Pages that link to "05000328/LER-1982-136, Forwards LER 82-136/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000328/LER-1982-136, Forwards LER 82-136/03L-0:
Displayed 9 items.
- ML20067D710 (redirect page) (← links)
- 05000328/LER-1982-136 (redirect page) (← links)
- 05000327/LER-1982-126, Forwards LER 82-126/01T-0 (← links)
- 05000328/LER-1982-136-03, /03L-0:on 821115,inleakage Found to Be 340 Cubic Ft Per Minute to Annulus During Performance of Surveillance Instruction 264.Caused by Numerous Leaks Found Through Personnel Access & Equipment Doors & Other Areas (← links)
- 05000327/LER-1982-128-01, /01T-0:on 821109,discovered That Suction Damper FCO-31A-14 Had Not Closed Allowing Direct Flow Path to Outside Environ.Caused by Faulty Air Operated Solenoid Valve.Damper Repaired & Operation Verified (← links)
- 05000327/LER-1982-124-03, /03L-0:on 821023 & 28,liquid Radwaste Effluent Line Monitor Failed to Meet Surveillance Requirement.Caused by Contamination Buildup in Sample Chamber.Sample Chamber Cleaned.Procedures Under Review (← links)
- 05000328/LER-1982-122-03, /03L-0:on 821021,during Mode 1 Operation, Pressurizer Pressure Channel 2-PS-68-323B Declared Defective Due to Loss of Ac Power to Channel.Caused by Defective Fuse Holder Cap.Cap Replaced & Channel Returned to Svc (← links)
- 05000327/LER-1982-116-03, /03L-0:on 820916,both Trains of RHR Sys Inoperable Due to Inadvertent Closing of RHR Suction Valve 1-FCV-74-2. Caused by Removal of Power Fuses to Allow Work on Output Relays.Rhr Pump Stopped & Valve Reopened W/Auxiliary Pow (← links)
- 05000328/LER-1982-115-01, /01T-0:on 821002,inner & Outer Doors of Upper Containment Personnel Airlock Were Open Simultaneously Due to Latch Bar Blocking Outer Door Open.Caused by Door Swing Operating Chain Being Out of Adjustment.Chain Adjusted (← links)