- 05000328/LER-1982-049-03, /03L-0:on 820330,w/unit in Mode 1 at 30% Reactor Power,One Upper Containment Airlock Door Found Jammed Closed.Caused by Failure of CAM Roller Bearing in Operating Mechanism.Bearing Replaced & Door Satisfactorily Tested (← links)
- 05000327/LER-1982-053-03, /03L-0:on 820415,vital Battery Bank II Declared Inoperable When Cell 4 Connection Resistance Found Greater than 150 micro-ohms.Caused by Loose Bolt Connection.Bolt Torqued & Resistance Checked (← links)
- 05000327/LER-1982-053, Forwards LER 82-053/03L-0 (← links)
- 05000328/LER-1982-032-03, /03L-0:on 820228,rod Position Indicator M-4 on Control Bank D Declared Inoperable When Indication Dropped to Zero.Caused by Defective Connector.Spare Connector Being Used Until Defective Connector Repaired (← links)
- 05000328/LER-1982-032 (redirect page) (← links)
- 05000327/LER-1982-050-03, /03L-0:on 820413,diesel Generator 1A.A Declared Inoperable When Power Fuses Blew in Control Circuitry.Caused by Broken Lead on Annunciator Horn Shorting to Case.Horn Replaced (← links)
- 05000327/LER-1982-050, Forwards LER 82-050/03L-0 (← links)
- 05000327/LER-1982-048-03, /03L-0:on 820408,at 100% Power,Automatic Control Valve 1-PCV-3-132 in Auxiliary Feedwater Sys Flowpath Failed to Open on Demand.Caused by Faulty Soldered Amphenol Connector to Electrohydraulic Actuator.Connector Repaired (← links)
- 05000328/LER-1982-026-03, /03L-0:on 820221,containment Sump Level Transmitter 2-LT-65-176 Inoperable Due to High Readings. Caused by Leaking Sensor Bellows.Sensor Bellows Replaced & Transmitter Recalibr (← links)
- 05000328/LER-1982-026, Forwards LER 82-026/03L-0 (← links)
- 05000327/LER-1982-025-03, /03L-0:on 820212,pressurizer Level Channel 1-LT-68-335 Declared Inoperable.Caused by Transmitter Out of Calibr Due to Instrument Drift.Barton Model 764 Transmitter Recalibr (← links)
- 05000327/LER-1982-025, Forwards LER 82-025/03L-0 (← links)
- 05000327/LER-1982-027-01, /01T-0:on 820307,while Preparing to Perform SI-566,ERCW Flow Verification Test,Containment Spray Heat Exchanger 1A Found W/Low Essential Raw Cooling Water Flow. Caused by Fresh Water Clams in Piping.Clams Removed (← links)
- 05000327/LER-1982-027, Forwards LER 82-027/01T-0 (← links)
- 05000327/LER-1982-024-03, /03L-0:on 820218,turbine Bldg Sump & Condensate Demineralizer Radioactive Effluent Line Monitors Declared Inoperable.Caused by Crud & Debris Buildup on Flow Switch. Switches Cleaned (← links)
- 05000327/LER-1982-024, Forwards LER 82-024/03L-0 (← links)
- 05000327/LER-1982-028, Forwards LER 82-028/03L-0 (← links)
- 05000327/LER-1982-029-03, /03L-0:on 820215,w/unit in Mode 3,glycol Containment Isolation Valve 1-FCV-61-194 Would Not Reopen When Stroked from Full Open Position.Caused by Conductor G1B1 Not Being Terminated.Conductor Reterminated (← links)
- 05000328/LER-1982-022, Forwards LER 82-022/03L-0 (← links)
- 05000328/LER-1982-021-01, /01T-0:on 820217,during Startup,Shutdown Rods in Shutdown Bank a Exceeded Plus/Minus 12 Steps of Actual Position on Indicators.Caused by Misinterpretation of Limiting Condition for Operation 3.1.3.3.Rods Recalibr (← links)
- 05000328/LER-1982-021, Forwards LER 82-021/01T-0 (← links)
- 05000328/LER-1982-016-03, /03L-0:on 820127,steam Generator Pressure Channels for Loops 3 & 4 to Remote Shutdown Instrumentation Declared Inoperable Due to Failure to Meet Channel Check Requirements.Caused by Open Circuit on Loop 2-PI-1-19C (← links)
- 05000328/LER-1982-016, Forwards LER 82-016/03L-0 (← links)
- 05000327/LER-1982-017, Forwards LER 82-017/03L-0 (← links)
- 05000327/LER-1982-020-03, /03L-0:on 820203,emergency Gas Treatment Sys Room Cooler Declared Inoperable Due to Fuses Blowing in Coolers Control Circuitry.Caused by Shorted Solenoid Coil of 2-FSV-67-338.Coil Replaced (← links)
- 05000327/LER-1982-020, Forwards LER 82-020/03L-0 (← links)
- 05000327/LER-1982-070, Forwards LER 82-070/01T-0 (← links)
- 05000327/LER-1982-018, Forwards LER 82-018/03L-0 (← links)
- 05000328/LER-1982-013-03, /03L-0:on 820118,steam Generator 3 Feedwater Flow Transmitter Loop 2-FT-3-90A Declared Inoperable.Caused by Frozen Sense Lines.Lines Thawed & Insulation Added.Design Change Request Initiated (← links)