ENS 55602
ENS Event | |
|---|---|
14:07 Sep 30, 2021 | |
| Title | 60-DAY Optional Telephonic Notification for an Invalid Emergency Diesel Generator Actuation |
| Event Description | This 60-day telephone notification is being made per the reporting requirements specified by 10 CFR 50.73(a)(2)(iv)(A) and 10 CFR 50.73(a)(1) to describe an invalid specific system actuation.
At 0907 [EDT] on September 30, 2021, with Unit 1 in Mode 1, at 100 percent power, an actuation of the 1-1 emergency diesel generator (EDG) occurred during loss of voltage relay functional testing. The 1-1 EDG auto-start was due to human error during performance of the test procedure when the bus 1AE undervoltage signal was improperly defeated and a simulated undervoltage signal was applied. No actual undervoltage condition was present during this event. The 1-1 EDG automatically started as designed when the bus undervoltage signal was received. This was a complete actuation of an EDG to start and come to rated speed, and all affected systems functioned as expected in response to the actuation. Following the actuation, the relays were restored and the 1-1 EDG was shut down in accordance with plant procedures. This event is considered an invalid system actuation reportable under 10 CFR 50.73(a)(2)(iv)(A). The actuation was not initiated in response to actual plant conditions or parameters and was not a manual initiation. Therefore, in accordance with 10 CFR 50.73(a)(1), this telephone notification is provided within 60 days after discovery of the event instead of submitting a written Licensee Event Report. There was no impact on the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified. |
| Where | |
|---|---|
| Beaver Valley Pennsylvania (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.73(a)(1), Submit an LER, Invalid Actuation | |
| Time - Person (Reporting Time:+1290.05 h53.752 days <br />7.679 weeks <br />1.767 months <br />) | |
| Opened: | Kent Sloan 09:10 Nov 23, 2021 |
| NRC Officer: | Thomas Kendzia |
| Last Updated: | Nov 23, 2021 |
| 55602 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Beaver Valley with 10 CFR 50.73(a)(1), Submit an LER | |
WEEKMONTHYEARENS 556022021-09-30T14:07:00030 September 2021 14:07:00
[Table view]10 CFR 50.73(a)(1), Submit an LER 60-DAY Optional Telephonic Notification for an Invalid Emergency Diesel Generator Actuation ENS 468172011-03-15T21:16:00015 March 2011 21:16:00 10 CFR 50.73(a)(1), Submit an LER Invalid Actuation of the Standby Service Water Pump ENS 468162011-03-07T15:18:0007 March 2011 15:18:00 10 CFR 50.73(a)(1), Submit an LER Invalid Actuation of the Auxiliary Feedwater System ENS 450992009-05-06T17:52:0006 May 2009 17:52:00 10 CFR 50.73(a)(1), Submit an LER Automatic Actuation of Rps, Eccs and Edg Generated by an Invalid Actuation Signal ENS 450012009-04-20T05:53:00020 April 2009 05:53:00 10 CFR 50.73(a)(1), Submit an LER Unexpected Start of the Steam Driven Auxiliary Feedwater Pump During Plant Cooldown ENS 446612008-10-16T14:07:00016 October 2008 14:07:00 10 CFR 50.73(a)(1), Submit an LER Invalid Actuation of Steam Driven Aux Feed Pump ENS 411192004-09-10T21:30:00010 September 2004 21:30:00 10 CFR 50.73(a)(1), Submit an LER Invalid Actuation of Steam Driven Auxiliary Feedwater Pump 2021-09-30T14:07:00 | |