L-PI-03-006, May 2003 Monthly Operating Report for Prairie Island

From kanterella
Jump to navigation Jump to search
May 2003 Monthly Operating Report for Prairie Island
ML031640143
Person / Time
Site: Prairie Island  
Issue date: 06/06/2003
From: Solymossy J
Nuclear Management Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
L-PI-03-0060
Download: ML031640143 (7)


Text

Con,n,med to NuearExceHl 5

June 6, 2003 Praire Island Nuclear Generating Plant Operated by Nuclear Management Company, LLC L-PI-03-0060 Technical Specification 5.6.4 U S Nuclear Regulatory Commission ATTN: Document Control Desk Washingtpn, DC 20555 PRAIRIE ISLAND NUCLEAR GENERATING PLANT DOCKETS. 50-282 AND 50-306 LICENSE NOS. DPR-42 AND DPR-60 MONTHLY OPERATING REPORT-Mav 2003 Attached is the Monthly Operating Report for May 2003 for the Prairie Island Nuclear Generating Plant. The Nuclear Management Company has not made new or revised existing Nuclear Regulatory Commission commitments in this letter or the attachment.

ph M. Solymossyf Vice President, Prairie IslAnd Nuclear Generating Plant I

CC Regional Administrator, USNRC, Region Ill Project Manager, Prairie Island Nuclear Generating Plant, USNRC, NRR NRC Resident Inspector, Prairie Island Nuclear Generating Plant rGlennY Wilson, State of Minnesota

Attachment:

NRC Monthly Report; May 2003 1717 Wakonade Drive East

  • Welch, Minnesota 55089-9642 Telephone: 651.388.1121

NRC MONTHLY REPORT PRINTED 6/2/2003 Page 1 DOCKET NO. 50-282 UNIT PRAIRIE ISLAND NO. I DATE 6/2/2003 COMPLETED BY DALE DUGSTAD PHONE 651-388-11214376 NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE MONTH: MAY 2003 During the month of May, Unit 1 was base loaded. There were no shutdowns or power reductions.

There are no other items to report.

CURRENT CONTINUOUS OPERATING RUN OF 41 DAYS

NRC MONTHLY REPORT PRINTED 6/2J2003 Page 2 DOCKET NO. 50-282 UNIT PRAIRIE ISLAND NO. 1 DATE 61220O3 COMPLETED BY DALE DUGSTAD PHONE 651-388-1121-4376 OPERATING DATA REPORT OPERATING STATUS

1. UNIT NAME:

PRAIRIE ISLAND NO. 1

2. REPORTING PERIOD:

MAY 2003

3. UCENSED THERMAL POWER (MWT): 1650
4. NAMEPLATE RATING (GROSS MWE):

593

5. DESIGN ELECTRICAL RATING (NET MWE): 536
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):

554

7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):

522

8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 - 7) SINCE LAST REPORT, GIVE REASON:

NONE

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE):

NONE

10. REASONS FOR RESTRICTIONS, IF ANY:

NONE THIS MONTH YR-TO-DATE CUMULATIVE

11. HOURS IN REPORTING PERIOD 744 3623 258215
12. NUMBER OF HOURS REACTOR CRITICAL 744.0 3623.0 223842.4
13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 5571.1
14. HOURS GENERATOR ON-LINE 744.0 3482.6 221726.2
15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
16. GROSS THERMAL ENERGY GENERATED (MWH) 1224462 5694815 353980593
17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 415640 1968490 117794420
18. NET ELECTRICAL ENERGY GENERATED (MWH) 391840 1865805 110929546
19. UNIT SERVICE FACTOR 100.0 96.1 85.9
20. UNIT AVAILABILITY FACTOR 100.0 96.1 85.9
21. UNIT CAPACITY FACTOR ( MDC NET) 100.9 98.7 84.6
22. UNIT CAPACITY FACTOR ( DER NET) 98.3 96.1 80.9
23. UNIT FORCED OUTAGE RATE 0.0 3.9 4.6
24. FORCED OUTAGE HOURS 0.0 140.4 10603.1

NRC MONTHLY REPORT PRINTED 61212003 Page 3 DOCKET NO. 50-282 UNIT PRAIRIE ISLAND NO.1 DATE 6/212003 COMPLETED BY DALE DUGSTAD PHONE 651-388-11214376 UNIT SHUTDOWNS AND POWER REDUCTIONS MONTH: MAY 2003 DATE 5131/2003 NOTES:

UNIT TYPE I

N/A None.

HOURS REASON METHOD LER NUMBER SYSTEM COMPONENT 0

N/A N/A N/A TYPE F-FORCED S-SCHEDULED REASON A-EQUIPMENT FAILURE B-MAINTENANCE OR TEST C-REFUELING D-REGULATORY RESTRICTION E-OPERATOR TRAINING AND LICENSE EXAMINATION F-ADMINISTRATIVE G-OPERATIONAL ERROR H-OTHER METHOD SYSTEM CODE 1-MANUAL DRAFT IEEE STD 2-MANUAL TRIP 800-1984(P805-D5) 3-AUTO TRIP 4-CONTINUED 5-REDUCED LOAD COMPONENT CODE 9-OTHER IEEE STD 803A-1983

NRC MONTHLY REPORT PRINTED 6/2/2003 Page 4 DOCKET NO. 50-306 UNIT PRAIRIE ISLAND NO. 2 DATE 6/2/2003 COMPLETED BY DALE DUGSTAD PHONE 651-388-1121-4376 NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE MONTH: MAY 2003 During the month of May, Unit 2 was base loaded. There were no shutdowns or power reductions.

There are no other items to report.

CURRENT CONTINUOUS OPERATING RUN OF 455 DAYS

NRC MONTHLY REPORT PRINTED 6/2003 Page 5 DOCKET NO. 50-306 UNIT PRAIRIE ISLAND NO. 2 DATE 6/2/2003 COMPLETED BY DALE DUGSTAD PHONE 651-388-11214376 OPERATING DATA REPORT OPERATING STATUS

1. UNIT NAME:

PRAIRIE ISLAND NO. 2

2. REPORTING PERIOD:

MAY 2003

3. LICENSED THERMAL POWER (MWT):

1650

4. NAMEPLATE RATING (GROSS MWE):

593

5. DESIGN ELECTRICAL RATING (NET MWE):

536

6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):

554

7. MAXIMUM DEPENDABLE CAPACITY (NET MWE):

522

8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 - 7) SINCE LAST REPORT, GIVE REASON:

NONE

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE):

NONE

10. REASONS FOR RESTRICTIONS, IF ANY:

NONE THIS MONTH YR-TO-DATE CUMULATIVE

11. HOURS IN REPORTING PERIOD 744 3623 249333
12. NUMBER OF HOURS REACTOR CRITICAL 744.0 3623.0 221727.2
13. REACTOR RESERVE SHUTDOWN HOURS 0.0 0.0 1516.1
14. HOURS GENERATOR ON-LINE 744.0 3623.0 220034.5
15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
16. GROSS THERMAL ENERGY GENERATED (MWH) 1223579 5925341 352336425
17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 415720 2044840 116391650
18. NET ELECTRICAL ENERGY GENERATED (MWH) 392061 1942516 110072419
19. UNIT SERVICE FACTOR 100.0 100.0 88.2
20. UNIT AVAILABILITY FACTOR 100.0 100.0 88.2
21. UNIT CAPACITY FACTOR ( MDC NET) 101.0 102.7 87.3
22. UNIT CAPACITY FACTOR (DER NET) 98.3 100.0 83.1
23. UNIT FORCED OUTAGE RATE 0.0 0.0 2.8
24. FORCED OUTAGE HOURS 0.0 0.0 6390.7

NRC MONTHLY REPORT PRINTED 6/22003 Page 6 DOCKET NO. 50-306 UNIT PRAIRIE ISLAND NO. 2 DATE 6/22003 COMPLETED BY DALE DUGSTAD PHONE 651-388-1121-4376 UNIT SHUTDOWNS AND POWER REDUCTIONS MONTH: MAY 2003 DATE UNIT TYPE 5/31/2003 2

N/A NOTES:

None.

HOURS REASON METHOD LER NUMBER SYSTEM 0

N/A N/A COMPONENT N/A TYPE F-FORCED S-SCHEDULED REASON A-EQUIPMENT FAILURE B-MAINTENANCE OR TEST IETHOD 1-MANUAL 2-MANUAL TRIP SYSTEM CODE DRAFT IEEE STD 800-1984(P805-D5)

C-REFUELING D-REGULATORY RESTRICTION E-OPERATOR TRAINING AND LICENSE EXAMINATION 3-AUTO TRIP 4-CONTINUED 5-REDUCED LOAD COMPONENT CODE 9-OTHER IEEE STD 803A-1983 F-ADMINISTRATIVE G-OPERATIONAL ERROR H-OTHER