05000327/FIN-2005011-01
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Reliance on 20-foot Separation Zones for Fire Protection in Unit 1 480V Board Room 1B |
Description | The team identified an unresolved item (URI) associated with reliance on 20-foot separation zones between redundant SSD equipment in Unit 1 480V Board Room 1B (Fire Area FAA-095). The 20-foot zones did not meet the requirements of 10 CFR 50, Appendix R, Section III.G.2 and also appear not to meet the basis for NRC approval of Deviation #11 related to those requirements. This issue is unresolved pending further NRC review of the licensing basis and the potential for the condition to adversely affect SSD. The licensees SSA for Fire Area FAA-095 relied on three separate 20-foot separation zones between redundant SSD equipment in the room. Fire Area FAA-095 contained three Unit 1 480V motor control centers (MCCs), all three Unit 1 battery chargers (train A, train B, & spare), two of four channels of vital inverters for Unit 1, and two of four channels of vital inverters for Unit 2. The SSA relied on at least two of the three Unit 1 battery chargers and one of the two channels of Unit 1 and Unit 2 inverters in the room not being damaged by a fire in the room. One 20-foot separation zone was located on the north side of the room, separating the train A battery charger (located in the north end of the room) from the spare battery charger (located in the middle of the room). Another 20 foot separation zone was located on the south side of the room separating the train B battery charger (located in the south end of the room) from the spare battery charger. The third 20-foot separation zone was located in the middle of the room, between the vital inverters 1-I and 2-I (located in the north end of the room) and vital inverters 1-II and 2-II (located in the south end of the room). 10 CFR 50, Appendix R, Section III.G.2 stated that redundant SSD cables and equipment could be separated by 20 feet, with no intervening combustibles or fire hazards, and with detection and automatic suppression installed in the area. Deviation #11 applied to the auxiliary building in general. It allowed 20-foot separation zones in this building with intervening combustibles in the form of cable trays provided that: 1) the cables had fuse and breaker coordination to minimize the potential for fires initiating from cable faults and 2) extra sprinklers were installed to compensate for cable trays partially blocking any sprinklers. The team noted that the licensee had not identified in FAA-095 or in engineering documents exactly where the 20-foot separation zones were located. The team estimated the areas of the three 20-foot separation zones in FAA-095 and observed that each one did not meet the requirements of 10 CFR 50, Appendix R, Section III.G.2 and also appeared not to meet the basis for Deviation #11. In addition to intervening cable trays, each of the 20-foot separation zones included intervening ignition sources in the form of 480V MCCs and inverters. Also, two inverters located in the south end of the room, in the 20-foot separation zone between the Train A battery charger and the spare battery charger, did not have sprinklers installed above them. Licensee personnel stated that the lack of sprinklers in the south end of the room had been approved by Deviation #4. Deviation #4 applied to the Appendix R,Section III.G.2 requirement that fire detection and automatic suppression be provided in areas containing redundant SSD equipment that is separated by less than a three-hour fire rated construction. Deviation #4 allowed the licensee to omit sprinklers at the south end of FAA-095 on the basis that inadvertent operation of a sprinkler system would cause unacceptable damage to the inverters and battery chargers. Also, fire loading in FAA- 095 was considered to be low. However, the team observed that the battery charger and inverters at the north end of FAA-095 had sprinklers installed above them and that fire loading in FAA-095 was not low. The team found that, after Deviation #4 had been approved by the NRC, licensee engineers had recalculated the fire loading in FAA-095 and found it to be high. Apparently the original calculation of fire loading had failed to include the cable insulation inside of the 480V MCCs, inverters, and battery chargers. Licensee engineers determined the increased fire loading did not adversely affect SSD and and thus was acceptable without further review by the NRC. The team concluded that the licensee had inappropriately applied two separate NRC approved Deviations to the south end of FAA-095. More importantly, the team was concerned that the three 480V MCCs that intervened in the three 20-foot separation zones represented significant fire hazards. They occupied most of the length of FAA-095, from the north end to the south end of the room. They included a total of 42 vertical sections, with each vertical section being a potential ignition source. Each vertical section had stacks of open cable trays directly above it, so that a fire that initiated in a vertical section could readily spread up to seven or more cable trays. NUREG-1805 fire models demonstrated that such a fire could cause a hot gas layer throughout the room which could damage the cables (all had non-qualified thermoplastic insulation) and the SSD equipment located in FAA-095, should the automatic sprinkler system fail. The team noted that the sprinkler system for FAA-095 had a higher likelihood of failure because it was a cross-zone preaction-type of system. The sprinkler piping in FAA-095 was normally dry. To put fire water into the piping, at least two smoke detectors from different zones in the room would have to activate and automatically open a valve. If the cross-zone detector circuit failed or the valve failed to automatically open, all of the sprinklers in FAA-095 would fail to deliver water. Sequoyah\'s license condition for fire protection allowed changes to the fire protection program provided that the changes did not adversely affect SSD. The licensee\'s evaluation determined that the existing 20-foot separation zones were acceptable. Licensee personnel concluded that the existing 20-foot separation zones did not adversely affect SSD and were acceptable with no further review by the NRC, because there were sprinklers above the cable trays and MCCs. This issue is considered an unresolved item pending further NRC review of the licensing basis and the potential for the condition to adversely affect SSD. This issue is identified as URI 05000327,328/2005011-01, Reliance on 20-foot separation zones for Fire Protection in Unit 1 480V Board Room 1B. |
Site: | Sequoyah ![]() |
---|---|
Report | IR 05000327/2005011 Section 1R05 |
Date counted | Dec 31, 2005 (2005Q4) |
Type: | URI: |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.05 |
Inspectors (proximate) | M Speck M Widmann R Moore R Schin S Rose B Miller C Smith C Stancil D Mas Penaranda E Michel F Ehrhardt G Laska J Baptist J Diaz Velezl Laken Merriweatherb Melly R Schin D Payne J Quinones-Navarrom Widmannr Moore S Rose B Miller C Smith C Stancil D Mas Penaranda E Michel F Ehrhardt G Laska J Baptist J Diaz Velezl Lake M Speck |
INPO aspect | |
' | |
Finding - Sequoyah - IR 05000327/2005011 | |||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Sequoyah) @ 2005Q4
| |||||||||||||||||||||||||||||||||