L-83-489, Application to Amend License DPR-67,deleting Tech Spec Requirement to Perform Containment Leakage Path Test for Penetration 25 (Fuel Transfer Tube) Tap 2 to Prevent Bellows Overpressurization

From kanterella
(Redirected from L-83-489)
Jump to navigation Jump to search
Application to Amend License DPR-67,deleting Tech Spec Requirement to Perform Containment Leakage Path Test for Penetration 25 (Fuel Transfer Tube) Tap 2 to Prevent Bellows Overpressurization
ML17214A436
Person / Time
Site: Saint Lucie 
Issue date: 09/16/1983
From: Robert E. Uhrig
FLORIDA POWER & LIGHT CO.
To: Eisenhut D
Office of Nuclear Reactor Regulation
Shared Package
ML17214A437 List:
References
L-83-489, NUDOCS 8309230127
Download: ML17214A436 (4)


Text

REGULATORY FORMATION DISTRIBUTION S N (RIDS)

ACCESSION NBR:8309230127 DOC.DATE 63/09/16 NOTARIZED:

NO FACIL:50-335 St ~ Lucie Planti Unit li Florida Power 8 Light Co.

AUTH ~ NAME AUTHOR AFFILIATION UHRIGn R ~ E ~

Florida Power 8 Light Co.

REC IP, NAME RECIPIENT AFFILIATION EISENHUT D.G.

Division of Licensing DOCKET ¹ 05000335-

SUBJECT:

Appljcation to amend License DPR-67ideleting Tech Spec reguirement to perform containment

'leakag'e path -test for penetration 25 (fidel transfer tube)

Tap 2 to prevent bellows overoressure testing.

DI'STRIBUTION CODE:

A001S COPIES RECEIVED:LTR f KNCI 'IZE' TITLE:

OR Submittal:

General Distribution NOTES:

RECIPIENT

ID CODE/NAtdE NRR ORB3 BC 01 INTERNAL:! KLD/MDS2 NRR/DL DIR NR ETB KG F

04 COPIES LTTR ENCL 57 g7 1

0 1

-1 1

1 1

1 RECIPIENT ID CODE/NAME NRR/DK/MTKB NRR/DL/ORAB NRR/DSI/RAB RGN2 COPIES

.LTTR

ENCL, 1

1 1

0 1

"1 1

EXTERNAL: ACRS NRC PDR NTIS 09 02 6

6 1

1 1

1 LPDR NSIC 03 05 TOTAL NUMBER OF COPIES REQUIRED:

LTTR 25 ENCL 23

M JI

~

N 0

~

0 K

Nl' I5 h

1 f

W Jl(

FLORIDAPOWER & LIGHT COMPANY September 16, 1983 L-83-489 Office of Nuclear Reactor Regulation Attention:

Nr. Qarrell G. Eisenhut, Director Division of Licensing U.

S. Nuclear Regulatory Commission Washington, D.

C.

20555

Dear Nr. Eisenhut:

Re:

St. Lucie Unit No.

1 Docket No. 50-335 Proposed License Amendment Containment Leakage

Paths, Penetration 25 In accordance with 10 CFR 50.90, Florida Power 5 Light Company submits herewith three signed originals and forty copies of a request to amend Appendix A of Facility Operating License QPR-67.

This amendment is submitted to delete the Technical Specification requiranent to per form a containment leakage path test for Tap 2 of Penetration 25 (Fuel Transfer Tube).

This bellows (Tap 2) is not a containment boundary and is designed for 16 psig, not the postulated accident pressure (Pa) of 39.6.

This amendment is needed to prevent the overpressure testing of this bellows.

The proposed amendment is described below and shown on the accompanying Technical Specification pages.

Page 3/4 6-5 The val ve tag number for Penetration 25 in Table 3.6-1 is changed to more accurately define the design.

Page 3/4 6-9 Tap 2 is deleted fr cm the Valve Tag Number and Location columns for Penetration 25 in Table 3.6-1.

In accordance wi th 10 CFR 50.91(b)(I),

a copy of this proposed license amendment is being forwarded to the State Designee for the State of Florida.

In accordance with 10 CFR 50.91(a) (I), and as discussed in the attached safety evaluation, we have determined that this amendment does not involve any significant hazards considerations pursuant to 10 CFR 50.91(c) in that the amendment does not:

PEOPLE... SERVING PEOPLE

Office of Nuclear Reactor Regulation Attention:

Mr. Darrell G. Eisenhut, Director Page 2

1) involve a singificant increase in the probability or consequences of an accident previously evaluated; or 2) create the possbility of a

new or different kind of accident from any acc ident pr evi ou sl y eva 1 ua ted; or 3) involve a significant reduction in a margin of safety.

The proposed amendment has been reviewed by the St. Lucie Facility Review Group and the Florida Power 5 Light Company Nuclear Review Board.

In accordance with 10 CFR 170.22, this amendment has been determined to be a

Class III amendment.

A check for

$4000 will be forwarded shortly.

Very truly yours, Robert E. Uhrig Vice President Advanced Systems 5 Technology REU/PLP/js Attachments CC:

J.

P. O'Reil ly, Region II Harold F. Reis, Esquire Ul ray Clark, Administrator Radiol ogical Health Services Depatment of Health and Rehabilitative Services 1323 Winewood Boul evard Tal lahassee, Fl or ida 32301