ABB, Inc. notified the NRC of solid state relays that failed to comply with
ABB manufacturing specifications. Subject relays are 27H catalog numbers
411R0175-DP-1E and
411R0175-1E. The failure to comply is in regard to improper installation of a jumper on the main printed circuit board (PCB) of the relay. Manufacturing specifications require the jumper
leads to extend far enough beyond the surface plane of the PCB to ensure proper connection. The jumper enables the relay to provide high-speed, instantaneous trip capability. If the jumper were not installed properly, the trip function may be erratic. The subject relays were manufactured between October 1, 2009 and September 9, 2010.
Two safety-related versions of this relay have been purchased by South Texas Project. ABB, Inc. is investigating whether any nuclear plants have purchased the affected relays for use in non safety-related applications.
ABB will be notifying South
Texas Project of this defect.