Pages that link to "05000364/LER-1981-004, Forwards LER 81-004/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000364/LER-1981-004, Forwards LER 81-004/03L-0:
Displayed 28 items.
- ML20003F161 (redirect page) (← links)
- 05000364/LER-1981-001, Forwards LER 81-001/03L-0 (← links)
- 05000364/LER-1981-003-03, /03L-0:on 810311,radiation Monitor R5 in Fuel Storage Pool Area Failed Low & Was Declared Inoperable. Caused by Loose Connector Pin.Connector Repaired (← links)
- 05000364/LER-1981-003, Forwards LER 81-003/03L-0 (← links)
- 05000364/LER-1981-004-03, /03L:on 810314,audible Count Rate in Containment Was Lost in Mode 6.Caused by Blown Fuse in 2D Inverter. Blown Inverter Fuse Replaced (← links)
- 05000364/LER-1981-004 (redirect page) (← links)
- 05000348/LER-1981-008-03, /03L-0:on 810313,surveillance Tests for Tech Spec 4.3.3.1 for Radiation Monitors R25 a & B Not Performed within Required Period.Caused by Personnel Not Properly Assessing Conditions for Surveillance.Test Schedule Revised (← links)
- 05000348/LER-1981-008, Forwards LER 81-008/03L-0 (← links)
- 05000348/LER-1981-009-03, /03L-0:on 810317,determined That Diesel Generator 1-2A Had Been Inoperable for 35-minute Period Following Entry Into Mode 4.Caused by Personnel Error.Personnel Instructed in Proper Procedures (← links)
- 05000348/LER-1981-029-01, /01T-0:on 810515,fire Protection Tanks a & B Fell Below Min Level.Caused by Ruptured Fire Main in Unit 2 Low Voltage Switch Yard.Ruptured Line Repaired (← links)
- 05000348/LER-1981-025, Forwards LER 81-025/03L-0 (← links)
- 05000364/LER-1981-011-03, /03L-0:on 810426 & 27,power Operated Relief Valve 445A Declared Inoperable.Caused by Seat Leakage.Valve Stroke Adjusted.Leakage Reoccurred & Valve Isolated.Repair Will Be Accomplished When Plant Conditions Permit (← links)
- 05000364/LER-1981-010-03, /03L-0:on 810429 & 30,containment Atmosphere Radioactivity Monitoring Sys R-11 Declared Inoperable.Caused by Filter Paper Not Advancing Due to Paper Spool Slippage on Shaft.Drive Shaft Adjusted & R-11 Returned to Svc (← links)
- 05000364/LER-1981-009-03, /03L-0:on 810428 & 0501,pressurizer Pressure Indicator PI456 Declared Inoperable.Caused by Out of Spec Indicator Reading Which Occurred During Channel Check. Transmitter Replaced & Channel Returned to Svc (← links)
- 05000348/LER-1981-037-01, /01T-0:on 810522,Westinghouse Notified Util of Potential Control & Protection Sys Interaction Concern Re Vol Control Tank Level Instrumentation Control.Caused by Inadequate Design/Safety Analysis Review (← links)
- 05000348/LER-1981-021-03, /03L-0:on 810413,output Voltage of Diesel Generator 2C Fell to Zero.Caused by Two Blown Voltage Regulator Fuses.Fuses Replaced (← links)
- 05000348/LER-1981-020-03, /03L-0:on 810411,B1F Sequencer Failed to Meet Time Requirement for Picking Up Step 6.Caused by Setpoint Drift of Sequencer Agastat Timer.Timer Adjusted (← links)
- 05000348/LER-1981-006, Forwards LER 81-006/03L-0 (← links)
- 05000348/LER-1981-004, Forwards LER 81-004/03L-0 (← links)
- 05000348/LER-1981-026-03, /03L-0:on 810506,on Two Separate Occasions,Diesel Generator 1C Failed to Reach Rated Speed & Voltage within Required Time.Caused by Faulty Fuel Oil Check Valve.Valve Replaced (← links)
- 05000348/LER-1981-024-03, /03L-0:on 810501,high Differential Pressure Across Strainer Found on Diesel Generator 1-2A.Caused by Excessive Accumulation of Lube Oil Sediment/Dirt in Strainer.Strainer Cleaned (← links)
- 05000348/LER-1981-023-03, /03L-0:on 810425,fuel Oil Found Leaking on Diesel Generator 1-2A.Caused by Failed Fuel Oil Filter Gasket. Gasket Replaced (← links)
- 05000348/LER-1981-001-03, /03L-0:on 810116,RHR Flow Lost.Caused by Loss of Power to 1A RHR Pump as Result of Feeder Breaker to Start Up Transformer 1A Opening.Diesel Generator 1-2A Energized Bus 1F & RHR Pump Restarted.Transformer 1A re-energized (← links)
- 05000348/LER-1981-001, Forwards LER 81-001/03L-0 (← links)
- 05000348/LER-1981-005-01, /01T-0:on 810324,determined That Time Stipulated in FSAR Section 9.2.1.3 for Operator Action in Accident Involving Svc Water Pond Dam Break & Limiting Active Failure Is Not Accurate.Caused by Design Error (← links)
- 05000348/LER-1981-005, Forwards LER 81-005/01T-0 (← links)
- 05000348/LER-1981-003-03, /03L-0:on 810202,fuel Storage Pool Area Gaseous activity-ventilation Sys Isolation Radiation Monitor R25B Declared Inoperable.Caused by Drive Belt Breaking.Belt Replaced (← links)
- 05000348/LER-1981-003, Forwards LER 81-003/03L-0 (← links)