At 2300 on October 24, 2005, both unit 3 and unit 4 start up transformers were declared
inoperable and
Tech Spec 3.8.1.1.e action statements were entered. With both units being energized from their respective start-up transformers, the high voltage limit is 241.5kV in accordance with 0-ONOP-004.6, Degraded
Switchyard Voltage. System Operations reported
switchyard voltage at 243.5 kV and 242.5 kV for unit 3 and unit 4 respectfully. System Operations was requested to lower
switchyard voltage to within limits. At 0015 on October 25, 2005,
switchyard voltage being lowered to within the
switchyard limits and both start-up transformers were declared
operable. The high
switchyard voltage is due to
hurricane Wilma's impact on the
Florida service area that has [led] to low system load with cooler weather conditions.
The NRC Resident Inspector has been notified.