ENS 44295
ENS Event | |
---|---|
15:00 Jun 13, 2008 | |
Title | Part 21 Report Involving Commercial Grade Relay Contacts Containing Potential Defects |
Event Description | The following Part 21 notification was received via fax:
On June 13, 2008, AmerGen Energy Company, LLC (AmerGen) completed a reportability determination which concluded that relay contacts contained an underlying design vulnerability that created a failure mode, and were reportable under Part 21, since the underlying vulnerability could create a substantial safety hazard. The relay contacts are Commercial Grade items dedicated by AmerGen. The relay contacts are provided by Joslyn Clark Controls Inc. (formerly AO Smith) as Normally Closed (N/C) open top contact assemblies (part numbers KPM-44, KPM-46, KPM-6A, and KPM-4A). These contacts are used in safety related applications, primarily in the engineered safeguards actuation system (ESAS). They are also used in safety related applications in the makeup/high pressure injection (HPI) system, main steam system, and the heat sink protection system (HSPS). The underlying vulnerability associated with the N/C Joslyn Clark contact is the design of the nylon contact arm. The design allows the contact to become configured incorrectly during assembly or following maintenance. If installed improperly, the moving contactor can hang up on the lip of the slot in the nylon actuator. The hang up results in failure of the contact to fully close and perform its function. Following proper assembly, the N/C Joslyn Clark contacts will not become hung-up during normal relay operation. As a result of this exposed design vulnerability, the Commercial Grade Dedication (CGD) plans as well as the maintenance procedures have been enhanced to prevent a relay from being placed into service with an improperly configured contact. Extent of condition reviews performed to date on relays installed in the plant, have not identified any of these deficiencies. The NRC resident inspector was notified of this part 21 notification by the licensee. |
Where | |
---|---|
Three Mile Island ![]() Pennsylvania (NRC Region 1) | |
Reporting | |
10 CFR 21.21 | |
Time - Person (Reporting Time:+-2.92 h-0.122 days <br />-0.0174 weeks <br />-0.004 months <br />) | |
Opened: | Adam Miller 12:05 Jun 13, 2008 |
NRC Officer: | Steve Sandin |
Last Updated: | Jun 13, 2008 |
44295 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 44295\u003C/a\u003E - \u003Ca href=\"/Three_Mile_Island\" title=\"Three Mile Island\"\u003EThree Mile Island\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EPart 21 Report Involving Commercial Grade Relay Contacts Containing Potential Defects\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 44295 - Three Mile Island\n","link":"","lat":40.154719444444446,"lon":-76.72520833333333,"icon":"/w/images/b/be/Constellation_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 442952008-06-13T15:00:00013 June 2008 15:00:00
[Table view]10 CFR 21.21 Part 21 Report Involving Commercial Grade Relay Contacts Containing Potential Defects 2008-06-13T15:00:00 | |