On September 16, 2017 at approximately 13:30, when performing a swap to place the Unit 2 "A" Reactor Building Equipment Compartment Exhaust fan (2V206A) in service, the fan tripped unexpectedly after being placed in service.
Reactor Building differential pressure lowered to As a result, Technical Specification 3.6.4.1 Surveillance Requirement 3.6.4.1.1 was not met due to loss of Secondary Containment differential pressure. The 2V206B fan was placed back in service and Reactor Building differential pressure was restored to above 0.25 inches WG.
The condition is being reported in accordance with 10 CFR 50.73(a)(2)(v)(C) as an event or condition that could have prevented fulfillment of a safety function.
The failure was not able to be replicated during investigation. The direct cause is inconclusive. A failure modes analysis was completed to identify the likely cause of the fan trip.
Potential causes include one of the following: the flow control damper linkages binding, the low flow switch failing to reset, or the "A" and "B" fans running in parallel long enough to result in a low flow trip. A corrective action was identified to address each of these potential causes including greasing the linkages, testing the low flow switch reset and replacing the switch if necessary, and enhancing the affected procedures.
There were no actual consequences to the health and safety of the public as a result of this event. |
comments regarding burden estimate to the Information Services Branch (T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
,7c15
3. LER NUMBER
CONDITIONS PRIOR TO EVENT
Unit 1 — Mode 1, approximately 100 percent Rated Thermal Power Unit 2 — Mode 1, approximately 100 percent Rated Thermal Power There were no structures, systems, or components that were inoperable at the start of the event that contributed to the event.
EVENT DESCRIPTION
On September 16, 2017, a plant operator identified belts associated with the Unit 2 "B" Reactor Building Equipment Compartment Exhaust fan (2V206B) [EIIS System/Component Identifier: VA/FAN] slipping and a hot burnt rubber smell in the area. The operator recommended swapping fans to place the "A" fan (2V206A) in service.
At approximately 13:30, when performing the swap to place the 2V206A fan in service, the 2V206A fan tripped unexpectedly after being placed in service. Reactor Building [EIIS System Code: NG] differential pressure lowered to Surveillance Requirement 3.6.4.1.1 was not met due to loss of Secondary Containment differential pressure. The 2V206B fan was placed back in service and Reactor Building differential pressure was restored to above 0.25 inches WG.
On September 16, 2017, at 15:53, this condition was reported (ENS#52973) in accordance with 10 CFR 50.72(b)(3)(v)(C) as an event or condition that, at the time of discovery, could have prevented the fulfillment of the safety function to mitigate the consequences of an accident by controlling the release of radioactive material. Susquehanna Steam Electric Station (SSES) has no redundant Secondary Containment System.
CAUSE OF EVENT
The failure was not able to be replicated during investigation. The direct cause is inconclusive.
A failure modes analysis was completed to identify the likely cause of the fan trip. Potential causes include the following:
1. Linkages on Flow Control Damper PDD27522A [EIIS System/Component Identifier: VA/CDMP] could have been binding and prevented the damper from going open.
2. Low Flow Switch FSL27522A [EllS System/Component Identifier: VA/FS] could have failed to reset during the 2V206A start.
comments regarding burden estimate to the Information Services Branch (T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, the information collection.
3. LER NUMBER
2017 - 009 - 01 44)
CONTINUATION SHEET
The procedure section for performing a fan swap includes the following caution statement: "Minimizing time between start of standby fan and subsequent shutdown of running fan will prevent low flow trip to occur. Low flow trip will occur if fans remain in parallel for approx. 30 seconds". Operator interviews indicated the discharge damper took longer than expected to open. The fans may have been running in parallel for longer than 30 seconds.
ANALYSIS/SAFETY SIGNIFICANCE
Based on engineering analysis of the event, secondary containment could have performed its safety function of isolating as assumed in the accident analysis and of re-establishing 0.25 inches of vacuum WG (drawdown) within the assumed accident analysis time (10 minutes).
This event will not be counted as a safety system functional failure (SSFF) for the NRC performance indicator based on the engineering analysis supporting the system's ability to fulfill the safety function.
CORRECTIVE ACTIONS
Due to the definitive cause being inconclusive, the remaining potential failure modes identified as unlikely are being addressed to minimize or eliminate an event similar to this. Corrective actions include the following:
1. Linkages on Flow Control Damper PDD27522A will be greased to reduce the probability of binding from occurring 2. The reset for the Low Flow Switch FSL27522A will be tested to address the potential of an intermittent failure. If the reset test is unsatisfactory, the low flow switch will be replaced.
3. The caution statement in the applicable Unit 1 and 2 procedures will be revised to state "Leaving fans operating in parallel may cause a low flow trip. Securing a fan should be performed as soon as the discharge damper indicates dual position. Low flow trip will occur if flow remains below trip setpoint of 18,000 scfm for approximately 30 seconds.
COMPONENT FAILURE INFORMATION
Information for Flow Control Damper PDD27522A:
Manufacturer: Trane Model: CF40A3SW3CCUBSX Information for Low Flow Switch FSL27522A Manufacturer: United Electric Controls Model: J-6-142-9515 comments regarding burden estimate to the Information Services Branch (T-2 F43), U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001, or by e-mail to used to impose an information collection does not display a currently valid OMB control number, the NRC may not conduct or sponsor, and a person is not required to respond to, file information collection.
|
|---|
|
|
| | | Reporting criterion |
|---|
| 05000387/LER-2017-001, Regarding Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | Regarding Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(ix)(A), Prevented Safety Function in Multiple System 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000387/LER-2017-002, Regarding Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | Regarding Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(ix)(A), Prevented Safety Function in Multiple System 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000388/LER-2017-003 | Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material | | 05000387/LER-2017-003, Regarding Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | Regarding Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(ix)(A), Prevented Safety Function in Multiple System 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000388/LER-2017-004 | 1 OF 3 | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material | | 05000387/LER-2017-004, Regarding Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | Regarding Secondary Containment Breach Due to Simultaneous Opening of Airlock Doors | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(ix)(A), Prevented Safety Function in Multiple System 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000388/LER-2017-005 | Secondary Containment Declared Inoperable Due to Trip of Zone Ill Filtered Exhaust Fan | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material | | 05000388/LER-2017-007 | Secondary Containment Declared Inoperable Due to Supply Air Flow | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material | | 05000387/LER-2017-008, Core Spray Inoperable Due to Not Meeting Seismic Requirements as a Result of a Human Performance Error | Core Spray Inoperable Due to Not Meeting Seismic Requirements as a Result of a Human Performance Error | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(ix)(A), Prevented Safety Function in Multiple System 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000388/LER-2017-009 | Secondary Containment Declared Inoperable Due to Trip of Zone II Equipment Exhaust Fan | 10 CFR 50.73(a)(2)(v)(C), Loss of Safety Function - Release of Radioactive Material | | 05000387/LER-2017-009-01, Regarding Secondary Containment Declared Inoperable Due to Trip of Zone II Equipment Exhaust Fan | Regarding Secondary Containment Declared Inoperable Due to Trip of Zone II Equipment Exhaust Fan | 10 CFR 50.73(a)(2)(iv)(A), System Actuation 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor 10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(i) 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2)(iii) 10 CFR 50.73(a)(2)(i)(A), Completion of TS Shutdown 10 CFR 50.73(a)(2)(ix)(A), Prevented Safety Function in Multiple System 10 CFR 50.73(a)(2)(viii)(A) 10 CFR 50.73(a)(2)(viii)(B) | | 05000387/LER-2017-010-02, Condition Prohibited by Technical Specifications Due to Drift of Reactor Pressure Switches | Condition Prohibited by Technical Specifications Due to Drift of Reactor Pressure Switches | 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(ix)(A), Prevented Safety Function in Multiple System | | 05000388/LER-2017-010-01, Condition Prohibited by Technical Specifications Due to Drift of Reactor Pressure Switches | Condition Prohibited by Technical Specifications Due to Drift of Reactor Pressure Switches | 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(ix)(A), Prevented Safety Function in Multiple System |
|