L-87-450, Special Rept:Several Impairments Incurred During Alternate Shutdown Mods,Including Impairments Opened Prior to Nov & Stayed Open for Longer than Required Per Tech Specs. Compensatory Measures Continue

From kanterella
(Redirected from L-87-450)
Jump to navigation Jump to search
Special Rept:Several Impairments Incurred During Alternate Shutdown Mods,Including Impairments Opened Prior to Nov & Stayed Open for Longer than Required Per Tech Specs. Compensatory Measures Continue
ML17342B008
Person / Time
Site: Turkey Point 
Issue date: 11/06/1987
From: Woody C
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
L-87-450, NUDOCS 8711100307
Download: ML17342B008 (7)


Text

/ ~

ACCESSION NBR:

FAC IL: 50-250 AUTH. NAME WOODYI C. O.

REC IP. NAME REGULA Y

ORMATION DISTRIBUTI Y

I (RIDS) 8711100307 DOC. DATE: 87/11/06 NOTARIZED:

NO DOCKET ¹ Turkey Point Planti Unit 3i Florida Poujer and Light C 05000250 AUTHOR AFFILIATION F 1 orida Poujer 5 Light Co.

RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Special rept: several impairments incurred during alternate shutdown modsiI including impairments opened prior to Nov 5 staged open for longer than required per Tech Specs.

Compensatorg measures continue.

DISTRIBUTION CODE:

AOOBD COPIES RECEIYED: LTR J ENCL j SIZE: 3 TITLE: OR/Licensing Submittal:

Fire Protection NOTES:

REC IP IENT ID CODE/NAME PD2-2 L*

McDONALD D INTERNAL: ARM/DAF/LFMB NRR/DEST/ADS OQC/HDS2 EXTERNAL:

LPDR NSIC COPIES LTTR ENCL 1

0 1

1 1

0 1

1 0

1 1

1 RECIPIENT ID CODE/NAME PD2-2 PD NRR WERMEIL> J N

/PSB REG FIL 01 NRC PDR COPIES LTTR ENCL 5

5 1

0 1

1 1

1 1

1 TOTAL NUMBER OF COPIES REQUIRED:

LTTR 16 ENCL 12

~ ~

~ ~

~ ~

'I V

n~

~

P.

BOX14, JUNO BEACH, FL 3340B-0420 C:I

~e,A~~

NOVEMBER 0 6 1987 L-87-450 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 Gentlemen:

Re:

Turkey Point Unit 3 Docket No. 50-250 Special Report - Breached Fire Barriers and Other Fire Protection S stem lm airments In accordance with Technical Specification 6.9.3 the attached Special Report is provided for your information.

Should there be any questions on this information, please contact us.

Very truly yours, t

C. O. Wo

~Group. Vice President Nuclear Energy COW/TCG/gp Attachment cc:

Dr. J. Nelson Grace, Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, Turkey Point Plant ooG 8711100307 871106 PDR

  • DOCK 05000250 8

PDR SDF I/004/I an FPL Group company

~ ~

~ ~

4 I

V O

4 h

A

~,I

~ I

~ Il 4

I h

4

~

~

4 V

4

~ V 4

I Jb

~ 4

~ A

~

I,

>> I

~

4

SPECIAL REPORT NOVEMBER 6, 1987 PIRE PROTECTION SYSTEM IMPAIRMENTS REQUIRING NRC NOTIPICATION

~Pur eee:

Technical Specification (TS) 3.14.5.b requires the submission of a report to the NRC if a non-functional fire barrier penetration is not returned to functional status within 7 days.

TS 3.14 states that certain other conditions also require NRC notification.

In accordance with the above requirements, this special report is being generated in order to notify the NRC.

This report will be updated on a 30 day basis.

Event:

The plant has been and is continuing to implement modifications in accordance with Appendix R Alternate Shutdown requirements and other unrelated requirements.

The schedular exemptions for the Safe Shutdown modifications, which outlined the alternative compensatory measures to be taken when a barrier is breached, expired on September 30,

1986, and on October 1,

1986.

Upon the expiration of the exemptions, the compensatory measures as described in Attachment 1 of our letter L-85-386 (dated October ll, 1985), are continuing to be in place until the Safe Shutdown modifications are complete.

Impairments incurred during Alternate Shutdown modifications are governed by the Technical Specifications or the exemptions, as applicable.

Other impairments are governed strictly by the Technical Specifications.

Cause and Corrective Actions:

The ma)or cause of the impairments is performed.

Due to the volume of work reporting the impairments in this one basis.

The impairments reported this present time, but were open in excess requiring NRC notification.

the number of modifications being being performed, the plant is report, rather than on a case-by-case month are either open or closed at the of the time period permitted without This report includes impairments not reported previously which were:

1) opened prior to November and 2) stayed open for longer than the time permitted by the Technical Specifications, and 3) are either still open or were closed prior to November.

The closed impairments have been reported at the time opened, unless noted otherwise.

The plant continues to implement the compensatory measures as applicable.

~ ~

E.

FIRE PROTECTION SYSTEM IMPAIRMENTS OPENED SINCE SEPTEMBER REPORT WHICH HAVE BEEN OPEN FOR LONGER THAN TECH SPEC LIMITS Impd 1192 1215 1216 1217 1221 87-0333 87-0335 Description Fire Door 058-2 Alarm Point 26 Alarm Point 27 Sealtight (Thermolag)

Fire Door 41-1 Penetration Seal CRN-C-1820 Pen.

Seal 104 E2 CRN-C-1826 Open 09/29/87 10/08/87 10/08/87 10/17/87 10/20/87 09/28/87 10/16/87 Closed 10/07/87 FIRE PROTECTION SYSTEM IMPAIRMENTS CLOSED SINCE SEPTEMBER REPORT BUT WERE OPEN FOR LONGER THAN TECH SPEC LIMITS Imp 8 Description Open Closed 1116 87-0046 87-0286 87-0287 Fire Door 108A-1 06/23/87 Penetration Seal 40E-E009 10/01/86 Fire Barrier 097E 06/11/87 Fire Barrier 097K 06/11/87 10/12/87 09/27/87 10/21/87 10/21/87 The following impairments were incurred prior to October

1987, however they are being included in this report as they were not reported previously.

Impd Description Open Closed 1180 87-0320 Fire Detection System 09/18/87 Raceway Protection B 4G1342 07/23/87