Pages that link to "05000333/LER-1980-068, Forwards LER 80-068/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000333/LER-1980-068, Forwards LER 80-068/03L-0:
Displayed 22 items.
- ML19331D408 (redirect page) (← links)
- ML19331D409 (← links)
- 05000333/LER-1980-068-03, /03L-0:on 800806,during Normal Cold Shutdown, Conducting Instrument Surveillance F-ISP-15,drywell Drain Sump Pump Flow Transmitter Found Out of Tolerance.Caused by Instrument Drift.Instrument Recalibr (← links)
- 05000333/LER-1980-068, Forwards LER 80-068/03L-0 (← links)
- 05000333/LER-1980-066-03, /03L-0:on 800805,during Normal Shutdown,Conducting Surveillance Procedure F-ISP-8,core Spray Sys Pipe Break Detection Switches 14-DPIS-43A & 43B Found Set Greater than Limit.Caused by Instrument Drift.Instruments Recalibr (← links)
- 05000333/LER-1980-066, Forwards LER 80-066/03L-0 (← links)
- 05000333/LER-1980-065-03, /03T-0:on 800814,during Normal Operations,While Inerting Primary Containment,Standby Gas Treatment Sys A&B Found Inoperable.Caused by Blocked Drain Line Allowing Water to Accumulate in Line Until Fans Could Not Discharge (← links)
- 05000333/LER-1980-069-03, /03L-0:on 800807,during Normal Shutdown,While Conducting Surveillance Test F-ST-22A,auto Depressurization Sys Timer Found Set Below Limit.Caused by Setpoint Drift. Timer Adjusted & Returned to Svc (← links)
- 05000333/LER-1980-069, Forwards LER 80-069/03L-0 (← links)
- 05000333/LER-1980-068-03, /03L-0:on 800806,during Normal Cold Shutdown, Conducting Instrument Surveillance F-ISP-15,drywell Drain Sump Pump Flow Transmitter Found Out of Tolerance.Caused by Instrument Drift.Instrument Recalibr (← links)
- 05000333/LER-1980-068 (redirect page) (← links)
- 05000333/LER-1980-067-03, /03L-0:on 800805,while Conducting Instrument Surveillance Check,Steam Line Low Pressure Switches Found Set Higher than 100 Psig Limit.Caused by Instrument Drift. Instruments Calibr & Returned to Svc (← links)
- 05000333/LER-1980-067, Forwards LER 80-067/03L-0 (← links)
- 05000333/LER-1980-063-03, /03L-0:on 800717,during Normal Shutdown, Surveillance Revealed That Average Power Range Monitor E Indicated 48 When Required to Read Between 49 & 51.Caused by Instrument Drift.Monitor Recalibr (← links)
- 05000333/LER-1980-063, Forwards LER 80-063/03L-0 (← links)
- 05000333/LER-1980-061-03, /03L-0:on 800714,during Shutdown,Functional Test of Hydraulic Snubbers Revealed Two Snubbers Which Failed Lockup & bleed-rate Values.Caused by Normal Wear.Snubbers Were Replaced (← links)
- 05000333/LER-1980-057-03, /03L-0:on 800628,during Normal Shutdown,One Cell in Each 24 Volt Battery for Diesel Fire Pump Failed to Meet Min Specific Gravity Requirements of Surveillance Test. Caused by Charger Being Out of Svc During Surveillance (← links)
- 05000333/LER-1980-057, Forwards LER 80-057/03L-0 (← links)
- 05000333/LER-1980-058-03, /03L-0:on 800628,during Normal Shutdown Operations,Functional Tests of Average Power Range Monitor Instruments Found Not Conducted Per Tech Specs.Caused by Manual Scheduling of Computer Outage (← links)
- 05000333/LER-1980-058, Forwards LER 80-058/03L-0 (← links)
- 05000333/LER-1980-059-03, /03L-0:on 800703,during Normal Shutdown Surveillance,Level Switches & Pressure Indicator Showed 128 Instruments Out of Calibr or Not Properly Operating.Caused by Instrument Drift.Instruments Recalibr.Two Replaced (← links)
- 05000333/LER-1980-059, Forwards LER 80-059/03L-0 (← links)
- 05000333/LER-1980-055-03, /03L-0:on 800607,surveillance Revealed Intermediate Range Monitor,A Indicating 120 When Reading of 125 Was Required.Caused by Instrument Drift.Adjustment & Calibr Restored Instrument to Operable Status (← links)
- 05000333/LER-1980-055, Forwards LER 80-055/03L-0 (← links)
- 05000333/LER-1980-060-03, /03L-0:on 800710,while Conducting Surveillance Per Tech Spec Table 4.2-6,Item 6,torus Water Level Instrument Did Not Properly Indicate Actual Level.Caused by Air in Level Transmitter &/Or Sensing Lines.Air Vented (← links)