ELV-01675, Responds to Violations Noted in Insp Rept 50-424/90-05 on 900217-0330.Corrective Actions:Locked Valve Procedure Revised to Eliminate Utilization of Hold Tag on Valves Required by Tech Specs to Be Secured in Position
| ML20043B598 | |
| Person / Time | |
|---|---|
| Site: | Vogtle |
| Issue date: | 05/24/1990 |
| From: | Hairston W GEORGIA POWER CO. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| ELV-01675, ELV-1675, NUDOCS 9005300262 | |
| Download: ML20043B598 (3) | |
Text
.
N Acorgia Pcmor Company
' 333 Pie:dmont Amnue t
- ' ' twanta. Georita 30308 Totephone 404 5%3195 Mahng Atkkets
. 40 inverness Center Parkwtiy Post 01fice Box 1295 i
Bamingham, Alatiama 3520t Telephor* 205 BGB 5581
-[
May 24, 1990 t'wem*o< se'"
[
W. O. Hairston, til Senior Vce Presicient L
Nuclear Opornhons.
ELV-01675 0391 q
Docket No.
50-424 U. S; Nuclear Regulatory Commission
. ATTN: Document Control Desk Washington, D.'C.
20555' Centlemen:
V0GTLE. ELECTRIC GENERATING PLANT F
REPLY TO A-NOTICE OF' VIOLATION Pursuant to 10 CFR 2.201, Georgia Power Company (GPC) submits the enclosed o
information in response to a violation identified in Inspection Report 50-424/90-05 which concerns the inspection conducted by Mr. R.: F. Aiello.and-Mr.
R. D. Starkey of the NRC from February 17 - March 30,.1990.
In the enclosure, transcription of the violation: precedes GPC's response.
Please contact this office if you have any questions.
Sincerely, Yh/l W. G. Hairston,'III i
WGH,III/ JAB /gm
Enclosure:
Violation 50-424/90-05-01 ard GPC Response.
xc: Georaia Power Comoany Mr. C. K. McCoy Mr. G. Bockhold, Jr.
Mr. R. M. Odom Mr. P. D. Rushton NORMS U. 'S. Nuclear Reculatory Commissign Mr. S.. D. Ebneter, Regional Admir.istrator Mr. T. A.' Reed, Licensing Project Manager, NRR Mr. R. F. Aiello, Senior Resident Inspector, Vogtle
}
9005300262 900524 PDR ADOCK 05000424 O
(( 0l PDC Il/
/
r m
ENCLOSURE V0GTLE ELECTRIC GENERATING PLANT - UNIT 1 NRC NOTICE OF VIOLATION 50-424/90-05-01 AND GPC RESPONSE
" Technical Specification 3.4.1.4.2.c, requires that, in Mode 5 with reactor coolant loops not filled, Reactor Makeup Water Storage Tank discharge valves, 1-1208-U4-175,176,177, and 183 be closed and secured in position.'
Contrary to the above, on February 26,-1990, with Unit _1 in Mode 5 and RCS level I
at 195 feet 5 inches, valve 1-1208-U4-176 was closed but was not mechanically l
secured in the closed position.
1 This a Severity Level. IV violation (Supplement I)".
t RESPONSE TO VIOLATION 50-424/90-05-01 l'
l Admission or Denial of the Violation:
~
~'
The violation occurred as-stated.
Reason for the Violation:
As stated in the Notice ~of Violation, Technical Specification 3.4.1.4.2.c r
requires the-subject valve to be-closed and secured in-position.
Similarly, Technical Specification (TS) 3.6.1.7 requires the 24-inch containment purge supply and exhaust isolation. valves.to be closed and sealed' closed. The bases t
for TS 3.6.1.7 state that sealed closed isolation. valves are isolation' valves under administrative control to assure they cannot be inadvertently opened. The administrative controls, which constituted the locked valve policy, permitted clearance " hold tags" to be utilized to-secure small vakes which cannot feasibly be locked. However, Surveillance Requirement 4.4.1.4.2.2 requires the-subject valve to be secured in position:by mechanical stops. Therefore, the administrative controls were less than adequate which resulted in the violation.
Corrective Steos Which Have Been Taken and the Results Achieved:-
-The subject valve was wired in the closed position to provide a " mechanical stop" as required by Surveillance Requirement 4.4.1.4.2.2.
Corrective Steos Which Will Be Taken To Avoid Further Violations:-
To preclude any further violations, the following corrective steps will be-taken:-
o The-locked valve procedure will be revised by 9-15-90, to eliminate utilization of a " hold tag" on valves that are required by the Technical Specifications to be secured in position.
E-1-1
ENCLOSURE ~(CONTINUED)
V0GTLE ELECTRIC GENERATING PLANT - UNIT 1 l-NRC NOTICE OF VIOLATION 50-424/90-05-01 AND GPC RESPONSE o
A review of valves which are required by the Technical Specifications.to, i
be secured will. be performed by 9-15-90 to ensure a' locking mechanism is
(-
in place, t
o Any valve found by this review which is )resently secured by. hold tags-E and is required to be secured by the Tecinical Specifications will be.
provided with en appropriate locking mechanism.. This action will be completed by-9-15-90.
Date When Full Comoliance Will Be Achieved:
[
Full compliance was achieved with-the crimping of a steel cable' through-the -
drilled holes in the valve handle'to mechanically secure the subject valve.:
s This was accomplished on February 26, 1990.
.t f
4 I
I E-1-2 b