Pages that link to "05000295/LER-1981-011, Forwards LER 81-011/03L-0"
Jump to navigation
Jump to search
The following pages link to 05000295/LER-1981-011, Forwards LER 81-011/03L-0:
Displayed 50 items.
- 05000304/LER-1981-002-03, /03L-0:on 810227,during Surveillance of Purge Iodine Rad Monitor 2RT-PR09B,monitor Found Reading Low by Factor of Almost 3.Cause Unknown But Probably Just Normal Electronic Variation.Monitor Recalibr (← links)
- 05000304/LER-1981-002, Forwards LER 81-002/03L-0 (← links)
- 05000295/LER-1981-011-03, /03L-0:on 810317,pump for Turbine Bldg Air Sampler Found Off.Cause Unknown.Sample Filters Replaced & Pump Turned Back On.Addl Surveillance Being Instituted (← links)
- ML20038B572 (redirect page) (← links)
- 05000295/LER-1981-011 (redirect page) (← links)
- 05000304/LER-1981-001-03, /03L-0:on 810114,during Power Operation,Loop D Overtemp Delta T Channel 2T-431C Was Indicating Erratically Low by 15%.Cause Not Found.Sys Being Monitored for Similar Events (← links)
- 05000304/LER-1981-026-03, /03L-0:on 811022,during Refueling Calibr,Feedwater Flow Loop Found Reading High.Caused by Zero Shift on Flow Transmitter (Fisher-Porter Model B2496) & Output Drift on Square Root Extractor (Hagan 127-112) (← links)
- 05000304/LER-1981-026, Forwards LER 81-026/03L-0 (← links)
- 05000295/LER-1981-046, Forwards LER 81-046/03L-0 (← links)
- 05000295/LER-1981-045-01, /01T-0:on 811026,FSAR LOCA Analysis Assumed Time of 45-s for Containment Spray Flow Delivery to Containment, Less than Actual Time Required.Caused by FSAR Erroneous Assumption of Flow Start Time After Accident (← links)
- 05000295/LER-1981-044-03, /03L-0:on 811006,instrument Failure Alarm on Failed Fuel Liquid Rad Monitor 1RT-PR27 Would Not Reset. Caused by Stuck Flow Switch Due to Boric Acid Buildup.Boric Acid Cleared & Mechanism Adjusted (← links)
- 05000295/LER-1981-044, Forwards LER 81-044/03L-0 (← links)
- 05000304/LER-1981-025-03, /03L-0:on 811003,during Cold Shutdown,Shiftly Grab Sample Was Not Taken for Pipe Tunnel Iodine Rad Monitor 2 RT-PRO7B.Caused by Personnel Failure to Review Surveillance Form.Personnel Reinstructed (← links)
- 05000304/LER-1981-025, Forwards LER 81-025/03L-0 (← links)
- 05000304/LER-1981-024, Forwards LER 81-024/03L-0 (← links)
- 05000304/LER-1981-023-03, /03L-0:on 810913,reactor Coolant Boron Sample Not Obtained on Second Shift.Caused by Normal Sampling Path Being Isolated Due to Mod on Sampling Sys.Alternate Sample Point Isolated for Repairs (← links)
- 05000304/LER-1981-023, Forwards LER 81-023/03L-0 (← links)
- 05000295/LER-1981-043-03, /03L-0:on 810909,operator Attempted to Close RCDT to Waste Gas Containment Isolation Valve 1DT-9160A & Valve Failed to Close.Caused by Asco Model LB83146 Solenoid Valve on Airline to Valve Operator Apparent Failure to Vent (← links)
- 05000295/LER-1981-043, Forwards LER 81-043/03L-0 (← links)
- 05000295/LER-1981-041, Forwards LER 81-041/03L-0 (← links)
- 05000304/LER-1981-022, Forwards LER 81-022/03L-0 (← links)
- 05000295/LER-1981-042, Forwards LER 81-042/03L-0 (← links)
- 05000304/LER-1981-021-03, /03L-0:on 810903,during Test of Diesel Generator Cardox Sys,Diesel Room 2B Supply Fan Damper Failed in Open Position.Caused by Instrument Air Valve Valving Out (← links)
- 05000304/LER-1981-021, Forwards LER 81-021/03L-0 (← links)
- 05000304/LER-1981-020-01, /01T-0:on 810914,three Auxiliary Feedwater Pumps Failed to Start.Caused by Failure to Detect Flaw in Control Circuitry of Pumps 2B & 2C & Pressure Switch Drift in 2A. Failures Not Related.Circuit Temporarily Modified (← links)
- 05000304/LER-1981-020, Forwards LER 81-020/01T-0 (← links)
- 05000295/LER-1981-040-03, /03L-0:on 810830 & 0905,loop B Overtemp Delta T Indicator Found Reading Higher than Other Indicators.Caused by Deviation from Normal Gain Characteristics of Function Generator,Hagen Model 127-113.Generator Replaced (← links)
- 05000295/LER-1981-040, Forwards LER 81-040/03L-0 (← links)
- 05000295/LER-1981-039, Forwards LER 81-039/01T-0 (← links)
- 05000295/LER-1981-037, Forwards LER 81-037/03L-0 (← links)
- 05000295/LER-1981-036, Forwards LER 81-036/03L-0 (← links)
- 05000295/LER-1981-038-01, /01T-0:on 810817,containment Isolation Valve for Prompt Relief Trip Gas Space Sampling Failed to Close. Probably Caused by Incorrect Installation of Gas Analyzer Panel Due to Use of Uncontrolled Drawings (← links)
- 05000295/LER-1981-030-03, /03L-0:on 810524,breaker Failed & Would Not Reclose After Circuit Supplying Diesel Generator Control Panel 1B Was Turned Off During Dc Ground Procedure on Dc Bus 112.Caused by Mechanical Breaker Failure (← links)
- 05000295/LER-1981-030, Forwards LER 81-030/03L-0 (← links)
- 05000295/LER-1981-031, Forwards LER 81-031/03X-1 (← links)
- 05000295/LER-1981-035-03, /03L-0:on 810806,containment Gas & Particulate Radiation Monitor 1RE-0011 & 12 Failed.Caused by Monitor Blower Tripping Due to Mechanical Seizure.New Blower Installed & Monitor Reset (← links)
- 05000295/LER-1981-035, Forwards LER 81-035/03L-0 (← links)
- 05000304/LER-1981-018-03, Blower for Containment Particulate & Gas Radiation Monitor 2RE0011 & 12 Tripped. Caused by Overpressure Due to Filter Paper Jamming Transport Mechanism.Mechanism Unjammed & Paper Path Cleared (← links)
- 05000304/LER-1981-018, Forwards Updated LER 81-018/03X-1 (← links)
- 05000295/LER-1981-034-03, /03L-0:on 810803,gas Decay Tank Cubicle Radiation Monitor ORT-PR02B Indicated High.Caused by Monitor Drifting Out of Calibr.Monitor Recalibr,Tested & Returned to Svc on 810817 (← links)
- 05000295/LER-1981-034, Forwards LER 81-034/03L-0 (← links)
- 05000304/LER-1981-008-03, Unit 2 Tripped & Safety Injected,Causing One Feedwater Pump to Tripp.Caused by Loss of Inverter 213 Due to High Inverter Circulating Current. Tuning Adjustments Made (← links)
- 05000304/LER-1981-008, Forwards Updated LER 81-008/03X-2 (← links)
- 05000304/LER-1981-017, Forwards LER 81-017/03L-0 (← links)
- 05000295/LER-1981-033-03, /03L-0:on 810708,while Radiation Monitor 1RE0019 Was Inoperable,Manual Grab Sample Not Taken.Caused by Personnel Misunderstanding of Terms Out of Svc & Inoperative.Personnel Reinstructed (← links)
- 05000295/LER-1981-033, Forwards LER 81-033/03L-0 (← links)
- 05000295/LER-1981-029-99, /99X-0:on 810528,inverter 114 Failed,Yielding Safety Injection.Caused by Primary Winding of Master Sola Transformer Which Shorted to Ground,Tripping Inverter & Causing Slave Transformer to Burn Up (← links)
- 05000295/LER-1981-029, Forwards LER 81-029/99X-0 (← links)
- 05000304/LER-1981-016-03, /03L-0:on 810706,reactor Coolant Sample Containment Isolation Valve Failed to Close within Allowable Time Limits.Cause Unknown.Lubrication & Loosening of Packing Allowed Operability for 3 Days Before Problem Reoccurred (← links)
- 05000304/LER-1981-015, Forwards LER 81-015/99X-0 (← links)