- 05000295/LER-1981-029-99, /99X-0:on 810528,inverter 114 Failed,Yielding Safety Injection.Caused by Primary Winding of Master Sola Transformer Which Shorted to Ground,Tripping Inverter & Causing Slave Transformer to Burn Up (← links)
- ML20010A503 (redirect page) (← links)
- 05000295/LER-1981-029 (redirect page) (← links)
- 05000304/LER-1981-016-03, /03L-0:on 810706,reactor Coolant Sample Containment Isolation Valve Failed to Close within Allowable Time Limits.Cause Unknown.Lubrication & Loosening of Packing Allowed Operability for 3 Days Before Problem Reoccurred (← links)
- 05000304/LER-1981-015, Forwards LER 81-015/99X-0 (← links)
- 05000295/LER-1981-032-03, /03L-0:on 810629,RCS Charging Pump 1A Balancing Drum Line Was Found Leaking from Circumferential Indication Upstream of Weld Connecting Line to Suction of Pump Casing. Caused by Vibration of Drum Piping.Piping Repaired (← links)
- 05000295/LER-1981-032, Forwards LER 81-032/03L-0 (← links)
- 05000304/LER-1981-014-03, /03L-0:on 810619,svc Water Inlet Valve to RCFC, 2MOVSW0002,failed to Stroke Open on Train B Actuation Signal Per Tech Spec,During Quarterly Safeguard Surveillance.Cause Not Determined (← links)
- 05000304/LER-1981-014, Forwards LER 81-014/03L-0 (← links)
- 05000295/LER-1981-004, Forwards Updated LER 81-004/03X-1 (← links)
- 05000304/LER-1981-013-03, /03L-0:on 810619,steam Generator 2B Level Indication 2LI-548 Found Shifting W/Start & Stops of Containment Fan Cooler 2E.Caused by Defective Transmitter Due to Bad Force Motor (← links)
- 05000304/LER-1981-013, Forwards LER 81-013/03L-0 (← links)
- 05000295/LER-1981-023-03, /03L-0:on 810422,discrepancies in PT-210 Were Not Reported.Fan Dampers Failed to Open on Fan Start,Fan Failed to Start & Relief Dampers Failed to Close on Fan Trip.Caused by Lack of Tech Spec Directions.Mods Under Investigat (← links)
- 05000304/LER-1981-010-03, /03L-0:on 810513,following Maint Functional Tests, Loop B Overpower/Temp Delta T Channel Became Erratic.Cause Not Known.Channel Monitored for 84-h W/O Recurrence,Verified Operable & Returned to Svc (← links)