L-13-174, Emergency Response Data System Data Point Library Update

From kanterella
(Redirected from L-13-174)
Jump to navigation Jump to search
Emergency Response Data System Data Point Library Update
ML13143A016
Person / Time
Site: Beaver Valley
Issue date: 05/22/2013
From: Emily Larson
FirstEnergy Nuclear Operating Co
To:
Office of Nuclear Reactor Regulation, Document Control Desk
References
L-13-174
Download: ML13143A016 (12)


Text

~

FirstEnergy Nuclear Operating Company Eric A. Larson Site Vice President Beaver Valley Power Station P.O. Box 4 Sh~pmgpo~PA 15077 724-682-5234 Fax: 724-643-8069 May 22, 2013 L-13-174 10 CFR 50, Appendix E,Section VI ATTN: Document Control Desk U.S. Nuclear Regulatory Commission Washington, DC 20555-0001

SUBJECT:

Beaver Valley Power Station, Unit No.1 Docket No. 50-334, License No. DPR-66 Emergency Response Data System Data Point Library Update In accordance with reporting requirement 10 CFR 50, Appendix E,Section VI.3.a, updates of the Emergency Response Data System (EROS) Data Point Library (DPL) for Beaver Valley Power Station, Unit No.1 (BV1) are provided. The attachment includes the required details of the changes, and the enclosure provides copies of the updated DPL pages.

There are no regulatory commitments contained in this letter. If there are any questions or if additional information is required, please contact Mr. Thomas A. Lentz, Manager - Fleet Licensing, at 330-315-6810.

Sincerely, r?;';t,~-

Eric A. Larson

Attachment:

Summary of Changes to Data Point Library

Enclosure:

Beaver Valley Power Station EROS Data Point Library, Updated Pages cc:

NRC Region I Administrator NRC Resident Inspector NRC Project Manager (w/o enclosure)

Director BRPIDEP Site BRPIDEP Representative

Reactor Unit BV1 BV1 BV1 BV1 BV1 BV1 BV1 BV1 BV1 Attachment L-13-174 Summary of Changes to Data Point Library Page 1 of 1 DPL Point DescriptionofChange~)

XROO5 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1 ES" XROO6 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1 ES" XROO7 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1ES" XROO9 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1 ES" XR010 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1 ES" XR011 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1ES" XR013 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1 ES" XR014 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1 ES" XR015 Date: Changed to "4/29/2013" Maximum Instr Range: Replaced "1.2E6" with "S.1 ES"

Enclosure L-13-174 Beaver Valley Power Station EROS Data Point Library, Updated Pages (9 pages follow)

BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:

4/29/2013 Reactor Unit:

BV1 Data Feeder:

ARERAS NRC EROS Parameter:

EFF-GAS-RAD1 Point 10:

XR005 Plant Spec Point Desc.:

1 RM-VS-1 09 CH5 Generic/Cond Oesc.:

RADIOACTIVITY OF RELEASED GASSES AnaloglDlgltal:

A Engr Units/Dlg States:

CPM Engr Units Conversion:

Xe133=1.24E7 CPM/uCllcc Minimum Instr Range:

1.0 Maximum Instr Range:

5.1 E5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

How Processed:

N/A Sensor Location:

SEE UNIQUE SYSTEM DESCRIPTION FIELD AlarmlTrip Set Points:

HIGH 879 CPM >BACKGROUND NI Detector Power Supply Cut-Orf Power Level:

N/A NI Detector Power Supply Turn-ON Power Level:

N/A Instrument Failure Mode:

DEPENDS ON FAILURE MODE Temperature Compensation for DP Transmitters:

N Level Reference Leg:

N/A Unique System Oesc.:

Point Is 1 minute average. Site dose assessment Varies CPM to uCl/cc conversion depending Oil which default source term was selected and decay period. Alarm setpolnt corresponds to 10 CFR 20 Limits at most restrictive receptor per ODeM. RM-1VS-109 monitors for low range noble gases at the discharge of the Auxiliary Building shielded area exhaust fans and at the discharge of the Containment Refueling and Purge Exhaust Fan (during.

refueling). Provides alarms to warn the operator of abnormal releases and.

provides Input to compute integratedtelease data. Ref: Op Manual Chapt~r 43: RM-416-1: Calculation Package ERS-SFL-92-024: CR 04-0548~

1-78

BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:

4/29/2013 Reactor Unit:

BV1 Data Feeder:

ARERAS NRC EROS Parameter:

EFF-GAS-RAD2 Point 10:

XR006 Plant Spec Point Desc.:

1RM-VS-109 CH7 Generic/Cond Desc.:RADIOACTIVITY OF RELEASED GASSES AnaloglDlgltal:

A Engr Units/Dig States:

CPM Engr Units Conversion:

Xe133=3.54E2 CPM/ubllcc Minimum Instr Range:

1.0 Maximum Instr Range:

5.1 E5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

How Processed:

N/A Sensor Location:

SEE UNIQUE SYSTEM DESCRIPTION FIELD Alarmrfrip Set Points:

HIGH <;: 642 CPM >BACKGROUND NI Detector Power Supply Cut-Ofr Power Level:

N/A NI Deteclor Power Supply Turn-ON Power Level:

NfA Instrument Failure Mode:

DEPENDS ON FAILURE MODE Temperature Compensatfon for DP Transmitters:

N Level Reference Leg:

N/A Unique System Desc.:

Point Is 1 minute average. Site dose assessment varies CPM to uCI/cc conversion depending on which default source term was selected and decay period. Alarm setpoint corresponds to a General Emergency (or eight hours.

RM-1VS-109 Channel 7 monitors for mid range noble gases at the discharge of the Auxiliary Building Shielded Area Exhaust Fans and at the discharge of the Containment Refueling and Purge Exhaust Fan (during refueling). This SPING monitor provides alarms to warn the operator of abnormal releases and provides input 10 compute integrated release data. Ref: Op Manuat Chapter 43; RM-416-1; Calculation Package ERS-SFL-92-024; CR 04-05484 1-79

BEAVER VALLEY POWER STATION EROS DATA POINT LIBRARY Date:

4/29/2013 Reactor Unit:

BV1 Data Feeder:

ARERAS NRC EROS Parameter:

EFF-GAS-RAD3 Point 10:

XR007 Plant Spec PoInt Desc.:

1 RM-VS-1 09 CH9 Generic/Cond Desc.:

RADIOACTIVITY OF RELEASED GASSES Analog/Digital:

A Engr Unils/Dig Slates:

CPM Engr Units Conversion:

Xe133=3.95 CPM/uCl/cc Minimum Instr Range:

1.0 Maximum In sIr Range:

5.1E5 Zero Poinl

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

How Processed:

N/A Sensor Location:

SEE UNIQUE SYSTEM DESCRIPTION FIELD AlarmlTrip Set Points:

10.8 NI Detector Pow/lr Supply Cut-Off Power Level:

N/A NI Detector Power Supply Turn-ON Power Level:

N/A Instrument Failure Mode:

DEPENDS ON FAILURE MODE Temperature Compensation for DP Transmitters:

N Level Reference Leg:

N/A Unique System Desc.:

Point is 1 minute average. Site dose assessment varies CPM to tlCl/cc conversion depending on which default source term was selecled and decay period. RM-1VS-109 Channel 9 monitors for high range noble gases at th~

discharge of the Auxiliary Building Shielded Area Exhaust Fans and at th~*

discharge of the Containment Refueling and Purge Exhaust Fan (during refueling). This SPING monitor provides alarms to warn the operator of abnormal releases and provides input to compute Integrated release data.

Ref: Op Manual Chapter 43; RM-416-1; Calculation Package ERS-SFl 024; CR 04-05484 1-80

BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Date:

4/29/2013 Reactor Unit:

BV1 Data Feeder:

ARERAS NRC EROS Parameter:

EFF-GAS-RAD4 Point 10; XR009 Plant Spec Point Desc.:

1RM-VS-110 CH5 Generic/Cond Desc.:

RADIOACTIVITY OF RELEASED GASSES AnaloglDlgllal:. A Engr Unils/Dig States:

CPM Engr Units Conversion:

Xe133"'1.33E7 CPM/uCl/cc Minimum Instr Range:

1.0 Maximum Instr Range:

5.1 E5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

How Processed:

N/A Sensor Location:

SEE UNIQUE SYSTEM DESCRIPTION FJELD AlarmlTrip Set Points:

HIGH 2030 CPM >BACKGROUND NI Detector Power Supply Cut-Off Power Level:

NlA NI Detector Power Supply Turn-ON Power Level:. N/A Instrument Failure Mode:

DEPENDS ON FAILURE MODE Temperature Compensation for DP Transmitters:

N Level Reference Le~: N/A Unique System Dese.:

Point is 1 minute average. Site dose assessment varies CPM to uCl/cc conversion depending on which default source term was selected and decay period. Alarm setpoint corresponds to 10 CFR;W Limits at most restrictive receptor per ODCM. RM-1VS-110 Channel 5 monllors for low range noble gases at the discharge of the Leak Collection Area Exhaust Fans before the Elevated Release Vent. This SPING monitor provides alarms to warn the operator of abnormal releases and provides input to compute integrated release data. Ref: Op Manual Chapter 43; RM-416-1; Calculation Package ERS-SFL-92-024; CR 04-05484 1-81

BEAVER VALLEY POWER STATION EROS DATA POINT LIBRARY Date:

4/29/2013 Reactor Unit:

BV1 Data Feeder:

ARERAS*

NRC EROS Parameter:

EFF-GAS*RAD5 Point 10:

XR010 Plant Spee PoInt Desc.:

1 RM-VS-11 0 CH7 Generic/Cond Desc.:

RADIOACTIVITY OF RELEASED GASSES AnaloglDigital:

A Engr Units/Dig States:

CPM Engr Units Conversion:

Xe133"'3.01 E2 CPM/uCllcc Minimum Instr Range:

1.0 Maximum Instr Range:

5.1 E5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

How Processed:

N/A Sensor Location:

SEE UNIQUE SYSTEM DESCRIPTION FIELD Alarmffrip Set Points:

HIGH <= 766 CPM >BACKGROUND NI Detector Power Supply Cut-Off Power Level:

N/A NI Detector Power Supply Turn-ON Power Level:

N/A Instrument Failure Mode:

DEPENDS ON FAILURE MODE Temperature Compensation for DP Transmitters:

N Level Reference Leg:

N/A Unique System Dese.:

PoInt Is 1 minute average. SIte dose assessment varies CPM to uCllcc conversion depending on which default source term was selected and decflY period. Alarm setpoint corresponds to a General Emergency if the release continues 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />. RM-1VS-110 Channel? monitors for mid range noble gases at the discharge of the Leak Collection Area Exhaust Fans before the Elevated Release Vent. ThIs SPING monitor provides alarms to warn lile operator of abnormal releases and provides input to compute integrated release data. Ref: Calculation Package ERS-SFL-92-024; CR 04:,05484 1-82

BEAVER VALLEY POWER STATION EROS DATA POINT LIBRARY Date:

4/29/2013 Rel:lctor Unit:

,BV1 Data Feeder:

ARERAS NRC EROS Parameter:

EFF-GAS-RAD6 Point 10:

XR011 Plant Spec Point Dese,:

1RM-VS-110 CH9 Generic/Cond Dese.:

RADIOACTIVITY OF RELEASED GASSES

'Anah)'g/Olgital:

A Engr Units/Dig States:

CPM Engr Units Conversion:

Xe133=4.87 CPM/uCllee Minimum Instr Range:

1.0 Maximum Instr Range:

5.1 E5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

How Processed:

N/A Sensor Location:

SEE UNIQUE SYSTEM DESCRIPTION FJELD Alarmffrip Set Points:

18.6 NI Detector Power Supply Cut-Off Power Level:

N/A NI Detector Power Supply Turn-ON Power Level:

N/A Instrument Failure Mode:

DEPENDS ON FAILURE MODE Temperature Compensation for DP Transm!lters:

N Level Reference Leg:

N/A UnIque System Desc.:

Point is 1 minute average. Site dose assessment varies CPM to uClicc conversion depending on whIch default source term was selected and decay period. RM-1VS-110 Channel 9 monitors for high range noble gases at (he discharge of the Leak Collection Area Exhaust Fans before the Elevated Release Vellt. This SPING monitor provides alarms to warn the operator of abnormal releases and provIdes Input to compute integrated release data.

Ref: Op Manual Chapler43; RM-416-1; Calculation Package ERS-SFL 024; CR 04-05484 1-83

BEAVER VAllEY POWER STATION EROS DATA POINT LIBRARY Date:

4/29/2013 Reactor Unit:

BV1 Dat~feeder: ARERAS NRC EROS Parameter:

EXTRA 15 Point 10:

XR013 Plant Spec Point Desc.:

1RM-GW-109 CH5 Generic/Cond Desc.:

RADIOACTIVITY OF RELEASED GASSES Analog/Digital:

A Engr Units/Dig States:

CPM Engr Units Conversion:

Xe133"'1.26E7 CPM/uCllcc Minimum Instr Range:

1.0 Maximum Inslr Range:

5.1 E5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

How Processed:

N/A Sensor Locallon:

SEE UNIQUE SYSTEM DESCRIPTION FIELD AlarmlTrip Set Points:

HIGH 3.6E5 CPM >BACKGROUND NI Detector Power Supply Cui-Off Power Level:

N/A NI Detector Power Supply Turn-ON Power Level:

N/A Instrument Failure Mode:

DEPENDS ON FAILURE MODE Tempera.ture Compensation for DP Transmitters:

N Level Reference Leg:

N/A Unique System Desc.:

Point Is 1 minute average. Site dose assessment varies CPM to uCllcc conversion depending 00 which default source term was selecled and decay period. Alarm selpolot corresponds to 10 CFR 20 Limits at most restrictive receptor per ODCM. RM-1GW-109 Channel 5 monitors for low range noble gases at the discharge of the gaseous waste disposal blowers. This SPING monitor provides alarms 10 warn the operator of abnormal releases and provides input to compute Integrated release data. Ref: Op Manual Chapler 43; RM-419-1; Calculation Package ERS-SFL-92-024; CR 04-05484 1-84

BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY Oate:

4/29/2013 Reactor Unit:

BV1 Oata Feeder:

ARERAS NRC EROS Parameter:

EXTRA 16 Point 10:

XR014 Plant Spec Point Oesc.:

1RM*GW*109 CH?

GenerlC/Cond Oesc.:

RADIOACTIVITY OF RELEASED GASSES Analog/Digital:

A Engr Units/Dig States:

CPM Engr Unlts Conversion:

Xe133=3.00E2 CPMluClIcc Minimum Inslr Range:

1.0 MaxImum Instr Range:

5.1 E5 Zero Point

Reference:

N/A Reference Point NOles:

N/A PROC or SEN~: S Number of Sensors:

How Processed:

N/A Sensor Location:

SEE UNIQUE SYSTEM DESCRIPTION FIELD AlarmlTrip Set Points:

N/A NI Detector Power Supply Cut-Off Power Level:

N/A NI Detector Power Supply Turn*ON Power Level:

N/A Instrument Failure Mode:

DEPENDS ON FAILURE MODE Temperature Compensation for DP Transmitters:

N Level Reference Leg:

N/A Unique System Dese.:

Point is 1 minute average. Site dose assessment varies CPM to uClIce conversion depending on which default sOllrce term was selected and decay period. RM*1GW*109 Channel? monitors for mid range nobie gases at the discharge of the gaseous waste disposal blowers. This SPING monitor provides alarms to warn the operator of abnormal releases and provides Input to compute Integrated release data. Ref: Op Manual Chapter 43; RM-419*1; Calculation Package ERS*SFL*92*024; CR 04-05484 1*85

BEAVER VALLEY POWER STATION EROS DATA POINT LIBRARY Date:

4/2~/2013 Reactor Unit:

BV1 Data Feeder:

ARERAS NRC EROS Parameter:

EXTRA 17 Point 10:

XR015 Plant Spec Point Dese.:

1RM-GW-109 CH9 Generic/Cond Dese.:

RADIOACTIVITY OF RELEASED GASSES Analog/Digital:

A Engr Units/Dig States:

CPM Engr Units Conversion:

Xe133-=:3.95 CPM/uCl/cc Minimum Instr Range:

1.0 Maximum Instr Range:

5.iE5 Zero Point

Reference:

N/A Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

How Processed:

N/A Sensor Location:

SEE UNIQUE SYSTEM DESCRIPTION FIELD AlarmlTrip Set Points:

HIGH i.76E5 CPM >BACKGROUND NI Detector Power Supply Cut-Off Power Level:

N/A NI Detector Power Supply Turn-ON Power Level:

N/A Instrument Failure Mode:

DEPENDS ON FAILURE MODE Temperature Compensation for DP Transmitters:

N Level Reference Leg:

N/A Unique System Desc.:

Point is 1 minute average. Site dose assessment varies CPM to uCI/cc conversion depending on which default source term was selected and decay period. Alarm setpolnt corresponds to a General Emergency If the release continues for eight hours. RM-1GW-109 Channel 9 monitors for High Range noble gases at the discharge of the Gaseous Waste Disposal Blowers. rhe monitor provides alarms to warn the operator of abnormal releases and provides input to compute integrated release data. Ref: Op Manual Chapler 43; RM-419-1; Calculation Package ERS-SFL-92-024; CR 04-05484 1-86