ENS 42854
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
22:15 Sep 21, 2006 | |
| Title | Oscillation Power Range Monitors (Oprms) Inoperable |
| Event Description | On September 14, 2006, the Plant Staff was notified by General Electric (GE) via a draft Safety Communication SC06-010 of a potential non-conservative setting of the OPRM Enabled Region Drive Flow Setpoint when the plant is in Single Reactor Recirculation Loop Operations. On September 21, 2006, at 1815 hours0.021 days <br />0.504 hours <br />0.003 weeks <br />6.906075e-4 months <br />, based on available information, it was conservatively determined that all four OPRM channels were inoperable due to their current flow setpoint settings and uncertainties associated with OPRM enabling.
The OPRM instrumentation provides inputs to the Reactor Protection System. The OPRM instrumentation is relied upon for providing a safe shutdown safety function when operating during an unstable power to flow condition. Operations personnel entered Technical Specification LCO 3.3.1.3 Action B.1 to initiate an alternate method to detect and suppress thermal hydraulic instability oscillations. This event is being reported as a condition that could have prevented the safety function of structures or systems required to shut down the reactor and maintain it in a safe shutdown condition. These actions and this report are based on preliminary information. Updates will be provided as necessary as additional information becomes available. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Perry Ohio (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor | |
| Time - Person (Reporting Time:+-2.03 h-0.0846 days <br />-0.0121 weeks <br />-0.00278 months <br />) | |
| Opened: | David O'Donnell 20:13 Sep 21, 2006 |
| NRC Officer: | Jason Kozal |
| Last Updated: | Sep 21, 2006 |
| 42854 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |