- 05000327/LER-1982-126, Forwards LER 82-126/01T-0 (← links)
- ML20083N933 (redirect page) (← links)
- 05000328/LER-1982-142 (redirect page) (← links)
- 05000328/LER-1982-142-03, /03L-0:on 821229,while Running Surveillance Instruction 166.1 for Containment Isolation Valves,Valves 2-FCV-68-305 Failed to Open.Caused by Faulty Diaphragm. Diaphragm Replaced (← links)
- 05000327/LER-1982-135-03, Three Level Switches on Upper Head Injection Sys Found to Be Out of Tolerance During Review of Surveillance Instruction 196.Probably Caused by Instrument Drift of Barton Model 288A Level Switches (← links)
- 05000328/LER-1982-137-03, Four Upper Head Injection Switches Found Out of Tolerance & One Failed to Close.Caused by Instrument Drift & Broken Microswitch.Switch Repaired & Level Switches Adjusted.Pilot Valve Replaced (← links)
- 05000328/LER-1982-138-03, /03L-0:on 821123,lower Containment Airlock Door Failed Air Leak Rate Test.Caused by Backed Off Packing Nut That Allowed Packing to Loosen.Nut Retightened & Door Tested.Design Change Request Submitted (← links)
- 05000327/LER-1982-131-03, /03L-0:on 821109,during Mode 6,nuclear Instrumentation Sys Source Range Detector N-32 Declared Inoperable Due to Spiking.Caused by Heat Gun Used in Work on Penetration Junction Boxes.Penetration Work Suspended (← links)
- 05000328/LER-1982-132-03, /03L-0:on 821103,one RHR Pump Declared Inoperable Due to Discharge Flow Switch Failure to Actuate.Caused by Failure of Contacts to Close Due to Faulty Actuating Cam. Flow Switch Repaired & Recalibr (← links)
- 05000328/LER-1982-129-03, /03L-0:on 821103,letdown Orifice Containment Isolation Valve 2-FCV-62-73 Failed Shut.Caused by Control Fuses Failing Due to Shorted Coil in Relay 8149AX.Coil & Fuses Replaced.Valve Tested & Returned to Svc on 821104 (← links)
- 05000327/LER-1982-117-03, /03L-0:on 820914,during SI-220 Test on Fire Pump 1B-B Start Circuit,Time Delay Setpoint on Relay 1B2 Found Out of 5% Tolerance of 120-s.Cause Not Stated.Time Delay Setpoint Readjusted to within 5% Tolerance (← links)
- 05000327/LER-1982-012-03, /03L-0:on 820122,when Divider Barrier Equipment Hatch 3 Was Opened,Seal Gasket Discovered Missing.Probably Caused by Personnel Failure to Verify Gasket Reinstallation on 811016.Gasket Installed.Engineers Reinstructed (← links)
- 05000328/LER-1982-136-03, /03L-0:on 821115,inleakage Found to Be 340 Cubic Ft Per Minute to Annulus During Performance of Surveillance Instruction 264.Caused by Numerous Leaks Found Through Personnel Access & Equipment Doors & Other Areas (← links)
- 05000327/LER-1982-124-03, /03L-0:on 821023 & 28,liquid Radwaste Effluent Line Monitor Failed to Meet Surveillance Requirement.Caused by Contamination Buildup in Sample Chamber.Sample Chamber Cleaned.Procedures Under Review (← links)