L-03-156, September 2003 Monthly Operating Report for Beaver Valley Units 1 and 2

From kanterella
(Redirected from L-03-156)
Jump to navigation Jump to search

September 2003 Monthly Operating Report for Beaver Valley Units 1 and 2
ML032890076
Person / Time
Site: Beaver Valley
Issue date: 10/08/2003
From: Pearce L
FirstEnergy Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
GL-97-002, L-03-156
Download: ML032890076 (5)


Text

he FENOC Fni.Ene.'gv M Ope Cr Beaver Valley PowerStation P. O. Box 4 Shippingport,PA 15077 L-03-156 October 8, 2003 Beaver Valley Power Station Unit I - Docket No. 50-334, License No. DPR-66 Unit 2 - Docket No. 50-412, License No. NPF-73 Monthly minathk report U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

In accordance with NRC Generic Letter 97-02, "Revised Contents of the Monthly Operating Report", and Unit 1 and 2 Technical Specification 6.9.4, the "Monthly Operating Report" is submitted for Unit 1 and Unit 2 for the month of September, 2003. No regulatory commitments are contained in this submittal.

Respectfully, W. Pearce

-~~~ ~

~~~- -~ ~- - ~~ ~- ~ Vice-President BVPS DTJ/cmg Enclosures cc: NRC Regional Office King of Prussia, PA

.. 'g'-' ... .

jX9 4

UNIT SHUTDOWNS DOCKET NO. 50-334 UNIT NAME BVPS Unit #1 DATE October 1, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: September 2003 No. Date Type Duration Reason Method of Cause / Corrective Actions (Y/M/D) F: Forced (Hours) (1) Shutting S: Scheduled Down (2) Comments NONE.

(1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip I Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E- Operator Training I Ucense Examination 5 - Other (Explain)

F - Administrative G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

1I

6 OPERATING DATA REPORT DOCKET NO.
50-334 UNIT NAME: BVPS UNIT #1 REPORT DATE: 10/01/03 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962
  • * * ** * * * * *
  • C * * * * * *
  • Nokes: Rated thermal power at
  • la. REPORTING PERIOD: SEPTEMBER 2003
  • BVPS-1 was uprated from 2652 MWt*
  • to 2689 KWt on 10/20/01. Net *
1. DESIGN ELECTRICAL RATING (Net e)W: 835
  • MDC was also uprated from *
  • 810 XWe to 821 MWe. *
2. MAX. DEPENDABLE CAPACITY (Net MWe): 821

-g ** ** *--* * ** * *'*

  • C*

THIS MONTH YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 720.0 6551.0 240335.0

3. NO. OF ERS. REACTOR WAS CRITICAL: 720.0 5250.5 165842.0
4. SERVICE HOURS GENERATOR ON LINE: 720.0 5203.9 163315.9
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWE): 602700.0 4157899.0 122813906.0
7. GROSS ELECT. ENERGY GEN. (MWH): 637630.0 4413317.0 131082907.0
8. GROSS THERMAL ENERGY GEN. (MWE): 1934204.0 13462002.0 403733311.5
9. UNIT AVAILABILITY FACTOR (%): 100.0 79.4 69.4
10. UNIT CAPACITY FACTOR (MDC) (%): 102.0 77.3 64.9
11. UNIT FORCED OUTAGE RATE (%): 0.0 1.1 15.3

UNIT SHUTDOWNS DOCKET NO. 50-412 UNIT NAME BVPS Unit #2 DATE October 1, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: September 2003 No. Date Type Duration Reason Method of Cause / Corrective Actions (YV/MD) F: Forced (Hours) (1) Shutting S: Scheduled . Down (2) Comments 1 030913 S 432.0 C 1 The Unit was shutdown for its planned 1Oth refueling outage on 9/13/03.

(1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip / Scram C - Refueling 3 - Automatic Trip I Scram D - Regulatory Restriction 4 - Continuation E - Operator Training I License Examination 5 - Other (Explain)

F - Administrative G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output until 1806 hours0.0209 days <br />0.502 hours <br />0.00299 weeks <br />6.87183e-4 months <br /> on 9/11/03 when a planned reduction to less than 50% output was commenced in order to support Main Steam Safety Valve testing prior to the beginning of the 1 0 th refueling outage. An output of approximately 48% was achieved at 0427 hours0.00494 days <br />0.119 hours <br />7.060185e-4 weeks <br />1.624735e-4 months <br /> on 9/12/03. At 1910 hours0.0221 days <br />0.531 hours <br />0.00316 weeks <br />7.26755e-4 months <br /> on 9/12/03, the

-- Unit began 'to shut down for its-planned-1Ot-hrefuellng outage -The- Unit was removed -from service at 0001 hours1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> on 9/13/03. Mode 2 was entered at 0036 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The Reactor was manually tripped as part of the planned shutdown and Mode 3 was entered at 0043 hours4.976852e-4 days <br />0.0119 hours <br />7.109788e-5 weeks <br />1.63615e-5 months <br /> on 9/13/03. The Unit continued to cool down and depressurize, entering Mode 4 at 0340 hours0.00394 days <br />0.0944 hours <br />5.621693e-4 weeks <br />1.2937e-4 months <br /> and Mode 5 at 0600 hours0.00694 days <br />0.167 hours <br />9.920635e-4 weeks <br />2.283e-4 months <br /> on 9/13/03. The Unit entered Mode 6 at 0859 hours0.00994 days <br />0.239 hours <br />0.00142 weeks <br />3.268495e-4 months <br /> on 9/17/03, and remained in this refueling mode for the remainder of the report period.

OPERATING DATA REPORT DOCKET NO.: 50-412 UNIT NAME: BVPS UNIT 82 REPORT DATE: 10/01/03 COMPLETED BY: DAVID T. JONES C 4ZTELEPEONE: (724) 682-4962

  • * * * * * *
  • 0 * * * * * * * *
  • REPORTING PERIOD: SEPTEMBER 2003
  • Scten: Rated thermal power at
  • la.
  • BVPS-2 was uprated from 2652 MWt*
1. DESIGN ELECTRICAL RATING (Net MWe): 836
  • to 2689 Mwt on 10/30/01. Net *
  • MDC was also uprated from *
2. MAX. DEPENDABLE CAPACITY (Net NWe): 831
  • 820 NWe to 831 FWe.
  • THIS MONTE YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 720.0 6551.0 139118.0
3. NO. OF ERS. REACTOR WAS CRITICAL: 288.6 6119.6 115674.7
4. SERVICE HOURS GENERATOR ON LINEs 288.0 6119.0 114945.5
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWS)t 224608.0 5089493.0 90271896.0
7. GROSS ELECT. ENERGY GEN. (KWH)t 238873.0 5354950.0 95386995.0
8. GROSS THERMAL ENERGY GEN. (KWH)t 733841.0 16309075.0 290908686.0
9. UNIT AVAILABILITY FACTOR (t): 40.0 93.4 82.6
10. UNIT CAPACITY FACTOR (MDC) Ct): 37.5 93.5 78.8
11. UNIT FORCED OUTAGE RATE (t): 0.0 0.0 9.3

Text

he FENOC Fni.Ene.'gv M Ope Cr Beaver Valley PowerStation P. O. Box 4 Shippingport,PA 15077 L-03-156 October 8, 2003 Beaver Valley Power Station Unit I - Docket No. 50-334, License No. DPR-66 Unit 2 - Docket No. 50-412, License No. NPF-73 Monthly minathk report U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

In accordance with NRC Generic Letter 97-02, "Revised Contents of the Monthly Operating Report", and Unit 1 and 2 Technical Specification 6.9.4, the "Monthly Operating Report" is submitted for Unit 1 and Unit 2 for the month of September, 2003. No regulatory commitments are contained in this submittal.

Respectfully, W. Pearce

-~~~ ~

~~~- -~ ~- - ~~ ~- ~ Vice-President BVPS DTJ/cmg Enclosures cc: NRC Regional Office King of Prussia, PA

.. 'g'-' ... .

jX9 4

UNIT SHUTDOWNS DOCKET NO. 50-334 UNIT NAME BVPS Unit #1 DATE October 1, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: September 2003 No. Date Type Duration Reason Method of Cause / Corrective Actions (Y/M/D) F: Forced (Hours) (1) Shutting S: Scheduled Down (2) Comments NONE.

(1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip I Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E- Operator Training I Ucense Examination 5 - Other (Explain)

F - Administrative G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

1I

6 OPERATING DATA REPORT DOCKET NO.
50-334 UNIT NAME: BVPS UNIT #1 REPORT DATE: 10/01/03 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962
  • * * ** * * * * *
  • C * * * * * *
  • Nokes: Rated thermal power at
  • la. REPORTING PERIOD: SEPTEMBER 2003
  • BVPS-1 was uprated from 2652 MWt*
  • to 2689 KWt on 10/20/01. Net *
1. DESIGN ELECTRICAL RATING (Net e)W: 835
  • MDC was also uprated from *
  • 810 XWe to 821 MWe. *
2. MAX. DEPENDABLE CAPACITY (Net MWe): 821

-g ** ** *--* * ** * *'*

  • C*

THIS MONTH YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 720.0 6551.0 240335.0

3. NO. OF ERS. REACTOR WAS CRITICAL: 720.0 5250.5 165842.0
4. SERVICE HOURS GENERATOR ON LINE: 720.0 5203.9 163315.9
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWE): 602700.0 4157899.0 122813906.0
7. GROSS ELECT. ENERGY GEN. (MWH): 637630.0 4413317.0 131082907.0
8. GROSS THERMAL ENERGY GEN. (MWE): 1934204.0 13462002.0 403733311.5
9. UNIT AVAILABILITY FACTOR (%): 100.0 79.4 69.4
10. UNIT CAPACITY FACTOR (MDC) (%): 102.0 77.3 64.9
11. UNIT FORCED OUTAGE RATE (%): 0.0 1.1 15.3

UNIT SHUTDOWNS DOCKET NO. 50-412 UNIT NAME BVPS Unit #2 DATE October 1, 2003 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: September 2003 No. Date Type Duration Reason Method of Cause / Corrective Actions (YV/MD) F: Forced (Hours) (1) Shutting S: Scheduled . Down (2) Comments 1 030913 S 432.0 C 1 The Unit was shutdown for its planned 1Oth refueling outage on 9/13/03.

(1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip / Scram C - Refueling 3 - Automatic Trip I Scram D - Regulatory Restriction 4 - Continuation E - Operator Training I License Examination 5 - Other (Explain)

F - Administrative G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output until 1806 hours0.0209 days <br />0.502 hours <br />0.00299 weeks <br />6.87183e-4 months <br /> on 9/11/03 when a planned reduction to less than 50% output was commenced in order to support Main Steam Safety Valve testing prior to the beginning of the 1 0 th refueling outage. An output of approximately 48% was achieved at 0427 hours0.00494 days <br />0.119 hours <br />7.060185e-4 weeks <br />1.624735e-4 months <br /> on 9/12/03. At 1910 hours0.0221 days <br />0.531 hours <br />0.00316 weeks <br />7.26755e-4 months <br /> on 9/12/03, the

-- Unit began 'to shut down for its-planned-1Ot-hrefuellng outage -The- Unit was removed -from service at 0001 hours1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> on 9/13/03. Mode 2 was entered at 0036 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The Reactor was manually tripped as part of the planned shutdown and Mode 3 was entered at 0043 hours4.976852e-4 days <br />0.0119 hours <br />7.109788e-5 weeks <br />1.63615e-5 months <br /> on 9/13/03. The Unit continued to cool down and depressurize, entering Mode 4 at 0340 hours0.00394 days <br />0.0944 hours <br />5.621693e-4 weeks <br />1.2937e-4 months <br /> and Mode 5 at 0600 hours0.00694 days <br />0.167 hours <br />9.920635e-4 weeks <br />2.283e-4 months <br /> on 9/13/03. The Unit entered Mode 6 at 0859 hours0.00994 days <br />0.239 hours <br />0.00142 weeks <br />3.268495e-4 months <br /> on 9/17/03, and remained in this refueling mode for the remainder of the report period.

OPERATING DATA REPORT DOCKET NO.: 50-412 UNIT NAME: BVPS UNIT 82 REPORT DATE: 10/01/03 COMPLETED BY: DAVID T. JONES C 4ZTELEPEONE: (724) 682-4962

  • * * * * * *
  • 0 * * * * * * * *
  • REPORTING PERIOD: SEPTEMBER 2003
  • Scten: Rated thermal power at
  • la.
  • BVPS-2 was uprated from 2652 MWt*
1. DESIGN ELECTRICAL RATING (Net MWe): 836
  • to 2689 Mwt on 10/30/01. Net *
  • MDC was also uprated from *
2. MAX. DEPENDABLE CAPACITY (Net NWe): 831
  • 820 NWe to 831 FWe.
  • THIS MONTE YEAR TO DATE CUMULATIVE 3a. HOURS IN REPORTING PERIOD: 720.0 6551.0 139118.0
3. NO. OF ERS. REACTOR WAS CRITICAL: 288.6 6119.6 115674.7
4. SERVICE HOURS GENERATOR ON LINEs 288.0 6119.0 114945.5
5. UNIT RESERVE SHUTDOWN HOURS: 0.0 0.0 0.0
6. NET ELECTRICAL ENERGY GEN. (MWS)t 224608.0 5089493.0 90271896.0
7. GROSS ELECT. ENERGY GEN. (KWH)t 238873.0 5354950.0 95386995.0
8. GROSS THERMAL ENERGY GEN. (KWH)t 733841.0 16309075.0 290908686.0
9. UNIT AVAILABILITY FACTOR (t): 40.0 93.4 82.6
10. UNIT CAPACITY FACTOR (MDC) Ct): 37.5 93.5 78.8
11. UNIT FORCED OUTAGE RATE (t): 0.0 0.0 9.3