L-83-129, Application for Amend to License DPR-67 Changing Tech Specs to Modify Surveillance Requirements & Bases Associated W/Chlorine Detection Sys

From kanterella
(Redirected from L-83-129)
Jump to navigation Jump to search
Application for Amend to License DPR-67 Changing Tech Specs to Modify Surveillance Requirements & Bases Associated W/Chlorine Detection Sys
ML17213B130
Person / Time
Site: Saint Lucie NextEra Energy icon.png
Issue date: 03/09/1983
From: Robert E. Uhrig
FLORIDA POWER & LIGHT CO.
To: Eisenhut D
Office of Nuclear Reactor Regulation
Shared Package
ML17213B131 List:
References
L-83-129, NUDOCS 8303160171
Download: ML17213B130 (4)


Text

IE REGULA Y

INFORMATION DISTRIBUTI SYSTEM (RIDS)

AOCESSION NBR;8303160171 DOC ~ DATE: 83/03/09 NOTARIZED:

NO FAGIL:50"335 St ~ Lucie Planti Unit 1< Florida Power L Light Co, AUTH ~ NAME AUTHOR AFFILIATION UHRIGgR,E, Florida Power' Light Co, R E~C IP ~ NAME RECIPIENT AFFILIATION EISENHUTgDeG, Division of Licensing

SUBJECT:

Application for amend to License DPR-67 changing Tech Specs to modify surveillance requirements 8 bases associated w/Chlorine detection sys>

DISTRIBUTION CODE:

A001S COPIES RECEIVED:LTR ENCL SIZEe TITLE:

OR Submittalt General Distribution NOTES DOCKET 05000335 RECIPIENT ID CODE/NAME NRR ORB3 BC 01 INTERNAL: ELD/HDS2 NRR/DL DIR NRR FILE COPIES LTTR ENCL 7

7 1

0 1

1 1

1 1

1 RECIPIENT ID CODE/NAME NRR/DE/MTEB NRR/DI /DRAB NRR/DS I/RAB RGN2 COPIES LTTR ENCL 1

1 1

0 1

1 1

EXTERNALS ACRS NRC PDR NTIS 09 02 1

1 1

LPDR NSIC 03 05 1

1 1

1 TOTAL, NUMBER OF COPIES REQUIRED:

L'TTR 25 ENCL 23

0 fl II

'I 1

) f 1

ii II 1

o I

~ I I

I1 11 r

ll

)I, l

II

)I

/ t' II II I I 41 H

1'f I'

il H

P. O. BOX 14000, JUNO BEACH, FL 3340B yl ib FLORIDA POWER & LIGHTCOMPANY March 9, 1983 L-83-129 Office of Nuclear Reactor Regulation Attention:

Mr. Darrell G.

Ei senhut, Director Division of Licensing U.

S.

Nuclear Regulatory Commission Washington, D.

C.

20555

Dear Mr. Eisenhut:

Re: St. Luci e Unit 1

Docket No.

50-335 Proposed License Amendment Chlorine Detection System In accordance with 10 CFR 50.30, Florida Power 5 Light Company submits herewith three signed originals and forty copies of a request to amend Appendix A of Facility Operating License DPR-67.

This amendment is submitted to modify the surveillance requirements and bases associated with the Chlorine Detection System.

Since the removal of the 1-ton chlorine cylinders from the St. Lucie

site, which were used in the treatment of plant circulating water, the main source of chlorine, for which the original analysis was performed, no longer exists.
However, a smaller quantity of chlorine is stored offsite near the sewage treatment and city water storage facilities.

The attached evaluation provides the consequences of an accidental failure of a 150-lb. chlorine cylinder on the habitability of'he St.

I ucie Unit 1 control roan.

The St. Lucie Unit 2 control rocm is further from the storage chlorine cylinder location and is, therefore, not more limiting.

The results of the evaluation are detailed in Attachment 1

and specifically document that the 150-lb. chlorine cylinder does not constitute a source which would require having qualified detectors at the control room air intakes.

(Based on Regulatory Guide 1.78 toxicity limit of 15 ppm).

Calibration and Periodic testing has also been a problem in that chlorine must be introduced into the detectors to verify their operability requiring an unnecessary possible exposure for plant personnel.

In order to facilitate plant operation and maintenance during the present refueling outage, it is requested that this Technical Specification change be approved by mid-April 1983.

ool 1 8303ibOi7.i; 830309 I<', PDR."ADOCK, 05000335 PDR PEOPLE... SERVING PEOPLE

~

Office of Nuclea

'actor Regulation Page 2

The proposed amendment is described below:

Page'3/4 3-36 Specifications

3. 3.3.6 and 4.3. 3.6 are deleted.

Page 3/4 7-23 The Control rocm emergency ventilation system surveillance requirement of specification 4.7.7.1.e concerning the chlorine accident detection signal is deleted.

Page B 3/4 3-3 The bases for the chlorine detection system is deleted.

Page B 3/4 7-5 The bases for the chlorine accident detection signal is deleted.

The proposed amendment has been reviewed by the St. Luci e Facility Review Group and the Florida Power 5 Light Company Nuclear Review Board.

Very truly yours, Robert E. Uhrig Vice President Advanced Systems 5 Technology REU/PLP/js Attachment cc: J.

P. O'Reil ly, Region II Harold F. Reis, Esquire P NS-L 1-83-1 52-1