ENS 46654
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
03:59 Mar 4, 2011 | |
| Title | Techncial Specification Required Shutdown Due to Inoperable Hpci |
| Event Description | At 2259 EST, Susquehanna Unit 1 commenced a TS Required shutdown for High Pressure Coolant Injection (HPCI) T.S. 3.5.1. Due to a suspected steam leak, the HPCI Inboard Steam Supply Valve HV155F002 was closed to attempt to identify and isolate an unknown drywell leakage condition. After closing the HV155F002, a detectable change in drywell leak rate occurred, therefore, HV155F002 was left closed. Closing HV155F002 makes HPCI INOP and UNAVAILABLE.
TS 3.5.1 was entered for this condition on 2/25/2011 at 2136 EST. LCO completion time for T.S. 3.5.1 entry is 3/11/2011 at 2136 EST. The licensee has notified the NRC Resident Inspector and State authorities. The licensee also anticipates issuing a press release. |
| Where | |
|---|---|
| Susquehanna Pennsylvania (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
| Time - Person (Reporting Time:+-4.53 h-0.189 days <br />-0.027 weeks <br />-0.00621 months <br />) | |
| Opened: | Ron Fry 23:27 Mar 3, 2011 |
| NRC Officer: | Bill Huffman |
| Last Updated: | Mar 3, 2011 |
| 46654 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (99 %) |
| After | Power Operation (86 %) |
WEEKMONTHYEARENS 540782019-05-22T06:56:00022 May 2019 06:56:00
[Table view]10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Technical Specification Required Shutdown ENS 519832016-06-06T09:56:0006 June 2016 09:56:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown, 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Isolable Leakage Identified from Seal Water Line Weld Inside Rcs Pressure Boundary ENS 485952012-12-14T18:50:00014 December 2012 18:50:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown - Control Structure Chillers Inoperable ENS 480362012-06-19T21:20:00019 June 2012 21:20:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown, 10 CFR 50.72(b)(3)(ii)(A), Seriously Degraded Mode Change Required by Technical Specifications ENS 466542011-03-04T03:59:0004 March 2011 03:59:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Techncial Specification Required Shutdown Due to Inoperable Hpci ENS 437222007-10-13T06:20:00013 October 2007 06:20:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Inoperable Control Rods ENS 423852006-03-04T10:17:0004 March 2006 10:17:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Control Rods Declared Inoperable During Shutdown ENS 420932005-10-29T03:32:00029 October 2005 03:32:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Inoperable Control Rods ENS 415852005-04-10T15:50:00010 April 2005 15:50:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Failed 125V Dc Battery Charger 2019-05-22T06:56:00 | |