0.61 F*2 85 22 H

17 76 MAN 2BH

-0.78

-0.64 F*2 86 22 H

23 78 MAN 2BH

-2.49

-1.53 F*2 87 22 H

17 80 SAN 2BH

-0.87

-0.73 F*2 88 22 H

18 81 SAN 2BH

-0.74

-0.67 F*2 89 22 H 22 81 SAN 2BH

-0.86

-0.79 F*2 90 22 H

26 81 SAN 2BH

-2.47

-1.92 F*2 91 22 H 15 85 MAN 2BH

-2.31

-1.73 F*2 92 22 H

15 86 MAN 2BH

-2.42

-1.75 F*2 93 22 H 14 88 MAN 2BH

-2.39

-1.74 F*2 Page 48 of 48