ENS 47998
From kanterella
Jump to navigation
Jump to search
ENS Event | |
---|---|
08:27 Jun 6, 2012 | |
Title | Inadequate Cooling Available to Support Electrical Power Systems |
Event Description | Wolf Creek commenced a nuclear plant shutdown in accordance with Technical Specifications. Engineering analysis has determined that with one non-functional Class IE A/C unit, there is inadequate cooling available to support electrical power systems required by Technical Specifications (TS) 3.8.4, 3.8.7, 3.8.9, during all postulated conditions. Actions are currently underway to restore the non-functional Class IE A/C unit to a functional status.
The non-functional Class IE A/C unit had a clogged oil pump strainer. Per TS 3.0.3, Wolf Creek began reducing power and was at 89% power at the time of the report. The licensee has notified the NRC Resident Inspector.
The A Class IE A/C unit was restored to functional at 6/6/2012 0505 CDT. The plant shutdown was terminated at 87 percent power. Actions are underway to restore the unit to 100 percent power. Notified R4DO (Gepford). |
Where | |
---|---|
Wolf Creek Kansas (NRC Region 4) | |
Reporting | |
10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown | |
Time - Person (Reporting Time:+-3.13 h-0.13 days <br />-0.0186 weeks <br />-0.00429 months <br />) | |
Opened: | Warren Brandt 05:19 Jun 6, 2012 |
NRC Officer: | Dong Park |
Last Updated: | Jun 6, 2012 |
47998 - NRC Website | |
Unit 1 | |
---|---|
Reactor critical | Critical |
Scram | No |
Before | Power Operation (100 %) |
After | Power Operation (100 %) |
WEEKMONTHYEARENS 545082020-02-02T00:45:0002 February 2020 00:45:00
[Table view]10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Shutdown Due to Containment Purge Valve Excessive Leakage ENS 522182016-09-02T13:08:0002 September 2016 13:08:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown ENS 510742015-05-16T02:48:00016 May 2015 02:48:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to 2 Ac Inverters Inoperable ENS 510712015-05-15T09:36:00015 May 2015 09:36:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to 2 Ac Inverters Inoperable ENS 494482013-10-18T17:11:00018 October 2013 17:11:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Loss of Cooling to Switchgear Rooms ENS 493392013-09-11T22:31:00011 September 2013 22:31:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Loss of Cooling to Switchgear Rooms ENS 491262013-06-17T16:11:00017 June 2013 16:11:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Non-Functional Class 1E Electrical A/C Unit ENS 490082013-05-06T22:33:0006 May 2013 22:33:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Shutdown Required Due to Non-Functional Class 1E Air Conditioning Unit ENS 479982012-06-06T08:27:0006 June 2012 08:27:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Inadequate Cooling Available to Support Electrical Power Systems ENS 471542011-08-15T15:55:00015 August 2011 15:55:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown - Contaminated Oil Sample ENS 464572010-12-06T10:18:0006 December 2010 10:18:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Tech Spec Required Shutdown Due to Exceeding Allowed Outage Time on the 'A' Emergency Diesel Generator ENS 463092010-10-05T03:00:0005 October 2010 03:00:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown ENS 461982010-08-23T13:14:00023 August 2010 13:14:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Tech Spec Required Shutdown Due to Both Edgs and an Rhr Loop Inoperable ENS 459852010-06-07T23:44:0007 June 2010 23:44:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Due to Voiding in the Component Cooling Water System ENS 456632010-01-26T21:25:00026 January 2010 21:25:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Entry Into Technical Specification Required Shutdown ENS 439852008-02-14T00:50:00014 February 2008 00:50:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification 3.0.3 Required Shutdown ENS 438952008-01-11T22:22:00011 January 2008 22:22:00 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Tech. Spec. Required Shutdown Due to Gas Voiding in Discharge Piping ENS 420042005-09-21T03:40:00021 September 2005 03:40:00 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown Commenced Due to Inoperability of Residual Heat Removal Containment Sump Isolation Valves 2020-02-02T00:45:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_47998&oldid=423852"