Purpose:
The purpose of this Fisher Information Notice (FIN) is to alert FPL that as of 20 June, 2008, Fisher Controls International LLC became aware of the possibility of a situation which may affect the performance of the applicable equipment.
Equipment Affected by This Information Notice:
Items provided to FPL - Turkey Point per Fisher Order Number 010-A001017058,Item 0001, (FPL Order 00108848, Rev. 3). This equipment included 3" CL150 Fisher V150 valve assemblies (quantity 2). The equipment is identified by Fisher Serial Numbers 18497294 and 18497295 (FPL Tag Number 04224971).
Applicability:
This notice applies only to the subject equipment supplied by Fisher Controls International LLC, identified above, that was provided to FPL-Turkey Point. Fisher Controls has determined that the subject items did not meet the material requirements specified by the FPL Order 00108848, Rev. 3. Specifically the discrepancies are:
- TFE packing was provided instead of graphite packing.
- TCM seal rings were provided instead of HD metal seal rings.
The difference in these parts will also require that a different seal protector ring be provided.