On August 22,2003, at 0201 Central Time, while operating at 100 percent power, Grand Gulf Nuclear Station experienced an
invalid actuation of the 'A' Standby
Service Water (
SSW) System. A failed DC/DC converter power supply in Panel 1H22P400 for the Division 1 Diesel Generator (
DG) resulted in a faulty
DG speed monitor signal indicating
DG speed greater than 450 revolutions per minute (
RPM). The
DG was not running since it was already
inoperable due to a planned outage. The event occurred during restoration activities to prepare the
DG for retest. The invalid
DG start signal caused the outside air fan and
SSW 'A' to auto start as designed to support
DG operation.
SSW 'A' started and functioned as designed. No other actuations occurred and all support systems functioned properly.
The licensee notified the NRC Resident Inspector.