Pages that link to "05000366/LER-1982-102, Forwards LER 82-102/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000366/LER-1982-102, Forwards LER 82-102/03L-0:
Displayed 21 items.
- 05000366/LER-1982-123, Forwards LER 82-123/03L-0 (← links)
- 05000366/LER-1982-093, Forwards LER 82-093/03L-0 (← links)
- 05000366/LER-1982-114, Forwards LER 82-114/03L-0 (← links)
- 05000321/LER-1982-096, Forwards LER 82-096/03L-0 (← links)
- ML20071N614 (redirect page) (← links)
- 05000366/LER-1982-102 (redirect page) (← links)
- 05000366/LER-1982-102-03, /03L-0:on 820830,w/unit steady-state at 2,258 Mwt, Discovered 820812 Scheduled Monthly Fire Hose Station safety-related Areas Surveillance Procedure Not Completed Before 820819 Grace Period Expiration (← links)
- 05000321/LER-1982-004-03, /03L-0:on 820202,during Refueling & While Performing HNP-1-3001,high Reactor Pressure Instrument Functional Test & calibr,1B21-N023C Found to Actuate at 1085 Psig.Caused by Setpoint Drift of Barksdale Model B2T (← links)
- 05000366/LER-1982-115-03, /03L-0:on 821122,core Spray RHR Permissive Pressure Switch B Found Inoperable During Calibr Procedure. Caused by High Setpoint Micro Switch Failure to Actuate. Micro Switch Replaced,Calibr & Returned to Svc on 821217 (← links)
- 05000366/LER-1982-128-03, /03L-0:on 821125,during Power Ascension,Core Max Fraction of Limiting Power Density Found Greater than Tech Spec Limit.Caused by Control Rod Movement in Low Xenon Concentration Producing Higher Power.Monitor Adjusted (← links)
- 05000321/LER-1982-098-03, /03L-0:on 821108,discovered That Liquid Radwaste Monitor Instrument Procedures Not Performed Monthly.Caused by Inadequate Procedures.Correct Procedures Performed Monthly (← links)
- 05000366/LER-1982-124-03, /03L-0:on 821102,during Administrative Review, Temporary Changes Made to Arm Calibr Procedure Not Reviewed & Signed within Required 14 Days.Caused by Personnel Error. One Dept Assigned Responsibility for Tracking Changes (← links)
- 05000321/LER-1982-085-03, /03L-0:on 821103,walkdown of TIP Withdrawal LSFT Logic Relay Wiring Revealed Two Wires Installed Onto Wrong Relay.Caused by Incorrect Relay Connection Diagram.Wires Will Be Terminated to Correct Terminal Relays (← links)
- 05000321/LER-1982-097-01, /01T-0:on 821116,spent Fuel Rod Broken During Visual Insp of Several Spent Fuel Bundles.Caused by Severely Degraded Cladding at Point of Separation Due to Corrosion. Rod Will Be Placed Back Into Bundle & Bundle Flagged (← links)
- 05000366/LER-1982-120-03, /03L-0:on 821022,barrier Adjacent to Silicone Foam Fire Barrier in Cable Spread Room Found Breached.Caused by Penetration Left Unsealed After Installation of Conduit. Maint Request Initiated.Seal Repaired on 821102 (← links)
- 05000366/LER-1982-093-03, /03L-0:on 820817,while Operating at Full Load, Control Rod Drive Accumulator Trouble Alarm Received.Caused by Slow Bleed Down of Accumulator Pressure.Accumulator Recharged (← links)
- 05000321/LER-1982-093-03, /03L-0:on 821107,liquid Radwaste Discharge Monitor Auto Control to Discharge Isolation Valve Found Inoperable During Liquid Radwaste Discharge.Caused by Jumper Not Being Removed After Completion of Corrective Maint.Jumper Re (← links)
- 05000366/LER-1982-116-03, /03L-0:on 821014,during Full Load Operation, Drywell Hydrogen & Oxygen Analyzer B Found Inoperative. Caused by Failure of Diaphragm Capscrew on Sample Pump Connecting Rod.Capscrew Replaced & Analyzer Recalibr (← links)
- 05000321/LER-1982-087-03, /03L-0:on 821005,during Run Mode,Rcic Flow Switch Actuated Low & Declared Inoperable.Caused by Setpoint Drift Due to Loose Set Screw on RCIC Flow Instrument.Switch Reset & Calibr.Set Screws Tightened (← links)
- 05000366/LER-1982-113-03, /03L-0:on 821009,during Testing,Discharge Check Valve on RHR Svc Water Pump Stuck Open.Caused by Corroded Flapper Shaft.Check Valve Rebuilt & Returned to Svc (← links)
- 05000321/LER-1982-096-03, /03L-0:on 821008,oil Pump Trip Signal Received for B Recirculation Pump.Caused by Supply Breaker to Operating Oil Pump Being Placed in Off Position.Breaker Reset & B Recirculation Pump Returned to Svc (← links)