In March 2005, battery cell internal resistance for an
EDG battery bank revealed five cells with abnormal resistance. "There was one cell for which no reading could be obtained and was replaced immediately. A second cell had a reading that was nearly four times the average of the associated string and was subsequently replaced as a proactive measure during the
EDG maintenance outage. Three (3) other cells were noted with higher than average readings that are not considered to be operability concerns. In total, five (5) cells out of a total of 240 were found with higher than expected internal resistance values.
The failed battery was destructively tested revealing significant corrosion within the battery. The unit-2 batteries have been replaced. The unit-1 batteries will be replaced in the fall 2007 outage.
Manufacturer: Enersys (Exide)
Model: 3CA-5
Serial Number: beginning with 05
The licensee notified the NRC Resident Inspector.