Pages that link to "05000327/LER-1982-053, Forwards LER 82-053/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000327/LER-1982-053, Forwards LER 82-053/03L-0:
Displayed 8 items.
- ML20052H665 (redirect page) (← links)
- ML20052H671 (← links)
- ML20054L654 (← links)
- 05000327/LER-1982-053-03, /03L-0:on 820415,vital Battery Bank II Declared Inoperable When Cell 4 Connection Resistance Found Greater than 150 micro-ohms.Caused by Loose Bolt Connection.Bolt Torqued & Resistance Checked (← links)
- 05000327/LER-1982-053, Forwards LER 82-053/03L-0 (← links)
- 05000328/LER-1982-049-03, /03L-0:on 820330,w/unit in Mode 1 at 30% Reactor Power,One Upper Containment Airlock Door Found Jammed Closed.Caused by Failure of CAM Roller Bearing in Operating Mechanism.Bearing Replaced & Door Satisfactorily Tested (← links)
- 05000327/LER-1982-053-03, /03L-0:on 820415,vital Battery Bank II Declared Inoperable When Cell 4 Connection Resistance Found Greater than 150 micro-ohms.Caused by Loose Bolt Connection.Bolt Torqued & Resistance Checked (← links)
- 05000327/LER-1982-053 (redirect page) (← links)
- 05000328/LER-1982-032, Forwards LER 82-032/03L-0 (← links)
- 05000327/LER-1982-050-03, /03L-0:on 820413,diesel Generator 1A.A Declared Inoperable When Power Fuses Blew in Control Circuitry.Caused by Broken Lead on Annunciator Horn Shorting to Case.Horn Replaced (← links)
- 05000327/LER-1982-050, Forwards LER 82-050/03L-0 (← links)
- 05000327/LER-1982-048-03, /03L-0:on 820408,at 100% Power,Automatic Control Valve 1-PCV-3-132 in Auxiliary Feedwater Sys Flowpath Failed to Open on Demand.Caused by Faulty Soldered Amphenol Connector to Electrohydraulic Actuator.Connector Repaired (← links)