ENS 52438
ENS Event | |
|---|---|
16:30 Dec 15, 2016 | |
| Title | Offsite Notification Made for Potential Fuel Oil Leakage |
| Event Description | On 12/14/16 at 1206 [EST], 0-PT-89.9K (underground fuel-oil piping pressure test), was performed UNSAT after a failed attempt to maintain pressure in the supply line to the Unit 2 'H' Emergency Diesel Generator (EDG) Day Tank. The exact source of the leakage is unknown at this time but is reasonable to believe some fuel oil was released underground. The associated Fuel Oil line is currently tagged out and isolated. This condition is reportable to the Virginia Department of Environmental Quality [VA DEQ] as part of the Underground Storage Tank Program. Pressure tasting of the other EDG fuel oil supply lines has been previously completed satisfactorily. The 2H EDG remains Operable as the redundant fuel oil transfer pump and its fuel oil piping are Operable and capable of maintaining adequate day tank level. The VA DEQ was notified of this condition
at 1130 [EST] on 12/15/16. This event is reportable in accordance with 10CFR50.72(b)(2)(xi) for 'Any event or situation, related to the health and safety of the public or onsite personnel, or protection of the environment, for which a news release is planned or notification to other government agencies has been or will be made.' The licensee has notified the NRC Resident Inspector and will notify Louisa County.
This is a follow-up report to Event Number 52438, made on 12/15/2016, regarding offsite notification to the Virginia Department of Environmental Quality for potential fuel oil leakage from the supply line to the Unit 2H Emergency Diesel Generator (EDG) Day Tank. During investigation of the potential fuel oil leak from the 2HB EDG Day Tank supply line (as previously reported in EN 52438), the 2HA fuel oil line, which runs close to the 2HB line, was disturbed and began to leak a mist of fuel oil. The fuel oil was contained in the area and was being cleaned via vacuum truck as it was leaking. Personnel at the scene noted the soil was not contaminated with fuel oil initially and saw the leak start on 2HA line. It has been estimated that less than one gallon of fuel oil was released to the surrounding soil during troubleshooting of the leak. The fuel oil was immediately vacuumed. The 2HA line was isolated and the leakage was stopped. The 2HA line is to be repaired and tested. The 2H EDG remains available, however, it is considered inoperable at this time. Investigation of the 2HB fuel oil line continues. The condition of the 2HA fuel oil line was reported to the Virginia Department of Environmental Quality [VA DEQ] as part of the Underground Storage Tank Program on 12/28/16. Therefore, this event is reportable in accordance with 10CFR50.72(b)(2)(xi) for 'Any event or situation, related to the health and safety of the public or onsite personnel, or protection of the environment, for which a news release is planned or notification to other government agencies has been or will be made.' The licensee has notified the NRC Resident Inspector and will notify Louisa County. Notified R2DO (Rose). |
| Where | |
|---|---|
| North Anna Virginia (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release | |
| Time - Person (Reporting Time:+-2.67 h-0.111 days <br />-0.0159 weeks <br />-0.00366 months <br />) | |
| Opened: | Don Taylor 13:50 Dec 15, 2016 |
| NRC Officer: | Dong Park |
| Last Updated: | Dec 28, 2016 |
| 52438 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 578162025-07-17T15:00:00017 July 2025 15:00:00
[Table view]10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification ENS 567432023-09-18T18:20:00018 September 2023 18:20:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification ENS 566182023-07-11T19:30:00011 July 2023 19:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification ENS 563742023-02-20T21:18:00020 February 2023 21:18:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to State Agency ENS 560732022-08-27T14:15:00027 August 2022 14:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Turbine Trip Due to Main Transformer Fire ENS 555702021-11-10T20:15:00010 November 2021 20:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Pcb Oil Spill ENS 524382016-12-15T16:30:00015 December 2016 16:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Made for Potential Fuel Oil Leakage ENS 508842015-03-13T13:28:00013 March 2015 13:28:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Osha Due to Onsite Plant Employee Passing Away ENS 490722013-05-27T19:45:00027 May 2013 19:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Drowning at Lake Anna ENS 476822012-02-21T18:45:00021 February 2012 18:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Tritium Identified Onsite Above the Voluntary Reporting Threshold ENS 476652012-02-15T17:44:00015 February 2012 17:44:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification of Sewage System Release ENS 473452011-10-14T18:40:00014 October 2011 18:40:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Bearing Cooling Water Discharge Into Lake ENS 471982011-08-25T20:10:00025 August 2011 20:10:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Notification to Offsite Agency Regarding an Onsite Oil Spill ENS 463772010-10-29T18:00:00029 October 2010 18:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Increase in Tritium Levels in a Ground Water Sample ENS 456232010-01-11T20:10:00011 January 2010 20:10:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Water Seepage on an Onsite Structure ENS 455582009-12-10T15:35:00010 December 2009 15:35:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Bearing Cooling Water Discharged Into Lake ENS 449722009-04-06T16:30:0006 April 2009 16:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Truck Engine Fire with Contaminated Material in Trailer ENS 413222005-01-10T18:45:00010 January 2005 18:45:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Federal Energy Regulatory Commission ENS 406372004-04-03T18:14:0003 April 2004 18:14:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Notification to Virginia Deq Concerning a Chemical Spill 2025-07-17T15:00:00 | |