V.C. Summer Nuclear Station is notifying the NRC in accordance with
NRC Bulletin 80-24, regarding
Service Water System leakage into containment.
At approximately 0310 on 05/03/09, Reactor Building sump sample analyses, in response to increasing sump level, indicated a probable leak from the Industrial Cooling Water System at 0.38 gpm.
In accordance with Bulletin 80-24, a 14 day written report will be submitted.
The licensee is continuing to monitor at this time. A corrective action plan to definitively identify where the leak is coming from will be developed.
The licensee notified the NRC Resident Inspector. The licensee plans on notifying State of South Carolina and the counties of Fairfield, Richland, Lexington, and Newberry EP representatives.
- * * RETRACTION ON 5/7/2009 AT 1705 FROM JASON WEATHERSBY TO MARK ABRAMOVITZ * * *
On 05/06/2009, a reactor building entry was made, and the previously reported leak was determined to be from the Industrial Cooling Water system. The location of the leak was from a mechanical seal of a non-safety rod position indication equipment cabinet cooling pump. No degradation of a containment boundary exists. EN 45039 is being retracted, and a 14 day report will not be submitted.
The licensee notified the NRC Resident Inspector.
Notified the R2DO (Guthrie).